Plan Review Details - Permit 02071916
Plan Review Stops For Permit 02071916
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-10-11 Cont ID  
Sent By btrobaug Date 2002-10-16 Time 16:59 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-08-19 Cont ID  
Sent By jwitmer Date 2002-08-19 Time 07:11 Rev Time 1.00
Received By jwitmer Date 2002-08-19 Time 07:10 Sent To  
Notes
2002-08-19 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02071916
 ADD: 3816/3900 N FLAGLER
 CONT: TITAN CONSTRUCTION GROUP
 TEL: (561)243-9446
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
  
 2)STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL
 BE REQUIRED. A5 FLOODZONE MINIMUM ELEVA-
 TION 7'-6" FOR BOTTOM OF MANUFACTURED
 BUILDING. FOR ANY A/C PAD THIS ELEVATION
 MUST BE MET.
  
 3)11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENTRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY. INDICATE HOW THE HANDICAPPED
 WILL MAKE THERE WAY ONTO THE PROPERTY
 FROM THE STREET ( PUBLIC TRANSPORTATION)
 INTO THE SALES OFFICE, HANDICAPPPED
 PARKING & ACCESS ISLE REQUIREMENTS.
  
 4) 1606.1.4 PROTECTION OF ALL OPENINGS,
 (1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE MUST MEET THE REQUIREMENTS FOR
 LARGE MISSLE TESTING.
  
 5)FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 6) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 7)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 8)SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD.
  
 9)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-10-16 Cont ID  
Sent By btrobaug Date 2002-10-16 Time 16:59 Rev Time 0.50
Received By btrobaug Date 2002-10-11 Time 16:12 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-08-07 Cont ID  
Sent By dpalmer Date 2002-08-07 Time 07:21 Rev Time 0.00
Received By dpalmer Date 2002-08-07 Time 07:21 Sent To  
Notes
2002-08-07 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE NOTE ELECTRICAL PLANS ON
 ASTATE APPROVED BLDG/TRAILER IS EXEMPT
 FROM REVIEW. HOWEVER AN ELECTRICAL
 RISER DIAGRAM IS REQ`D FOR TRAILER
 HOOK UP.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2002-10-22 Cont ID  
Sent By mamini Date 2002-10-22 Time 09:06 Rev Time 1.00
Received By mamini Date 2002-10-22 Time 09:06 Sent To  
Notes
2002-10-22 00:00:00PASSED WITH PROVISOS :
 1. SEE PLANS AS MARKED UP
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2002-09-10 Cont ID  
Sent By mamini Date 2002-09-10 Time 11:09 Rev Time 1.00
Received By mamini Date 2002-09-10 Time 11:08 Sent To  
Notes
2002-09-10 00:00:00FAILED :
 1. PLEASE SHOW THE LOCATION OF BACKFLOW
 PREVENTER ASSEMBLY AND CONNECTION TO
 CITY WATER SUPPLY, MUST BE INSTALLED AT
 POINT OF SERVICE ON PRIVATE PROPERTY,
 APPROVED BY THE CITY, 659-8005 EXT.2008.
 2. PLEASE SHOW LOCATION AND CONNECTION
 TO CITY SEWER SYS. A CLEAN OUT ON
 LATERAL MUST BE PROVIDED.
 3. A SEPARATE BACKFLOW PREVENTER FOR
 IRRIGATION SYS IS RECOMMENDED.
 4. ALL CONNECTION TO THE CITY SERVICES
 MUST BE PER CITY STANDARDS, 659-8040.
 5. TEMPORARY HOLDING TANKS AND WELL
 WATER IF USED WOULD REQUIRE PERMITS FROM
 PALM BEACH COUNTY HEALTH DEPARTMENT.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-10-21 Cont ID  
Sent By mcarsill Date 2002-10-21 Time 16:03 Rev Time 0.00
Received By mcarsill Date 2002-10-21 Time 16:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-08-02 Cont ID  
Sent By mcarsill Date 2002-08-02 Time 13:23 Rev Time 0.00
Received By mcarsill Date 2002-08-02 Time 13:23 Sent To  
Notes
2002-08-02 00:00:001) PLEASE INDICATE IN WRITING HOW
 LONG THE TRAILER WILL BE AT SUBJECT
 LOCATION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-10-17 Cont ID  
Sent By pkrauss Date 2002-10-17 Time 16:55 Rev Time 0.00
Received By pkrauss Date 2002-10-17 Time 16:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-08-26 Cont ID  
Sent By pkrauss Date 2002-08-26 Time 11:56 Rev Time 0.35
Received By pkrauss Date 2002-08-26 Time 11:56 Sent To Z
Notes
2002-08-26 00:00:00PROVIDE MANUFACTURER INFORMATION ON THE
 A/C EQUIPMENT BEING INSTALLED.
  
 INDICATE PACKAGE OR SPLIT SYSTEM.
  
 PLANS INDICATE 2 SYSTEMS WILL BOTH HAVE
 A CAPACITY OF 1005 CFM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-10-17 Cont ID  
Sent By kstevens Date 2002-10-17 Time 16:02 Rev Time 0.50
Received By kstevens Date 2002-10-17 Time 16:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-10-16 Cont ID  
Sent By kstevens Date 2002-10-16 Time 16:53 Rev Time 0.25
Received By kstevens Date 2002-10-16 Time 16:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-10-15 Cont ID  
Sent By kstevens Date 2002-10-15 Time 14:02 Rev Time 0.50
Received By kstevens Date 2002-10-15 Time 14:02 Sent To  
Notes
2002-10-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) HOLDING TANKS WILL BE USED FOR SANT.
 APPROVAL FROM THE HEALTH DEPT SHALL BE
 REQUIRED PRIOR TO RESUBMITTING FOR CITY
 WPB PLAN REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-08-14 Cont ID  
Sent By kstevens Date 2002-08-14 Time 09:07 Rev Time 0.00
Received By kstevens Date 2002-08-14 Time 09:07 Sent To  
Notes
2002-08-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) PLEASE SHOW LOCATION OF SANITARY AND
 WATER TIE IN.
 2) RPZ BACKFLOW REQUIRED ON WATER SERV-
 ICE.
 3) SEPARATE PERMIT REQUIRED FOR IRRIGAT-
 ION. PLUMBING CONTRACTOR SHALL INSTALL
 TIE IN FOR IRR. ON WATER SERVICE WITH A
 VALVE ABOVE GROUND FOR IRR. CONTR. TO
 TIE INTO.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 2 Status P Date 2002-10-21 Cont ID  
Sent By sgraham Date 2002-10-21 Time 16:37 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2002-08-27 Cont ID  
Sent By pkrauss Date 2002-08-26 Time 13:25 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-08-27 00:00:00NEED PLANNING BD APPROVAL