Plan Review Details - Permit 02071919
Plan Review Stops For Permit 02071919
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-10-31 Cont ID  
Sent By mcarsill Date 2002-10-31 Time 09:07 Rev Time 0.00
Received By mcarsill Date 2002-10-31 Time 09:07 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 2 Status P Date 2002-11-01 Cont ID  
Sent By mcarsill Date 2002-11-01 Time 10:59 Rev Time 0.00
Received By mcarsill Date 2002-11-01 Time 10:59 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 1 Status F Date 2002-08-01 Cont ID  
Sent By mcarsill Date 2002-08-01 Time 11:35 Rev Time 0.00
Received By mcarsill Date 2002-08-01 Time 11:34 Sent To  
Notes
2002-08-01 00:00:001) THE FIRE DEPARTMENT SPRINKLER
 CONNECTION FOR THE CLUBHOUSE SHALL NOT
 EXCEED 150 FEET TO A FIRE HYDRANT. ALSO
 THE LOCATION OF THE FIRE DEPARTMENT
 CONNECTION APPEARS TO BE CONTRARY
 TO THE MAIN ENTRANCE AND THE FIRST
 FIRE HYDRANT THAT IS NEAREST THE
 CLUBHOUSE. PLEASE ADJUST AS NECESSARY.
  
 2) ALL FIRE DEPARTMENT CONNECTIONS AND
 POST INDICATOR VALVES SHALL BE
 PROVIDED WITH SEVEN AND HALF FEET
 CLEARANCES IN FRONT AND TO THE SIDES
 OF THEM.
  
 3) BACKFLOW DEVICES ARE REQUIRED TO BE
 EQUIPPED WITH TAMPER SWITCHES, CHAINS
 AND LOCKS.
  
 4) THE COVERED WALK NEAR THE GATHERING
 AREA APPEARS TO BE OVER FOUR FEET
 WIDE. IF THIS COVERED WALK IS
 COMBUSTIBLE FIRE SPRINKLER PROTECTION
 IS REQUIRED.
  
 5) ALL EXTERIOR SPRINKLER HEADS SHALL
 BE CORROSION RESISTANT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-10-31 Cont ID  
Sent By mcarsill Date 2002-10-31 Time 09:08 Rev Time 0.00
Received By mcarsill Date 2002-10-31 Time 09:07 Sent To  
Notes
***NONE***