Plan Review Details - Permit 02071120
Plan Review Stops For Permit 02071120
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-07-19 Cont ID  
Sent By jwitmer Date 2002-07-19 Time 07:36 Rev Time 0.50
Received By jwitmer Date 2002-07-19 Time 07:36 Sent To  
Notes
2002-07-19 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02071120
 ADD: 629 EL PRADO
 CONT: O/B VALILUS, MARIE-ANNE
 TEL: 833-8967
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 FLOOR PLAN : INDICATING THE WINDOW PLACE
 MENT, SIZES OF WINDOWS TO BE REPLACED,
 SLEEPING ROOMS FOR EMERGENCY EGRESS,
  
 2)2001 FL BLD CODE, 1005.4:
 PROVIDE EMERGENCY EGRESS WINDOWS IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGTH OF 24" AND NET CLEAR
 OPENING WIDTH OF 20" AND A NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH
 SHALL NOT BE MORE THAN 44 " ABOVE THE
 FINISH FLOOR.
  
 3)FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 4) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.
  
 5)SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD.THE FORM FROM HURRICANE TEST-
 ING LAB WILL REQUIRE SITE SPECIFIC
 ENGINEERING. YOU WILL HAVE TO HIRE AN
 ENGINEER FOR THIS REPORT.
  
 THE WINDOW REPEORT SUBMITTED DOES NOT
 INDICATE THAT IT HAS PASSED THE LARGE
 MISSLE IMPACT TESTING AS REQUIRED BY
 PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.SEE ATTACHED EXAMPLE SCHEDULE.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026