Plan Review Details - Permit 02080120
| Plan Review Stops For Permit 02080120 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-08-29 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2002-08-29 |
Time |
15:27 |
Rev Time |
0.50 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-08-12 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-08-09 |
Time |
07:59 |
Rev Time |
0.75 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-08-12 00:00:00 | ****FAILED*********** | | | | | | 1. NEED CONTRACT TO VERIFY VALUE OF | | | PERMIT (LABOR & MATERIALS) | | | 2. NEED DETAIL SHOWN ON PLANS FOR | | | COMPLIANCE OF BARRIER PER FBC2001. | | | 3. DETAIL OF SLAB & ANCHORING OF POOL | | | EQUIPMENT MUST BE SHOWN ON PLANS. | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLAN EXAMINER | | | 659-8096 EXT. 8394 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2002-08-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-08-09 |
Time |
07:59 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-08-09 |
Time |
07:23 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-08-29 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2002-08-29 |
Time |
07:18 |
Rev Time |
0.75 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-08-29 00:00:00 | RE-SUB APPR,PES. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2002-08-23 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2002-08-23 |
Time |
06:49 |
Rev Time |
0.75 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-08-23 00:00:00 | PLUMBING PLAN REVIEW. DENIED FBC 2001 | | | 1) FBC-2001424.2.6.6.5 WHERE PROVIDED | | | THE VACUUM OR PRESSURE CLEANER FITTING | | | SHALL BE LOCATED AT LEAST 6" AND NOT | | | GREATER THAN 12" BELOW THE MINIMUM OPER- | | | ATING WATER LEVEL OR AS AN ATTACHMENT TO | | | THE SKIMMER. | | | 2) FBC-2001424.2.6.6.4 MINIMUM OF TWO | | | SUCTION INLETS SHALL BE PROVIDED FOR EA | | | PUMP. SEPARATED BY A MINIMUM OF 3 FEET | | | OR LOCATED ON TWO DIFFERENT PLANES. | | | (DETAIL) | | | 3) FBC-2001 SEC 424.2.6.6 ENTRAPMENT | | | PROTECTION FOR SUCTION INLETS. (DETAIL) | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X 8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-08-08 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2002-08-08 |
Time |
10:30 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-08-08 00:00:00 | PLUMBING PLAN REVIEW, DENIED FBC 2001 | | | PLEASE ADJUST YOUR NOTES, DETAILS, OR | | | SUBMITTALS TO REFLECT THE FOLLOWING IN- | | | FORMATION REQUIRED FOR PLAN REVIEW | | | 1) FBC-2001 424.2.7.2 PUMPS AND EQUIP- | | | MENT SHALL BE MOUNTED ON A SUBSTANTIAL | | | BASE IN A MANNER THAT WILL ELIMINATE | | | STRAIN ON PIPING. SLAB SHALL BE A NOMIN- | | | AL 4" THICK. (DETAIL) | | | 3) FBC-2001 424.2.12.1 PRESSURE TESTS. | | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | | FITTINGS. (ADD TO NOTES) | | | 4) FBC-2001424.2.6.6.5 WHERE PROVIDED | | | THE VACUUM OR PRESSURE CLEANER FITTING | | | SHALL BE LOCATED AT LEAST 6" AND NOT | | | GREATER THAN 12" BELOW THE MINIMUM OPER- | | | ATING WATER LEVEL OR AS AN ATTACHMENT TO | | | THE SKIMMER. | | | 5) FBC-2001 424.2.9 WATER SUPPLY, LOCAL | | | ORD. #2853-95, BACKFLOW REQUIRED ON | | | WATER SERVICE. (ADD TO NOTES) | | | 6) FBC-2001 424.2.13.2JOINTS AND CON- | | | NECTIONS, FBC PLMG SEC 605.21, PURPLE | | | PRIMER REQUIRED ON PVC PIPING. (ADD TO | | | NOTES) | | | END OF COMMENTS PAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-08-05 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-08-05 |
Time |
13:24 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|