Plan Review Details - Permit 02071105
Plan Review Stops For Permit 02071105
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-02-27 Cont ID  
Sent By jwitmer Date 2006-02-27 Time 09:31 Rev Time 1.55
Received By jwitmer Date 2006-02-27 Time 09:31 Sent To  
Notes
2006-02-27 00:00:002-27-06 SINGLE TENANT USE NO TENANT
 SEPERATION WILL BE REQUIRED!!!!!

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-01-17 Cont ID  
Sent By jwitmer Date 2006-01-17 Time 10:29 Rev Time 2.22
Received By jwitmer Date 2006-01-17 Time 10:28 Sent To PC
Notes
2006-01-17 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02071105
 ADD: 539 OGSTON ST
 CONT: H. CANO
 TEL: (561)543-1290
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW / REVISION
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 1) THIS PERMIT WAS LET AS A SHELL PERMIT
 AND FOR SINGLE TENANT.UPDATE VALUE OF
 PERMIT IF TENANT BUILD OUT IS TO BE PART
 OF THIS PERMIT.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PLANS ARE INCOMPLETE FOR A TENANT BUILD
 OUT:
 A) BAY # 1 NO REST ROOM.
  
 B) BAY # 2&3 BOTH INDICATE DOOR OPENINGS
  
 BUT NO INFORMATION AS TOO DOOR SWING FOR
 INTERIOR OR EXTERIOR DOOR.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 C) PLANS INDICATE USE OF FIRE STOPPING
 MATERIALS (A& B). PLEASE PROVIDE THE
 TECHNICAL SHEETS OF THE ACTUAL SYSTEM TO
 BE USED.
 705.7.1 JOINTS INSTALLED IN OR BE-
 TWEEN FIRE RESISTANT WALLS, FIRE RESIS-
 TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES
 AND FIRE RESISTANT ROOFS OR ROOF/ CEIL-
 ING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
 705.1.2 PENETRATIONS SHALL BE PRO-
 TECTED BY AN APPROVED PENETRATION FIRE-
 STOP SYSTEM AS TESTED IN ACCORDANCE WITH
 ASTM E 814, WITH A MINIMUM POSITIVE
 PRESSURE DIFFERENTIAL OF 0.01 INCH OF
 WATER COLUMN AND AN F RATING OF NOT LESS
 THAN REQUIRED RATING OF THE WALL
 PENETRATED.
 PROVIDE A FLEXIBLE SEALANT AT THE
 WALL/ ROOF DECK DETAILING SYSTEM TO BE
 USED.
  
 D) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 E) INSPECTION HISTORY INDICATES A
 FAILURE NEEDS FOR INFORMATION FOR GARAGE
 DOOR ANCHOR DETAILS.
  
 F) PLANS DO NOT INDICATE IF THE BATHROOM
  
 AND OFFICE WALLS ARE TO CONTINUE TO THE
 ROOF DECK ABOVE? PLANS DO NOT INDICATE
 A CEILING ASSEMBLY TYPE FOR THE OFFICE
 NOR THE RESTROOMS.
  
 G) PLANS ONLY PROVIDE INFORMATION ON THE
  
 FIRE RATED WALL, PLANS INDICATE USE OF
 WOOD STUDS FOR THE OFFICE AND RESTROOM
 PARTITIONS, DOES THE STUDS CONTINUE TO
 THE ROOF DECK? IF NOT ," NOTE" SIGNAGE
 MUST BE PROVIDED INDICATINGAREA ABOVE
 IS NOT TO BE USED FOR STORAGE. IF
 STORAGE IS AN OPTION PROVIDE THE
 FOLLOWING INFORMATION:
 106.4.2 STORAGE & FACTORY- INDUS-
 TRIAL OCCUPANCIES. IT SHALL BE THE
 RESPONSIBILITY OF THE OWNER, AGENT,
 PROPIETOR OR OCCUPANT OF GROUP S AND
 GROUP F OCCUPANCIES, OR ANY OCCUPANCY
 WHERE EXCESSIVE FLOOR LOADING IS LIKELY
 TO OCCUR, TO EMPLOY A COMPETENT ARCHI-
 TECT OR ENGINEER IN COMPUTING THE SAFE
 FLOOR LOAD CAPACITY. ALL SUCH COMPUTA-
 TIONS SHALL BE ACCOMPANIED BY AN AFFA-
 DAVIT FROM THE ARCHITECT OR ENGINEER
 STATING THE SAFE ALLOWABLE FLOOR LOADS
 ON EACH FLOOR IN POUNDS PER SQ FT.THE
 COMPUTATIONS & AFFADAVIT SHALL BE FILED
 AS A PERMANENT RECORD OF THE BLDG DEPT.
 106.4.3.SIGNS REQUIRED. IN EVERY
 BUILDING OR PART OF A BUILDING USED FOR
 STORAGE, INDUSTRIAL OR HAZARDOUS PUR-
 POSES, THE SAFE FLOOR LOADS, AS REVIEWED
 BY THE BUILDING OFFICIAL ON THE PLAN,
 SHALL BE MARKED ON PLATES OF APPROVED DE
 SIGN WHICH SHALL BE SUPPLIED & SECURELY
 AFFIXED BY THE OWNER OF THE BUILDING IN
 A CONSPICUOUS PLACE IN EACH STORY TO
 WHICH THEY RELATE. SUCH PLATES SHALL NOT
 BE REMOVEDOR DEFACED, & IF LOST,
 REMOVED THE OWNER OF THE BUILDING SHALL
 REPLACE THEM.
  
 H) IS THE OFFICE TO BE AIR CONDITIONED?
  
 I) ELECTRICAL PLANS WILL NEED TO BE UP
 DATED TO SHOW THE NEW LAY OUT, NEW
 OFFICE, AND EXIT LIGHTING.
  
 J) PLANS ALSO NEED TO INDICTE THE
 OCCUPANCY FOR EACH SPACE? IF DIFFERENT
 OCCUAPNCIES MAY REQUIRE MORE THAN A 1 HR
 RATED WALL. SEE TABLE 704.1.
  
 ADDITIONAL COMMENTS MAY OCCUR ON THE
 NEXT REVIEW DEPENDING ON THE ANSWERS TO
 THIS REVIEW.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-11-12 Cont ID  
Sent By jwitmer Date 2002-11-12 Time 15:58 Rev Time 2.25
Received By jwitmer Date 2002-11-12 Time 15:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-09-16 Cont ID  
Sent By jwitmer Date 2002-09-16 Time 07:13 Rev Time 2.25
Received By jwitmer Date 2002-09-16 Time 06:44 Sent To  
Notes
2002-09-16 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02071105
 ADD: 539 OGSTON ST
 CONT: H CONS CONSTRUCTION
 TEL: (561)791-8763
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) SURVEY RECOGNIZES THE WRONG CODE.
  
 2) SHEET# 1, NOT SIGNED OR SEALED, DATED
 DEC. 14, 1996 THIS WOULD BE THE REVIEWED
 UNDER THE 1994 STANDARD BUILDING CODE,
 WHY IS THIS PART OF THE PLAN?
  
 3) F 101.1.2 THIS LOT IS LOCATED IN THE
 "FIRE DISTRICT"
  
 4) F102.1 TYPES OF BUILDINGS ALLOWED IN
 A FIRE DISTRICT TYPE I, II, III, IV,
 & V. THIS PLAN INDICATES THAT THE EXIST-
 ING BUILDING IS A DUPLEX TYPE VI CON-
 STRUCTION,(CBS WALLS) WHICH IS IT?
  
 5) F 103.1 EXISTING BUILDINGS WITHIN THE
 FIRE DISTRICT. AN EXISTING BUILDING
 SHALL NOT HEREAFTER BE INCREASED UNLESS
 IT IS OF A TYPE CONSTRUCTION PERMITTED
 FOR NEW BUILDINGS WITHIN THE FIRE
 DISTRICT.
  
 6) F102.2.4 ROOF COVERINGS IN THE FIRE
 DISTRICT SHALL CONFORM TO REQUIREMENTS
 OF A CLASS A OR B ROOF COVERINGS AS
 DIFINED IN 1505.
  
 7) 301.2 OCCUPANCY OR USE: WHAT IS THE
 PROPOSED USAGE OF THIS BUILDING? DEPEND-
 ING ON THE USE STORAGE, HAZARDOUS, OR
 REPAIR GARAGE?
  
 8) F102.6 EXTERIOR WALLS OF TYPE IV
 BUILDINGS SHALL HAVE A FIRE RESISTANCE
 OF 2 HOURS OR MORE WHEN SUCH WALLS ARE
 LOCATED WITHIN 30 FT OF A COMMON PROPER-
 TY LINE OR AN SSUMED PROPERTY LINE .
 TABLE 600 TYPE V BUILDING ALSO REQUIRES
 2 HR RATED WALLS, ASSUMED PROPERTY LINE
 BETWEEN BUILDINGS ON SAME LOT.
  
 9) NORTH ELEVATION, SWING DOORS SHALL
 REQUIRE 1 1/2 HR OPENING PROTECTIVES,
 PER 705.1.1.2.
  
 10) FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 11) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 12)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) LARGE GARAGE DOOR 14' TALL
 B) ROOFING ASSEMBLIES
  
 13) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 14) FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-09-23 Cont ID  
Sent By dpalmer Date 2005-09-23 Time 13:20 Rev Time 0.00
Received By jwitmer Date 2006-01-17 Time 10:28 Sent To  
Notes
2005-09-23 00:00:00********** UNSAT **********
  
 1)NOTE:PLEASE ADDRESS NOTES FROM
 "PROVISO" WHICH WAS GIVEN ON DECEMBER
 17, 2002.
  
 2)NOTE: PLEASE SHOW ALL CIRCUTING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULES
 TO BE SUBMITTED.
 215.5
  
 3)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EM/EXT LTS. THE CIRCUIT
 FEEDING THESE SHALL BE THE LOCAL BRANCH
 CIRCUIT FEEDING THAT AREA.
  
 4)NOTE: PLEASE SEE A "TYPICAL" PANEL
 SCHEDULEAND LOAD CALCULATIONS WAS
 SUBMITTED, HOWEVER UNITS ARE NOT THE
 SAME SIZE, DO NOT CONTAIN THE SAME ITEMS
 ETC.
 PLEASE SEE 220.3,220.10,220.11 ETC
 PLEASE SEE ALL CONTINUOUS LOADS ARE TO
 BE SHOWN AT 125%.
 215.3,230.42
  
 5)NOTE: PLEASE SEE CONDUCTORS SHOWN FOR
 PANELS. PLEASE CALRIFY 10-"A""C"??
 PLEASE ALSO SEE VOLTAGE IS SHOWN AS
 120/480V ??
  
 6)NOTE: PLEASE SEE SHOW WINDOW CIRCUITS
 ARE SHOWN ON PANEL SCHEDULE, HOWEVER
 THESE ARE NOT SHOWN ON PLANS.?
 210.62, 220.12
  
 7)NOTE: PLEASE SEE 600.5 FOR MISSING
 SIGN CIRCUIT.
  
 8)NOTE: PLEASE INDICATE OCCUPANCY ON
 PLANS.
  
 9)NOTE: PLEASE SEE MIN GROUNDING
 ELECTRODE CONDUCTOR PER 250.66.
 PLEASE SEE ORIGINAL PLANS CALLED FOR 2/0
 MIN, HOWEVER RISER HAS NOW BEEN REVISED
 TO LARGER SEC'S AND SMALLER GEC.
 PLEASE SEE A 2/0 MIN IS REQUIRED AS
 SHOWN ON ORIGINAL PLANS.
  
 10)NOTE: PLEASE CORRELATE SIZING OF
 PANELS ON RISER. ONE SHOWS 150A AND THE
 OTHER 200A.
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-12-18 Cont ID  
Sent By dpalmer Date 2002-12-17 Time 12:42 Rev Time 1.00
Received By dpalmer Date 2002-12-17 Time 12:42 Sent To  
Notes
2002-12-18 00:00:00*************** PROVISO/NOTES *********
  
 1)NOTE: PLEASE SUBMIT ONLY ONE LOAD
 CALCULATION. NEW ATTACHED SHEETS HAVE
 TWO.
  
 2)NOTE: PLEASE PROVIDE CIRCUITING ON
 PLANS AND CORRELATE WITH A SUBMITTED
 PANEL SCHEDULE. PLEASE ALSO NOTE
 CIRCUITING FOR EM/EXT LTS TO CONFORM
 TO 700-12E.
  
 3)NOTE: PLEASE SHOW ACTUAL LOCATIONS
 OF EM/EXT FIXTURES..
  
 PLEASE SUBMIT THE ABOVE REVISION FOR
 REVIEW BEFORE ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-11-07 Cont ID  
Sent By dpalmer Date 2002-11-07 Time 07:04 Rev Time 0.00
Received By dpalmer Date 2002-11-07 Time 07:03 Sent To  
Notes
2002-11-07 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTESAME PLANS WERE
 SUBMITTED WITHOUT ANY CHANGES.
 PLEASE SEE COMMENTS FORM FIRST REVIEW.
  
  
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-09-16 Cont ID  
Sent By dpalmer Date 2002-09-16 Time 13:57 Rev Time 1.00
Received By dpalmer Date 2002-09-16 Time 13:57 Sent To  
Notes
2002-09-16 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE PANEL SCHEDULE
 MENTION SHOW WINDOWS AND SIGN CIRCUITS,
 BUT NOTHING SHOWNON PLANS?
  
 2)NOTE: PLEASENOTE NO PANEL SCHEDULE
 SUBMITTED FOR HOUSE PANEL?
  
 3)NOTE:PLEASE NOTE CIRCUITING NEEDS TO
 BE SHOWN ON PLANS AND CORRELATE WITH
 SUBMITTED PANELS.
  
 4)NOTE: PLEASE SHOW LOCATION ON PLANS
 AND SHOW LOCATIONS OF PANELS IN EACH
 SPACE. IT IS NOTED THAT ONE PANEL IS
 SHOWN ON FLOOR PLAN BUT NONE OF THE
 OTHERS??
  
 5)NOTE: PLEASE NOTE/SEE FIRE REVIEW
 COMMENTS FOR EM/EXIT LTS.
  
 6)NOTE: PLEASE NOTE THAT ALL CONTINUOUS
 LOADS ARE TO BE SHOWN AT 125%. PER 215-3
 230-42
  
 7)NOTE: PLEASE NOTE THAT PLANS THAT ARE
 SIGNED AND SEALED BY AN ENGINEER ARE
 REQ`D BY FS/FAC TO HAVE A TITLE BLOCK
 PER 61G15-23.002.
  
 8)NOTE: PLEASE SUBMIT AIC RATINS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 110-9/215-5
  
 9)NOTE: PLEASE CLARIFY WIRE SIZES FROM
 GUTTER TO MAINS/METER.
  
 10)NOTE: PLEASE SHOW SIZE/TYPE GROUNDING
 ELECTRODE CONDUCTOR PER 250-50 AND
 SIZE PER 250-66.
  
 11)NOTE: PLEASE SHOW LOAD CALCULATIONS
 TO CONFORM TO 220-3,220-10,220-11,220-13
 PLEASE NOTE SERVICE IS NOTED TO HAVE
 4 150A DISC`S AND 60A FOR HOUSE BUT
 HOUSE IS ALSO NOT SHOWN.?
  
 12)NOTE: PLEASE SEE OTHER REVIEWERS
 COMMENTS IN REFERENCE TO OLD PLANS AND
 PERMIT #`S BEING SHOWN AND SUBMITTED
 THAT HAVE BEEN EXPIRED FOR MANY YEARS.
 PLEASE NOTE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE NOTE THAT PLANS ARE NOT
 COMPLETE FOR REVIEW AT PRESENT TIME
 AND MAY HAVE OTHER COMENTS WHEN PLANS
 ARE RE-SUBMITTED. PLEASE CALL IF THERE
 ARE ANY QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2002-12-12 Cont ID  
Sent By mamini Date 2002-12-12 Time 16:18 Rev Time 2.00
Received By mamini Date 2002-12-12 Time 16:18 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2002-09-18 Cont ID  
Sent By mamini Date 2002-09-18 Time 08:25 Rev Time 3.00
Received By mamini Date 2002-09-18 Time 08:24 Sent To  
Notes
2002-09-18 00:00:00FAILED:
 1. CURB AND GUTTERS, SIDEWALKS ALONG THE
 PROPERTY THAT ARE DAMAGED MUST BE
 RESTORED TO ORIGINAL CONDITION OR BETTER
 2. ALL DRIVEWAYS THAT ARE NOT GOING TO
 BE USED MUST BE REPLACED WITH REGULAR
 CURBS AND GUTTERS.
 3.AN ENCLOSURE FOR THE PROPOSED DUMPSTER
 MUST BE PROVIDED.
 4. DRAINAGE SYS MUST BE PROVIDED FOR THE
 ENTIRE SITE. PLEASE PROVIDE PERVIOUS AND
 IMPERVIPOUS CALCULATION.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-12-18 Cont ID  
Sent By mcarsill Date 2002-12-18 Time 20:14 Rev Time 0.00
Received By mcarsill Date 2002-12-18 Time 20:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-11-15 Cont ID  
Sent By mcarsill Date 2002-11-15 Time 10:51 Rev Time 0.00
Received By mcarsill Date 2002-11-15 Time 10:51 Sent To  
Notes
2002-11-15 00:00:001) PREVIOUS PLAN REVIEW COMMENTS
 PROVIDED TO APPLICANT HAVE NOT BEEN
 ADDRESSED. PLEASE ADDRESS PREVIOUS
 PLAN REVIEW COMMENTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-09-13 Cont ID  
Sent By mcarsill Date 2002-09-13 Time 15:47 Rev Time 0.00
Received By mcarsill Date 2002-09-13 Time 15:47 Sent To  
Notes
2002-09-13 00:00:001) SOME OF THE PLANS ARE COPIES OF
 DRAWINGS THAT WERE SUBMITTED BACK IN
 1996-1997 TO THE CITY. SOME ARE
 MISSING ORIGINAL SEALS.
  
 2) WHAT WILL THE BUILDING BE USED FOR.
 WILL IT BE SINGLE OR MULTIPLE TENANTS.
 IF IT IS GOING TO BE USED FOR MULTIPLE
 TENANTS, NO INFORMATION HAS BEEN
 PROVIDED FOR THE TENANT DEMISING WALLS
 WITH REGARDS TO DESIGN OR FIRE RATING.
  
 3) NO INFORMATION PROVIDED REGARDING
 EMERGENCY LIGHTING OR EXIT SIGNS.
  
 4) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-02-16 Cont ID  
Sent By adarroug Date 2006-02-16 Time 11:31 Rev Time 0.00
Received By adarroug Date 2006-02-16 Time 11:31 Sent To B
Notes
2006-02-16 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-01-11 Cont ID  
Sent By adarroug Date 2006-01-11 Time 08:53 Rev Time 0.00
Received By adarroug Date 2006-01-11 Time 08:52 Sent To B1
Notes
2006-01-11 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-11-14 Cont ID  
Sent By adarroug Date 2005-11-14 Time 18:18 Rev Time 0.00
Received By adarroug Date 2005-11-14 Time 18:18 Sent To E
Notes
2005-11-14 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2002-12-09 Cont ID  
Sent By btrobaug Date 2002-12-09 Time 17:45 Rev Time 0.00
Received By btrobaug Date 2002-12-09 Time 17:45 Sent To  
Notes
2002-12-09 00:00:00THIS PLAN IS ON THE HIT LIST.COMM BOARD
 # 61./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By btrobaug Date 2002-11-05 Time 17:02 Sent To  
Notes
2002-11-05 00:00:00TO COMM BOARD #46./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status P Date 2002-10-28 Cont ID  
Sent By btrobaug Date 2002-10-28 Time 12:15 Rev Time 0.00
Received By btrobaug Date 2002-10-25 Time 12:14 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-12-24 Cont ID  
Sent By pkrauss Date 2002-12-24 Time 07:27 Rev Time 0.35
Received By pkrauss Date 2002-12-24 Time 07:12 Sent To  
Notes
2002-12-24 00:00:00PROVISO:
  
 MINIMUM VENTILATION SHALL BE .05 CFM
 PER SQUARE FT.PROVIDE CALCULATION ON
 JOBSITE AT TIME OF INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-11-21 Cont ID  
Sent By pkrauss Date 2002-11-21 Time 13:31 Rev Time 0.35
Received By pkrauss Date 2002-11-21 Time 13:31 Sent To  
Notes
2002-11-21 00:00:00DENIED:
  
 PLEASE PROVIDE INFORMATION ON
 VENTILATION.INDICATE SEQUENCE OF FANS
 SHOWN ON PLAN SHEET A.2 (FANS RUN
 CONTINUOUSLY OR JUST WHEN OVERHEAD
 DOOR IS OPEN? INDICATE AIR MAKE-UP
 SHOULD OVERHEAD DOOR BE CLOSED.)
  
 INDICATE OUTSIDE AIR REQUIREMENT IN
 ACCORDANCE WITH 2001 FBC(M) TABLE 403.3
 OR ASHRAE 62-89.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-10-01 Cont ID  
Sent By pkrauss Date 2002-10-01 Time 12:32 Rev Time 0.35
Received By pkrauss Date 2002-10-01 Time 12:18 Sent To  
Notes
2002-10-01 00:00:00DENIED:
  
 1.PLEASE INDICATE WHAT TYPE OF
 OCCUPANCY THIS WILL BE.PLAN
 SHEET A2 SEEM TO INDICATE THAT THIS
 SPACE MAY BE DIVIDED INTO 4 SEPARATE
 SPACES.WILL THEY BE STORAGE OR
 OFFICE?
  
 2.PROVIDE VENTILATION INFORMATION.
  
 3.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER 2001 FBC(M) TABLE 403.3 OR
 ASHRAE 62-89.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-12-31 Cont ID  
Sent By kstevens Date 2002-12-31 Time 10:51 Rev Time 0.25
Received By kstevens Date 2002-12-31 Time 10:51 Sent To  
Notes
2002-12-31 00:00:00PASSED - PROVISO
  
 ARI-1010 COMPLIANT WATER COOLER REQUIRED
  
 ALL CAPPED PLUMBING TO BE ABANDONED
 SHALL BE INSPECTED PRIOR TO COVERING.

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-11-13 Cont ID  
Sent By kstevens Date 2002-11-13 Time 16:13 Rev Time 0.50
Received By kstevens Date 2002-11-13 Time 16:13 Sent To  
Notes
2002-11-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW: COMMENT #4
 DRINKING FOUNTAIN IS REQUIRED. PLEASE
 SUBMIT DETAIL SHOWING COMPLIANCE WITH
 SECTION 11-4.15 AND ALL SUBSECTIONS.
 ALSO SECTION 11-4.1.3(10)(A) FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-10-03 Cont ID  
Sent By jleech Date 2002-10-03 Time 18:43 Rev Time 1.00
Received By jleech Date 2002-10-03 Time 18:42 Sent To  
Notes
2002-10-03 00:00:00DENIED;
 1.FLOOR PLAN ON PAGE A-2 AND SANITARY
 RISER DIAGRAM PAGE E-1 DO NOT MATCH.
 RISER DIAGRAM TO SH0W FUTURE BATHROOMS
 2.HANDICAP TOILET ROOMS SHALL COMPLY
 WITH 11-4.17.3. WATER CLOSET SHALL BE
 LOCATED IN THE CORNER, DIAGONAL TO THE
 DOOR.
 3.MINIMUM WIDTH OF HANDICAP BATHROOMS IS
 7'-2" INSIDE DIA. NOT 5'-9".
 4.PLEASE SHOW TYPE OF OCCUPANCY AND
 COMPLY WITH TABLE 403.1 OF THE FBC
 PLUMBING.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop Z ZONING
Rev No 2 Status P Date 2002-11-05 Cont ID  
Sent By sgraham Date 2002-11-05 Time 15:00 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2002-07-23 Cont ID  
Sent By btrobaug Date 2002-10-28 Time 12:17 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-07-23 00:00:00NEED LEVEL I