Plan Review Details - Permit 02071003
Plan Review Stops For Permit 02071003
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-07-18 Cont ID  
Sent By mcarsill Date 2002-07-18 Time 11:14 Rev Time 0.00
Received By mcarsill Date 2002-07-18 Time 11:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-07-17 Cont ID  
Sent By ndenmark Date 2002-07-17 Time 06:56 Rev Time 0.33
Received By ndenmark Date 2002-07-17 Time 06:55 Sent To  
Notes
2002-07-17 00:00:00PROVISO:
  
 1. 2001 FBC 306.6 REQUIRES LEVEL
 PLATFORM PROVIDED ON EACH SIDE OF THE
 APPLIANCE AND NO LES 30 INCHES WIDE IN
 ANY DIMENSION AND SHALL BE PROVIDED
 WITH GAURDS PER 304.8.
  
 2. IF ROOF HEIGHT OF EQUIPMENT EXCEEDS
 16' COMPLIANCE WITH 306.5 IS REQUIRED.
  
 3. MANUFACTURES INSTALLATION
 INSTRUCTIONS FOR CERAMIC BLANKET TO BE
 ON SITE FOR INSPECTION. PROVIDE
 INSPECTION OF WELDS PRIOR TO
 CONCEALMENT.