Plan Review Details - Permit 02071727
Plan Review Stops For Permit 02071727
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-02-25 Cont ID  
Sent By nmccray Date 2003-02-25 Time 11:21 Rev Time 0.00
Received By nmccray Date 2003-02-25 Time 11:21 Sent To  
Notes
2003-02-25 00:00:00REVISION TO FIRE ALARM SYSTEM

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-08-13 Cont ID  
Sent By mcarsill Date 2002-08-13 Time 11:40 Rev Time 0.00
Received By mcarsill Date 2002-08-13 Time 11:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-07-30 Cont ID  
Sent By mcarsill Date 2002-07-30 Time 15:51 Rev Time 0.00
Received By mcarsill Date 2002-07-30 Time 15:51 Sent To  
Notes
2002-07-30 00:00:001) THE REQUIRED FIRE ALARM SYSTEM IS
 TO BE MONITORED. RE: NFPA 88A,
 SECTION 5-2.
  
 2) NFPA 88A, REQUIRES THAT THE
 GARAGE HAVE DETECTORS INSTALLED THAT
 ARE ABLE TO SENSE PRODUCTS OF
 COMBUSTION. RE: NFPA 88A, SECTION 5-2.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910