Plan Review Details - Permit 02071311
Plan Review Stops For Permit 02071311
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-08-27 Cont ID  
Sent By mcarsill Date 2002-08-27 Time 11:54 Rev Time 0.00
Received By mcarsill Date 2002-08-27 Time 11:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-07-25 Cont ID  
Sent By mcarsill Date 2002-07-25 Time 13:15 Rev Time 0.00
Received By mcarsill Date 2002-07-25 Time 13:15 Sent To  
Notes
2002-07-25 00:00:001) PLANS DO NOT INDICATE THAT THE
 KITCHEN FIRE SUPRESSION SYSTEM WILL BE
 CONNECTED TO THE FIRE ALARM SYSTEM AS
 REQUIRED BY CODE.
 2) MENS ROOM DISPLAYS A HORN STROBE AND
 THE WOMENS ROOM DISPLAYS A STOBE.
 ELIMINATE THE HORN IN THE MENS ROOM.
 3) PLANS FAIL TO INDICATE ANY DEVICES
 NOTED FOR THE ELEVATOR AND THE PERTINENT
 ELEVATOR MECHANICAL ROOM.
  
 MIKE CARSILLO, CAPTAIN
 659-8096, EXT. 8497
 835-2910