| Plan Review Stops For Permit 02071003 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2002-07-18 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-07-18 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-07-18 |
Time |
11:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-07-17 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2002-07-17 |
Time |
06:56 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2002-07-17 |
Time |
06:55 |
Sent To |
|
|
| Notes |
| 2002-07-17 00:00:00 | PROVISO: | | | | | | 1. 2001 FBC 306.6 REQUIRES LEVEL | | | PLATFORM PROVIDED ON EACH SIDE OF THE | | | APPLIANCE AND NO LES 30 INCHES WIDE IN | | | ANY DIMENSION AND SHALL BE PROVIDED | | | WITH GAURDS PER 304.8. | | | | | | 2. IF ROOF HEIGHT OF EQUIPMENT EXCEEDS | | | 16' COMPLIANCE WITH 306.5 IS REQUIRED. | | | | | | 3. MANUFACTURES INSTALLATION | | | INSTRUCTIONS FOR CERAMIC BLANKET TO BE | | | ON SITE FOR INSPECTION. PROVIDE | | | INSPECTION OF WELDS PRIOR TO | | | CONCEALMENT. |
|
|
|