| 2002-09-05 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) SHEET S3 REFERS TO STANDARD BUILDING |
| | CODE.AMEND PLANS TO REFER TO FLORIDA |
| | BUILDING CODE 2001, INCLUDING TIMBER AND |
| | WOOD NOTE 4, WOOD FRAMING NOTE 2, DESIGN |
| | DATA NOTES 8 AND 9. |
| | |
| | 3) FBC 13-103.0ENERGY CODE COMPLIANCE |
| | FORM.THE FOLLOWING INFORMATION SHALL |
| | BE COMPLETED ON THE SUBMITTED FORM: |
| | CLIMATE ZONE IS 8, ENTER BUILDER'S |
| | NAME, ENTER PERMITTING OFFICE AS WEST |
| | PALM BEACH, ENTER PERMIT NO. AS |
| | 02080117, ENTER JURISDICTION NO. AS |
| | 604700 |
| | |
| | 4) FBC 13-103.1.2BEFORE A BUILDING |
| | PERMIT CAN BE ISSUED, THE SUBMITTED |
| | ENERGY CODE COMPLIANCE FORMS SHALL BE |
| | SIGNED BY THE BUILDING OWNER, THE |
| | OWNER'S ARCHITECT OR OTHER AUTHORIZED |
| | AGENT LEGALLY DESIGNATED BY THE OWNER. |
| | |
| | 5) THE SUBMITTED PRODUCT APPROVALS ARE |
| | FOR THE SINGLE HUNG WINDOWS AND SLIDING |
| | GLASS DOOR ONLY.SUBMIT TWO COPIES OF |
| | PRODUCT APPROVALS FOR THE ROOFING, |
| | FRENCH DOORS, GLASS BLOCK WINDOWS AND |
| | A MULLION FOR DEN REAR WINDOW (SEE |
| | COMMENT 6, BELOW). |
| | |
| | 6) SINGLE HUNG WINDOW PRODUCT APPROVAL |
| | NOA# 01-0109.01. THE SPECIFIC CONDITIONS |
| | ITEM 3.1 ON PAGE 2 STATES THAT THE |
| | PRODUCT APPROVAL APPLIES TO SINGLE UNIT |
| | APPLICATIONS ONLY.SUBMIT A PRODUCT |
| | APPROVAL APPLICABLE TO THE MULLED |
| | WINDOWS AT THE REAR OF THE DEN. |
| | |
| | 7) THE DOOR AND WINDOW SCHEDULES ON |
| | SHEET A2 REFER TO THE SLIDING GLASS DOOR |
| | AS PGT WINGUARD IMPACT APPROVED DOORS, |
| | AND THE SINGLE HUNG WINDOWS AS |
| | WINGUARD/33, .../DBL23 AND .../24. THESE |
| | REFERENCES DO NOT CORRESPOND TO THE |
| | SUBMITTED PRODUCT APPROVALS.AMEND THE |
| | SCHEDULES. |
| | |
| | 8) SHEET A3 - ELEVATIONS, STATES THAT |
| | THE EXISTING WINDOWS ARE TO REMAIN BUT |
| | THIS DOES NOT CORRELATE WITH SHEET A2 - |
| | FLOOR PLAN, WHICH REFERS TO THE EXISTING |
| | WINDOWS AS WINDOW SCHEDULE MARK B. |
| | |
| | 9) FBC 2405.2THE FOLLOWING GLAZING IS |
| | IN A 'HAZARDOUS LOCATION' AND IS |
| | REQUIRED TO BE SAFETY GLASS SATISFYING |
| | THE REQUIREMENTS OF THE CONSUMER PRODUCT |
| | SAFETY COMMISSION 16, CODE OF FEDERAL |
| | REGULATIONS, PART 1201 (CPSC 16-CFR, |
| | PART 1201): |
| | SHOWER DOOR AND FRENCH DOORS (NOTE: |
| | DOOR SCHEDULE REFERS TO BATHROOM |
| | DOOR 'MARK 2' AS A FRENCH DOOR, |
| | SHOULD THIS REFERENCE BE FOR |
| | EXTERIOR DOOR 'MARK 5' INSTEAD?) |
| | SUBMIT DETAILS TO DEMONSTRATE COMPLIANCE |
| | WITH THE REQUIREMENT FOR SAFETY GLAZING. |
| | |
| | 10) FBC 2309.6ATTIC ACCESS.AMEND THE |
| | PLANS TO SHOW AN ACCESS, TO THE ADDITION |
| | ATTIC, NOT LESS THAN 20"X36" OPENING. |
| | |
| | 11) FBC* TABLE 2306.1ROOF SHEATHING |
| | NAILING SCHEDULE ON SHEET S2 SHOULD |
| | READ: |
| | ZONE 1&2: 8D COMMON @ 6"O.C. EDGES |
| | 6"O.C. INTERMED. |
| | ZONE 3: 8D COMMON @ 4"O.C. EDGES |
| | 6"O.C. INTERMED. |
| | AMEND SCHEDULE TO DEMONSTRATE COMPLIANCE |
| | |
| | 12) FBC* 104.2.1.2TRUSS ANCHORS.ADD |
| | UPLIFT MAGNITUDES TO SHEET S2 - ROOF |
| | FRAMING PLAN AT TRUSS AND BEAM SUPPORTS. |
| | |
| | 13) SHEET S2, DETAIL 3.THE NOTE |
| | SPECIFIES 4-1/2" DIA J-BOLTS.AMEND THE |
| | SECTIONAL VIEW TO SHOW TWO ROWS OF BOLTS |
| | TO CORRELATE WITH THE NOTE. |
| | |
| | 14) SHEET A4, DETAIL 1 - FILLED CELL |
| | REINFORCEMENT.ANNOTATE THE PLANS TO |
| | SHOW THE #5 VERTICAL BARS TO HAVE MIN. |
| | 25" LAP WITH THE FOOTING DOWEL AND MIN. |
| | OF A STANDARD HOOK WITH 10" LONG LEG |
| | EMBEDDED 6' INTO THE TIE BEAM. |
| | |
| | 15) FBC 1007.4.2NEW STAIR RISERS AT |
| | THE LAUNDRY ROOM.THE DOOR SHALL NOT |
| | SWING OVER THE STAIR. |
| | |
| | 16) SHEET S1 - FOUNDATION PLAN.THE |
| | COLUMNS IN THE COVERED DECK AREA SHOULD |
| | BE C-3 NOT C-1. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |