Plan Review Details - Permit 02080075
Plan Review Stops For Permit 02080075
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-09-12 Cont ID  
Sent By jwitmer Date 2002-09-12 Time 13:23 Rev Time 1.22
Received By jwitmer Date 2002-09-12 Time 13:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-08-21 Cont ID  
Sent By jwitmer Date 2002-08-21 Time 07:37 Rev Time 2.50
Received By jwitmer Date 2002-08-21 Time 07:36 Sent To  
Notes
2002-08-21 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02080075
 ADD: 101 N CLEMATIS
 CONT: PLAN REVIEW/ TO BE ANNONCED
 RENDINA LEASING
 TEL: (561)586-2913
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) CORRIDOR 117 ON THE SHELL IS INDICAT-
 ED AS THROUGH THE BUILDING. INDICATE HOW
 THE LIFE SAFETY PLAN SHALL BE EFFECTED.
  
 2) MAIN ENTRY NOT CONSIDERED A EGRESS
 SINCE THE 2HR. FIRE RATED DOOR WILL CUT
 OFF THE EXIT. 1004.1.2 TRAVEL DISTANCE
 FOR A SINGLE DOOR SHALL NOT EXCEED 75'.
 TO THE FURTHEST CORNER OF OFFICE (106)
 THE TRAVEL DISTANCE IS 81', REQUIRING
 (2) MEANS OF EGRESS.SEE ATTACHED DETAIL.
 SINGLE EXIT (BUSINESS 1020.1(4)
  
 3) COMMON PATH OF TRAVEL 1004.1.3:
 INDICATE THE 2 EXITS TO BE AVAILABLE.
  
 4) 2 HR. ROLLING FIRE RATED DOOR, TO BE
 HOOKED TO SMOKE / FIRE ALARM RATHER THAN
 FUSABLE LINK. SMOKE KILLS BEFORE FIRE!
  
 5) OFFICE 116 PLANS INDICATE THIS WALL
 AS A NON RATED WALL? CORRIDOR INDICATED
 AS RATED?
  
 6) OFFICE 116 PLANS INDICATE THE REMOVAL
 OF STAIRS, LEADING TO WHERE? IS THERE
 A DOORWAY BEING CLOSED, IS THIS A RE-
 QUIRED MEANS OF EGRESS FOR THAT UNIT?
 IS THIS THE MEANS OF EGRESS FOR THE
 RESTRAUNT?
  
 7) DOORS 110, 116 RATING?DOOR E NEW?INDI
 CATE CHANGE IN GRADE AT DOOR E.
  
 8) SH 1 CORRECT THE APPLICABLE CODE.
 FLORIDA BUILDING CODE.
  
 9)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 10)705.7.1 JOINTS INSTALLED IN OR BE-
 TWEEN FIRE RESISTANT WALLS, FIRE RESIS-
 TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES
 AND FIRE RESISTANT ROOFS OR ROOF/ CEIL-
 ING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
  
 11)TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 12) TYPE II BUILDING NOT TYPE I, TYPE
 II BUILDING, NOTE STUD, BACKING TO BE
 NONCOMBUSTIBLE 609.2.1.
  
 13)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL. DOOR 101 REQUIRES 18"
 CLEAR ON LATCH SIDE.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-09-11 Cont ID  
Sent By dpalmer Date 2002-09-11 Time 17:26 Rev Time 0.50
Received By dpalmer Date 2002-09-11 Time 17:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-08-13 Cont ID  
Sent By dpalmer Date 2002-08-13 Time 13:15 Rev Time 0.00
Received By dpalmer Date 2002-08-13 Time 13:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-09-12 Cont ID  
Sent By mcarsill Date 2002-09-12 Time 16:04 Rev Time 0.00
Received By mcarsill Date 2002-09-12 Time 16:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-08-22 Cont ID  
Sent By mcarsill Date 2002-08-22 Time 11:38 Rev Time 0.00
Received By mcarsill Date 2002-08-22 Time 11:38 Sent To  
Notes
2002-08-22 00:00:00PLEASE SEE BUILDING PLAN REVIEW
 COMMENTS. THIS OFFICE CONCURS WITH
 THIS REVIEW. PLEASE REVISE AND CORRECT
 PLANS AS NECESSARY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-09-23 Cont ID  
Sent By pkrauss Date 2002-09-23 Time 13:29 Rev Time 0.40
Received By pkrauss Date 2002-09-23 Time 13:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-08-22 Cont ID  
Sent By pkrauss Date 2002-08-22 Time 09:43 Rev Time 0.35
Received By pkrauss Date 2002-08-22 Time 09:29 Sent To  
Notes
2002-08-22 00:00:00PROVISO:
  
 PLAN SHEET M-2 FRESH AIR CALCULATIONS -
 AHU 1 SERVICES 2 OFFICES ACCORDING TO
 THE SCHEDULE, THE PLAN INDICATES AHU 1
 SERVES 4 OFFICES & THE LUNCHROOM.AHU
 2 THE SCHEDULE INDICATES 2 OFFICES, THE
 PLAN SHOWS 2 OFFICES, SEC'Y, RECEPTION,
 WAITING RM, CONF, & A WORKRM.PLEASE
 CLARIFY THAT FRESH AIR CALCS ARE
 CORRECT.
  
 PLAN SHEET M-2 DETAIL FOR THE AHU -
 PLEASE NOTE, EMERGENCY DRAIN TO
 TERMINATE AT A CONSPICUOUS POINT AS PER
 2001 FBC(M) 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-09-11 Cont ID  
Sent By pschmitz Date 2002-09-11 Time 07:10 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-09-11 00:00:00RE-SUB,APPR,PES.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-08-15 Cont ID  
Sent By kstevens Date 2002-08-15 Time 12:18 Rev Time 0.00
Received By kstevens Date 2002-08-15 Time 12:18 Sent To  
Notes
2002-08-15 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SERVICE SINK REQUIRED PER TABLE
 403.1
 2) SHT 3.1 DOOR FROM CLOSET ROOM #111
 SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE FOR BREAK ROOM SINK.
 3)SHT 8.1 DETAIL #1 LUNCHROOM SINK SHALL
 COMPLY COMPLY WITH 11-4.24 AND ALL SUB-
 SECTIONS.
 4) SHT P-2 FLOOR SINK SHOWN ON SANT.
 RISER DIAGRAM BUT NOT ON FLOOR PLAN.
 PLEASE CLAIRFY.
 5) PLEASE PROVIDE DETAIL FOR DRINKING
 FOUNTAIN. SHOW COMPLIANCE WITH 11-4.15
 AND ALL SUBSECTIONS. PROVISIONS SHALL BE
 MADE FOR THOSE WHO HAVE DIFFICULTY BEND-
 ING OR STOOPING. 11-4.1.3(10)(A).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377