| 2002-09-30 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THE SCOPE OF WORK ON THE ORIGINAL |
| | APPLICATION WAS FOR REPLACING KITCHEN |
| | CABINETS,AND THE ELECTRICAL PERMIT |
| | APPLICATION STATED "PER PLANS".THERE |
| | WERE NO PLANS SUBMITTED FOR REVIEW |
| | UNTILL THIS SET,AND THE WORK WAS |
| | OBVIOUSLY MORE EXTENSIVE THAN THE |
| | KITCHEN.PLEASE PROVIDE A NEW VALUATION |
| | REFLECTING THE SCOPE OF WORK BEING DONE |
| | PER 104.6.5 CWPB AMMENDMENTS.(ATTACHED). |
| | |
| | 2} PLEASE PROVIDE A PANEL SCHEDULE,AND |
| | INDICATE THE SIZE OF THE SERVICE. |
| | |
| | 3} PLEASE LIST THE REQ'D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3 |
| | MUST BE 20A AND #12AWG.PUT SAME ON PANEL |
| | SCHEDULE. |
| | |
| | 4} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE OR NOTE ON PLANS FOR BRANCH |
| | CIRCUIT PROTECTION. PER 210-12 |
| | |
| | 5} PLEASE INDICATE THE REQUIRED KITCHEN |
| | CICUITS ON PANEL SCHEDULE. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/659-8096 EXT.8392 |