| 2002-08-21 00:00:00 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 02080075 |
| | ADD: 101 N CLEMATIS |
| | CONT: PLAN REVIEW/ TO BE ANNONCED |
| | RENDINA LEASING |
| | TEL: (561)586-2913 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1) CORRIDOR 117 ON THE SHELL IS INDICAT- |
| | ED AS THROUGH THE BUILDING. INDICATE HOW |
| | THE LIFE SAFETY PLAN SHALL BE EFFECTED. |
| | |
| | 2) MAIN ENTRY NOT CONSIDERED A EGRESS |
| | SINCE THE 2HR. FIRE RATED DOOR WILL CUT |
| | OFF THE EXIT. 1004.1.2 TRAVEL DISTANCE |
| | FOR A SINGLE DOOR SHALL NOT EXCEED 75'. |
| | TO THE FURTHEST CORNER OF OFFICE (106) |
| | THE TRAVEL DISTANCE IS 81', REQUIRING |
| | (2) MEANS OF EGRESS.SEE ATTACHED DETAIL. |
| | SINGLE EXIT (BUSINESS 1020.1(4) |
| | |
| | 3) COMMON PATH OF TRAVEL 1004.1.3: |
| | INDICATE THE 2 EXITS TO BE AVAILABLE. |
| | |
| | 4) 2 HR. ROLLING FIRE RATED DOOR, TO BE |
| | HOOKED TO SMOKE / FIRE ALARM RATHER THAN |
| | FUSABLE LINK. SMOKE KILLS BEFORE FIRE! |
| | |
| | 5) OFFICE 116 PLANS INDICATE THIS WALL |
| | AS A NON RATED WALL? CORRIDOR INDICATED |
| | AS RATED? |
| | |
| | 6) OFFICE 116 PLANS INDICATE THE REMOVAL |
| | OF STAIRS, LEADING TO WHERE? IS THERE |
| | A DOORWAY BEING CLOSED, IS THIS A RE- |
| | QUIRED MEANS OF EGRESS FOR THAT UNIT? |
| | IS THIS THE MEANS OF EGRESS FOR THE |
| | RESTRAUNT? |
| | |
| | 7) DOORS 110, 116 RATING?DOOR E NEW?INDI |
| | CATE CHANGE IN GRADE AT DOOR E. |
| | |
| | 8) SH 1 CORRECT THE APPLICABLE CODE. |
| | FLORIDA BUILDING CODE. |
| | |
| | 9)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 10)705.7.1 JOINTS INSTALLED IN OR BE- |
| | TWEEN FIRE RESISTANT WALLS, FIRE RESIS- |
| | TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES |
| | AND FIRE RESISTANT ROOFS OR ROOF/ CEIL- |
| | ING ASSEMBLIES SHALL BE PROTECTED BY AN |
| | APPROVED FIRE RESISTANT JOINT SYSTEM |
| | DESIGNED TO RESIST THE PASSAGE OF FIRE |
| | FOR A PERIOD NOT LESS THAN THE RE- |
| | QUIRED FIRE RESISTANCE RATING OF THE |
| | WALL, FLOOR OR FLOOR IN OR BETWEEN |
| | WHICH IT IS INSTALLED. |
| | |
| | 11)TABLE 803.3 MINIMUM INTERIOR FINISH |
| | CLASSIFICATION; PROVIDE INFORMATION |
| | BASED ON INTERIOR FINISH REQUIREMENTS |
| | BASED ON OCCUPANCY |
| | |
| | 12) TYPE II BUILDING NOT TYPE I, TYPE |
| | II BUILDING, NOTE STUD, BACKING TO BE |
| | NONCOMBUSTIBLE 609.2.1. |
| | |
| | 13)11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. DOOR 101 REQUIRES 18" |
| | CLEAR ON LATCH SIDE. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDEN- |
| | TIFYING THE SHEET OR SPECIFICATION PAGE |
| | WHERE THE CHANGES CAN BE FOUND, WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | JIM WITMER |
| | PLAN REVIEW |
| | TEL: (561)659-8096 EX.8412 |
| | FAX: (561)659-8026 |