Plan Review Details - Permit 02071593
Plan Review Stops For Permit 02071593
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-08-06 Cont ID  
Sent By hpiskura Date 2002-08-06 Time 11:15 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-08-01 Cont ID  
Sent By dpalmer Date 2002-08-01 Time 06:22 Rev Time 0.00
Received By dpalmer Date 2002-08-01 Time 06:22 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-08-29 Cont ID  
Sent By kstevens Date 2002-08-29 Time 08:55 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-08-09 Cont ID  
Sent By mcarsill Date 2002-08-09 Time 09:25 Rev Time 0.00
Received By mcarsill Date 2002-08-09 Time 09:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-08-29 Cont ID  
Sent By kstevens Date 2002-08-29 Time 08:55 Rev Time 0.00
Received By kstevens Date 2002-08-29 Time 08:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-08-10 Cont ID  
Sent By kstevens Date 2002-08-10 Time 14:30 Rev Time 0.00
Received By kstevens Date 2002-08-10 Time 14:30 Sent To  
Notes
2002-08-10 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) SHT #1 GENERAL NOTES: #6 PLUMBING
 CONTRACTOR RESPONSIBLE FOR 2" WASTE NOT
 GENERAL CONTRACTOR. WASTE SHALL BE PIPED
 TO SANITARY NOT STORM. ALL DRAINS AND
 WASTE TO SANITARY AND OVERFLOW SHALL
 DRAIN TO STORM.
 2) SHT #1 GENERAL NOTES: #7 PLUMBING
 CONTRACTOR SHALL BE RESPONSIBLE FOR 1"
 POTABLE WATER NOT GENERAL CONTRACTOR.
 A BACKFLOW PREVENTER IS REQUIRED FOR
 WATER SERVICE TO FOUNTAIN.
 3) PLUMBING PERMIT IS REQUIRED.
 4) SHT #4 NON-ELECTRIC EQUIPMENT: (ED)
 4" FLOOR DRAIN TO SANITARY SEWER NOT
 FOUND.
 5) SHT #4 GENERAL NOTES: #'S 5, 6, 7, &
 8 ALL REFER TO GENERAL CONTRACTOR BEING
 RESPONSIBLE FOR PLUMBING CONTRACTOR WORK
 PLEASE CLAIRFY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-07-25 Cont ID  
Sent By sgraham Date 2002-07-25 Time 10:08 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***