Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-08-27 Cont ID  
Sent By hpiskura Date 2002-08-27 Time 13:51 Rev Time 0.00
Received By hpiskura Date 2002-08-27 Time 13:02 Sent To  
Notes
2002-08-27 00:00:00PROVISO: SEPARATE PERMIT REQUIRED FOR
 STORE FRONT WITH PRODUCT APPROVALS/TEST
 REPORTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-07-29 Cont ID  
Sent By jwitmer Date 2002-07-29 Time 06:46 Rev Time 1.00
Received By jwitmer Date 2002-07-29 Time 06:46 Sent To  
Notes
2002-07-29 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02070546
 ADD: 3222 COMMERCE PLACE B / C
 CONT: PDC DEVELOPMENT CORP
 TEL: (561)793-5852
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3)FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 4)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 5) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.MISSING PRODUCTS:
 A)DOORS - IMPACT RESISTANT
 B)WINDOWS - IMPACT RESISTANT
  
 6)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGTH IN ACCORDANCE WITH TABLE 1511.7.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-08-28 Cont ID  
Sent By dpalmer Date 2002-08-28 Time 10:37 Rev Time 0.50
Received By dpalmer Date 2002-08-28 Time 10:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-07-24 Cont ID  
Sent By dpalmer Date 2002-07-24 Time 13:05 Rev Time 0.00
Received By dpalmer Date 2002-07-24 Time 13:05 Sent To  
Notes
2002-07-24 00:00:00***************UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT ALL CIRCUITING
 NEEDS TO BE PLACED ON PLANS SHOW
 CORRELATING PANEL SCHEDULES.
 PLEASE NOTE A PANEL IN ONE TENANT SPACE
 MAY NOT FEED CIRCUITS INTO OTHERS SPACE.
  
 2)NOTE: PLEASE CLARIFY SHOW WINDOW
 RECPS. PER 210-62
  
 3)NOTE: PLEASE CLARIFY SIGN CIRCUTIS
 PER 600-5
  
 4)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 THAT WILL MOST LIKELY AFFECT ELEC PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-08-22 Cont ID  
Sent By mcarsill Date 2002-08-22 Time 09:44 Rev Time 0.00
Received By mcarsill Date 2002-08-22 Time 09:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-07-11 Cont ID  
Sent By mcarsill Date 2002-07-11 Time 13:27 Rev Time 0.00
Received By mcarsill Date 2002-07-11 Time 13:27 Sent To  
Notes
2002-07-11 00:00:001) PLEASE CLARIFY EXITING AND SIGN
 PLACEMENT NEXT TO OFFICE # 3.
  
 2) IS BUILDING FIRE SPRINKLER PROTECTED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-07-23 Cont ID  
Sent By kstevens Date 2002-07-23 Time 13:34 Rev Time 0.00
Received By kstevens Date 2002-07-23 Time 13:34 Sent To  
Notes
***NONE***