Plan Review Details - Permit 02080117
Plan Review Stops For Permit 02080117
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-12-02 Cont ID  
Sent By rbrown Date 2002-12-02 Time 10:33 Rev Time 0.00
Received By rbrown Date 2002-12-02 Time 10:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-11-21 Cont ID  
Sent By rbrown Date 2002-11-21 Time 09:27 Rev Time 0.00
Received By rbrown Date 2002-11-21 Time 09:27 Sent To  
Notes
2002-11-21 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 9/5/02:
  
 2) SHEET S3, DESIGN DATA NOTE 9 STILL
 STATES A DESIGN WIND SPEED OF 110 MPH.
 UNDER FLORIDA BUILDING CODE THE BASIC
 WIND SPEED FOR THE CITY OF WEST PALM
 BEACH IS 140 MPH (REF: FBC* 1606.1.6).
 AMEND THE PLANS.NOTE THAT FBC 1606.1.7
 REQUIRES THAT THE BASIC WIND SPEED,
 IMPORTANCE FACTOR, AND WIND EXPOSURE
 CATEGORY ALL BE STATED ON THE PLANS.
  
 7) THE DOOR AND WINDOW SCHEDULES ON
 SHEET A2 REFER TO THE SLIDING GLASS DOOR
 AS 'PGT WINGUARD IMPACT APPROVED DOORS'
 AND THE SINGLE HUNG WINDOWS AS
 'WINGUARD/33, .../DBL23 AND .../24'.
 THESE PRODUCTS HAVE REFERENCES WHICH ARE
 DIFFERENT TO THE SUBMITTED PRODUCT
 APPROVALS AND ARE THEREFOR NOT COVERED
 BY THOSE APPROVALS.AMEND THE SCHEDULES
 OR SUBMIT RELEVANT PRODUCT APPROVALS.
  
 12) FBC* 104.2.1.2TRUSS ANCHORS.THE
 FACT THAT THE UPLIFTS ARE GIVEN IN THE
 TRUSS SHOP DRAWING NOTES IS ACKNOWLEDGED
 THE ROOF FRAMING PLAN ON SHEET S2, SHALL
 BE AMENDED TO SHOW THE UPLIFT AND THE
 CONNECTOR MARK (ANCHOR REFERENCE), FROM
 THE ANCHOR SCHEDULE ON SHEET S3, FOR
 EACH TRUSS OR GROUP OF TRUSSES.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-09-05 Cont ID  
Sent By btrobaug Date 2002-11-12 Time 17:39 Rev Time 0.00
Received By rbrown Date 2002-09-05 Time 16:47 Sent To  
Notes
2002-09-05 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) SHEET S3 REFERS TO STANDARD BUILDING
 CODE.AMEND PLANS TO REFER TO FLORIDA
 BUILDING CODE 2001, INCLUDING TIMBER AND
 WOOD NOTE 4, WOOD FRAMING NOTE 2, DESIGN
 DATA NOTES 8 AND 9.
  
 3) FBC 13-103.0ENERGY CODE COMPLIANCE
 FORM.THE FOLLOWING INFORMATION SHALL
 BE COMPLETED ON THE SUBMITTED FORM:
 CLIMATE ZONE IS 8, ENTER BUILDER'S
 NAME, ENTER PERMITTING OFFICE AS WEST
 PALM BEACH, ENTER PERMIT NO. AS
 02080117, ENTER JURISDICTION NO. AS
 604700
  
 4) FBC 13-103.1.2BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 5) THE SUBMITTED PRODUCT APPROVALS ARE
 FOR THE SINGLE HUNG WINDOWS AND SLIDING
 GLASS DOOR ONLY.SUBMIT TWO COPIES OF
 PRODUCT APPROVALS FOR THE ROOFING,
 FRENCH DOORS, GLASS BLOCK WINDOWS AND
 A MULLION FOR DEN REAR WINDOW (SEE
 COMMENT 6, BELOW).
  
 6) SINGLE HUNG WINDOW PRODUCT APPROVAL
 NOA# 01-0109.01. THE SPECIFIC CONDITIONS
 ITEM 3.1 ON PAGE 2 STATES THAT THE
 PRODUCT APPROVAL APPLIES TO SINGLE UNIT
 APPLICATIONS ONLY.SUBMIT A PRODUCT
 APPROVAL APPLICABLE TO THE MULLED
 WINDOWS AT THE REAR OF THE DEN.
  
 7) THE DOOR AND WINDOW SCHEDULES ON
 SHEET A2 REFER TO THE SLIDING GLASS DOOR
 AS PGT WINGUARD IMPACT APPROVED DOORS,
 AND THE SINGLE HUNG WINDOWS AS
 WINGUARD/33, .../DBL23 AND .../24. THESE
 REFERENCES DO NOT CORRESPOND TO THE
 SUBMITTED PRODUCT APPROVALS.AMEND THE
 SCHEDULES.
  
 8) SHEET A3 - ELEVATIONS, STATES THAT
 THE EXISTING WINDOWS ARE TO REMAIN BUT
 THIS DOES NOT CORRELATE WITH SHEET A2 -
 FLOOR PLAN, WHICH REFERS TO THE EXISTING
 WINDOWS AS WINDOW SCHEDULE MARK B.
  
 9) FBC 2405.2THE FOLLOWING GLAZING IS
 IN A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201):
 SHOWER DOOR AND FRENCH DOORS (NOTE:
 DOOR SCHEDULE REFERS TO BATHROOM
 DOOR 'MARK 2' AS A FRENCH DOOR,
 SHOULD THIS REFERENCE BE FOR
 EXTERIOR DOOR 'MARK 5' INSTEAD?)
 SUBMIT DETAILS TO DEMONSTRATE COMPLIANCE
 WITH THE REQUIREMENT FOR SAFETY GLAZING.
  
 10) FBC 2309.6ATTIC ACCESS.AMEND THE
 PLANS TO SHOW AN ACCESS, TO THE ADDITION
 ATTIC, NOT LESS THAN 20"X36" OPENING.
  
 11) FBC* TABLE 2306.1ROOF SHEATHING
 NAILING SCHEDULE ON SHEET S2 SHOULD
 READ:
 ZONE 1&2: 8D COMMON @ 6"O.C. EDGES
 6"O.C. INTERMED.
 ZONE 3: 8D COMMON @ 4"O.C. EDGES
 6"O.C. INTERMED.
 AMEND SCHEDULE TO DEMONSTRATE COMPLIANCE
  
 12) FBC* 104.2.1.2TRUSS ANCHORS.ADD
 UPLIFT MAGNITUDES TO SHEET S2 - ROOF
 FRAMING PLAN AT TRUSS AND BEAM SUPPORTS.
  
 13) SHEET S2, DETAIL 3.THE NOTE
 SPECIFIES 4-1/2" DIA J-BOLTS.AMEND THE
 SECTIONAL VIEW TO SHOW TWO ROWS OF BOLTS
 TO CORRELATE WITH THE NOTE.
  
 14) SHEET A4, DETAIL 1 - FILLED CELL
 REINFORCEMENT.ANNOTATE THE PLANS TO
 SHOW THE #5 VERTICAL BARS TO HAVE MIN.
 25" LAP WITH THE FOOTING DOWEL AND MIN.
 OF A STANDARD HOOK WITH 10" LONG LEG
 EMBEDDED 6' INTO THE TIE BEAM.
  
 15) FBC 1007.4.2NEW STAIR RISERS AT
 THE LAUNDRY ROOM.THE DOOR SHALL NOT
 SWING OVER THE STAIR.
  
 16) SHEET S1 - FOUNDATION PLAN.THE
 COLUMNS IN THE COVERED DECK AREA SHOULD
 BE C-3 NOT C-1.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-03-14 Cont ID  
Sent By btrobaug Date 2003-03-14 Time 17:02 Rev Time 0.50
Received By btrobaug Date 2003-03-14 Time 16:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-08-19 Cont ID  
Sent By sthyng Date 2003-03-14 Time 14:33 Rev Time 0.00
Received By btrobaug Date 2002-08-19 Time 10:49 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-14 Cont ID  
Sent By sthyng Date 2003-03-14 Time 14:33 Rev Time 0.00
Received By sthyng Date 2003-03-14 Time 14:33 Sent To E
Notes
2003-03-14 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-12 Cont ID  
Sent By btrobaug Date 2002-11-12 Time 17:39 Rev Time 0.00
Received By btrobaug Date 2002-11-12 Time 17:39 Sent To B
Notes
2002-11-12 00:00:00TO ROBRT B./WRT

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-06 Cont ID  
Sent By pkrauss Date 2003-03-06 Time 10:56 Rev Time 0.30
Received By pkrauss Date 2003-03-06 Time 10:56 Sent To  
Notes
2003-03-06 00:00:00MECHANICAL REVISION - PERMIT 03011315

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-08-20 Cont ID  
Sent By btrobaug Date 2002-08-19 Time 16:53 Rev Time 0.35
Received By pkrauss Date 2002-08-20 Time 09:57 Sent To B
Notes
2002-08-20 00:00:00PROVISO:
  
 ATTIC ACCESS OPENING SHALL BE NO LESS
 THAN 30" X 22" AS PER 2001 FBC(M) 306.3
  
 2001 FBC CHAPTER 13 610.1.ABC.3.5.2 -
 1. THE SERVICE PANEL OF THE EQUIPMENT IS
 LOCATED WITHIN 6 FT OF AN ATTIC
 ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE
 OWNER OR SHUT DOWN WHEN THE
 CONDENSATE DRAIN IS NOT WORKING
 PROPERLY.
 4. A NOTICE IS POSTED ON THE ELECTRIC
 SERVICE PANEL INDICATING TO THE
 HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-08-08 Cont ID  
Sent By kstevens Date 2002-08-08 Time 09:33 Rev Time 0.00
Received By kstevens Date 2002-08-08 Time 09:33 Sent To  
Notes
2002-08-08 00:00:00PASSED/PROVISO
  
 ANY PORTION OF THE DRAINAGE SYSTEM IN-
 STALLED UNDERGROUND SHALL NOT BE LESS
 THAN 2" IN DIAMETER. SEC. 710.3

Review Stop Z ZONING
Rev No 1 Status P Date 2002-08-19 Cont ID  
Sent By sgraham Date 2002-08-19 Time 09:04 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***