Plan Review Details - Permit 02070539
Plan Review Stops For Permit 02070539
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-04-05 Cont ID  
Sent By shill Date 2004-04-05 Time 13:07 Rev Time 1.00
Received By shill Date 2004-04-05 Time 13:07 Sent To  
Notes
2004-04-05 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)SEE PREVIOUS LIST, IMPACT
 PROTECTION REQUIRED.THE PRODUCT
 APPROVALS SUBMITTED INDICATE THAT THE
 DOORS DO NOT HAVE IMPACT RATING.
  
 2.)EXTERIOR STAIRS SHALL BE SEPARATED
 FROM THE INTERIOR BUILDING BY WALLS WITH
 A FIRE RESISTANCE RATING OF NOT LESS
 THAN 1 HR, WITH FIXED OR SELF-CLOSING
 OPENING PROTECTIVES.SHOW COMPLIANCE
 FOR THE NEW FRENCH DOORS.FBC1006.2.4
  
 3.)THE ELEVATIONS SHOW SIDELITES, NOT
 INCLUDED IN THE DOOR PRODUCT APPROVAL.
 ALSO NEED MULLION PRODUCT APPROVALS.
  
 4.)THE PRODUCT APPROVAL FOR THE
 COMPONENT APPROVAL - SERIES 1518
 DOOR IS INCOMPLETE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-12-23 Cont ID  
Sent By csiegber Date 2004-03-26 Time 16:16 Rev Time 1.50
Received By shill Date 2003-12-23 Time 14:30 Sent To  
Notes
2003-12-23 00:00:00*****CORRECTIONS*****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 REVISION - CHANGE GARAGE DOORS TO
 FRENCH DOORS
  
 1.)THE PLANS ARE TO BE SEALED BY THE
 DESIGNER OF RECORD, GORDON BUCK.
 INCLUDE A COMPLETE TITLE BLOCK.
  
 2.)SUBMIT PRODUCT APPROVALS FOR THE
 FRENCH DOORS.IMPACT PROTECTION
 REQUIRED FBC1606.1.4.
  
 3.)CLOUD ALL CHANGES TO EXPEDITE
 PLAN REVIEW.
  
 4.)THE INFORMATION ON THE "NEW
 RIGHT ELEVATION" (APPROVED SET) IS NOW
 MISSING FROM THE "NEW EAST ELEVATION"
 (REVISION SET).THE INFORMATION
 DELETED IS IN REGARDS TO FIRE RATED
 WINDOWS AND EGRESS.ADDRESS.
  
 5.)METAM24 IS NOT IN THE SIMPSON 2003
 CATALOG.META24 IS AN EMBEDDED TRUSS
 ANCHOR WITH A MAX UPLIFT OF 1500. THAT
 APPLICATION CONFLICTS WITH YOURS,
 DESIGN UPLIFT EXCEEDS PRODUCT
 LIMITATIONS.ADDRESS.CHECK ALL
 CONNECTORS.
  
 6.)PLEASE NOTE THAT THIS CHANGE
 HAS FAILED ZONING.A BUILDING REVISION
 CANNOT BE ISSUED WITHOUT ZONING
 APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-07-21 Cont ID  
Sent By csiegber Date 2003-12-17 Time 14:30 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-07-21 00:00:00BALCONY REVISION DATED 7/16/03

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-05-09 Cont ID  
Sent By btrobaug Date 2003-05-09 Time 17:25 Rev Time 0.50
Received By btrobaug Date 2003-05-09 Time 17:25 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-03-21 Cont ID  
Sent By shernand Date 2003-05-07 Time 14:25 Rev Time 1.00
Received By btrobaug Date 2003-03-20 Time 11:53 Sent To P
Notes
2003-03-20 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE SHOW THE LOCATION OF THE SERVICE
 ON THE DRAWING.HOW IS THE PANEL FOR THE
 REAR BUILDING BEING FED?
 NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-13 Cont ID  
Sent By sthyng Date 2003-03-19 Time 13:39 Rev Time 1.00
Received By btrobaug Date 2002-11-05 Time 17:18 Sent To R
Notes
2002-11-13 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND RESUBMIT FOR REVIEW.
  
 1} THE RISER DIAGRAM ONLY SHOWS ONE
 METER AND PANEL AT THE GARAGE.IS THERE
 A SEPERATE SERVICE AT THE HOUSE? PLEASE
 INDICATE COMPLIANCE WITH 250-32(A) &
 (D) ON THE RISER DIAGRAM.
  
 2} PLEASE SHOW LOAD CALCULATIONS AND
 PANEL SCHEDULES FOR ALL PANELS PER
 215-5 & 220-3(C)(1).
  
 3} THE AHU IN THE CABANA MUST COMPLY
 WITH 210-63 IF APPLICABLE.
  
 4} PLEASE CLARIFY THE PANEL SCHEDULE
 NOTES,SEE HI-LIGHTED PORTION.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-03-26 Cont ID  
Sent By csiegber Date 2004-03-26 Time 16:16 Rev Time 0.00
Received By csiegber Date 2004-03-26 Time 16:16 Sent To B
Notes
2004-03-26 00:00:00TO SH DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-12-17 Cont ID  
Sent By csiegber Date 2003-12-17 Time 14:30 Rev Time 0.00
Received By csiegber Date 2003-12-17 Time 14:13 Sent To B
Notes
2003-12-17 00:00:00TO HP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-11-24 Cont ID  
Sent By csiegber Date 2003-11-24 Time 16:15 Rev Time 0.00
Received By csiegber Date 2003-11-24 Time 16:15 Sent To B
Notes
2003-11-24 00:00:00TO HP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-07-18 Cont ID  
Sent By shernand Date 2003-07-18 Time 14:47 Rev Time 0.00
Received By shernand Date 2003-07-18 Time 14:47 Sent To B
Notes
2003-07-18 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-07 Cont ID  
Sent By shernand Date 2003-05-07 Time 14:25 Rev Time 0.00
Received By shernand Date 2003-05-07 Time 14:25 Sent To E
Notes
2003-05-07 00:00:00BT DESK, REVISION.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-19 Cont ID  
Sent By sgraham Date 2003-04-16 Time 15:53 Rev Time 0.00
Received By sthyng Date 2003-03-19 Time 13:38 Sent To E
Notes
2003-03-19 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-10-28 Cont ID  
Sent By btrobaug Date 2002-10-28 Time 14:40 Rev Time 0.00
Received By btrobaug Date 2002-07-09 Time 18:47 Sent To P
Notes
2002-10-28 00:00:00TO PLUMBING IN BOX./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-05-20 Cont ID  
Sent By pkrauss Date 2003-05-20 Time 13:14 Rev Time 0.30
Received By pkrauss Date 2003-05-20 Time 13:14 Sent To B
Notes
2003-05-20 00:00:00PROVISO:
  
 NO MECHANICAL WORK TO BE DONE IN MAIN
 HOUSE.MINI-SPLITS IN GARAGE APT. SEE
 MANUFACTURER INSTALLATION INSTRUCTIONS
 INSTALLATION REQUIREMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2003-05-05 Cont ID  
Sent By kstevens Date 2003-05-19 Time 08:24 Rev Time 0.00
Received By pkrauss Date 2003-05-05 Time 14:49 Sent To  
Notes
2003-05-05 00:00:00CUST SVC IN LOBBY NO MECH WORK TO BE
 DONE IN THE MAIN HOUSE-ADDING DOOR ONLY

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-03-27 Cont ID  
Sent By pkrauss Date 2003-03-27 Time 14:29 Rev Time 0.40
Received By pkrauss Date 2003-03-27 Time 14:18 Sent To  
Notes
2003-03-27 00:00:00PLEASE CORRELATE PLANS! 2ND REQUEST
 APPROVAL FOR GARAGE APT ONLY -
 ENERGY & MANUAL J CALCS SUBMITTED FOR
 THE GARAGE APT ONLY.NO MECHANICAL
 PLAN SUBMITTED.
  
 NO MECHANICAL WORK SUBMITTED FOR THE
 MAIN HOUSE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-11-01 Cont ID  
Sent By kstevens Date 2003-03-24 Time 10:37 Rev Time 0.40
Received By pkrauss Date 2002-11-01 Time 09:37 Sent To E
Notes
2002-11-01 00:00:00DENIED: MECHANICAL PERMIT 02070540
  
 PLANS SUBMITTED FOR 2ND REVIEW DO NOT
 INCLUDE PLANS FOR HVAC.(HVAC PLANS ARE
 STILL WITH OLD PLANS)PLEASE CORRELATE.
  
 PROVIDE INFORMATION FOR THE VENTING OF
 THE GAS STOVE/OVEN. PROVIDE MANUFACTURER
 SUBMITTAL DATA.
  
 CLARIFY THAT THE ONLY HVAC TO BE DONE IS
 AT THE GARAGE APARTMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-05-19 Cont ID  
Sent By kstevens Date 2003-05-19 Time 08:24 Rev Time 0.50
Received By kstevens Date 2003-05-19 Time 08:18 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-03-24 Cont ID  
Sent By btrobaug Date 2003-05-09 Time 17:26 Rev Time 1.00
Received By kstevens Date 2003-03-24 Time 10:15 Sent To M
Notes
2003-03-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING.
  
 1) MORE INFORMATION REQUIRED. DO THE
 PLANS SUBMITTED PRIOR TO PLANS SUBMITTED
 3-19-03 HAVE ANYTHING TO DO WITH THE JOB
 THAT WILL BE DONE?IF SO THEN ALL
 SHEETS WILL HAVE TO BE PUT TOGETHER AS
 A SET AND TWO COPIES WILL HAVE TO BE
 SUBMITTED. IF NOT THEN ALL PLANS THAT
 HAVE NOTHING TO DO WITH THE JOB SHALL
 NOT BE RESUBMITTED.
 2) MANUF INFO REQUIRED FOR INSTA-HOT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-10-31 Cont ID  
Sent By btrobaug Date 2003-03-21 Time 11:08 Rev Time 2.50
Received By kstevens Date 2002-10-30 Time 18:52 Sent To M
Notes
2002-10-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) SHT D-1.0 DEMO NOTES #4, ALL CAPPED
 PLUMBING PIPES SHALL BE INSPECTED PRIOR
 TO COVERING.
 2) SHT A-1.1 GARAGE FLOOR PLAN, MANUF.
 INFO REQUIRED FOR TANKLESS WATER HEATER.
 3) SHT A-1.1 GARAGE FLOOR PLAN, PLEASE
 SUBMIT MANUF. INFO FOR GAS WATER HEATER.
 SHOW DETAIL FOR VENTING. IS THIS A DIR-
 ECT VENT SYSTEM?
 4) SHT E-1 PLUMBING NOTES #8, AIR CHAMB-
 ERS ARE NOT APPROVED. PLEASE DELETE REF-
 ERENCE. WATER HAMMER ARRESTORS TO BE IN-
 STALLED PER 604.9. W/M - DISHWASHER -
 ICE MAKER.
 5) SHT E-1 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE. PLEASE SUBMIT A RISER DIA
 GRAM THAT MEETS CODE REQUIREMENTS. (SEE
 ATTACHED SHEET FOR EXAMPLE)
 6) ENCLOSED USABLE SPACE SHALL BE PER-
 MITTED UNDER STAIRS PROVIDED THE SPACE
 IS SEPARATED FROM THE STAIR ENCLOSURE BY
 THE SAME FIRE RESISTANCE AS THE EXIT EN-
 CLOSURE. SEC 1006.1.4 EXCEPTION (1).
 7) GAS PERMIT REQUIRED. SEE FOLLOWING
 GAS PERMIT APPLICATION REQUIREMENTS.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3) TYPE OF GAS, (LP OR NATURAL)
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 FBC-2001 FUEL GAS CODE SECS. 401.8 THRU
 402.5.2 & TABLES 402.2(1) THRU 402(34).
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR PER FBC-2001 FUEL GAS CODE SEC 304.
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 GAS CODE SEC. 402.2. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE SEC
 502 THRU 506.
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2003-05-21 Cont ID  
Sent By hpiskura Date 2003-05-21 Time 09:59 Rev Time 0.00
Received By hpiskura Date 2003-05-21 Time 09:59 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2003-03-31 Cont ID  
Sent By hpiskura Date 2003-03-31 Time 15:59 Rev Time 0.00
Received By hpiskura Date 2003-03-31 Time 13:51 Sent To Z
Notes
2003-03-31 00:00:00NEW PLANS DATED 3/18/03 PREPARED BY
 CANALES DESIGNS.
  
 SHEET A1, THE AREA SHOWN AS "EXISTING
 CONDITIONS W/REPAIRS"PLEASE CLEARLY
 DEFINE THE SCOPE OF WORK.
  
 SHOW A CONNECTION DETAIL AND THE LENGTH
 OF PROJECTION FOR THE NEW ROOF/CANOPY ON
 THE NEW RIGHT ELEVATION.
  
 OPENINGS WITHIN TEN FEET OF THE STAIRS
 ARE REQUIRED TO BE FIRE RATED.SEE FBC
 1006.2.4.
  
 NOTE THAT EMERGENCY EGRESS IS REQUIRED
 FROM THE SLEEPING ROOM. FBC 1005.4.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-11-14 Cont ID  
Sent By btrobaug Date 2003-03-20 Time 11:53 Rev Time 0.00
Received By hpiskura Date 2002-11-13 Time 14:51 Sent To  
Notes
2002-11-14 00:00:00THE NEW APARTMENT IS SUBJECT TO IMPACT
 FEES COLLECTED BY THE COUNTY.THE
 PERMIT PLANS MUST BE STAMPED BY THAT
 OFFICE AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 CALL 561-233-5025 FOR MORE INFORMATION.
  
 SHOW THE FINISH FLOOR ELEVATION RELATIVE
 TO NGVD.
  
 SHEET S2 SHOW THE DESIGN LOADS FOR THE
 FLOORS, HAND AND GUARD RAILS AND
 STAIRS. SEE FBC 1604 AND 1608.
  
 THERE ARE NO DIMENSIONS ON THE FRAMING
 PLANS, S2.
  
 WITH REGARDS TO SECTION 1/S2, WHAT ARE
 THE ASSUMED LOADS FOR THE TWO 1/2"
 BOLTS THAT WILL SUPPORT THE FLOOR
 GIRDER,PARTICULARLY THE F'B OF THE
 WOOD? SEE FBC 104.2
  
 SHOW THE REINFORCED MASONRY
 SPECIFICATIONS IN ACCORDANCE WITH FBC
 2103.1 IE GROUT SPEC, POUR HEIGHT,
 CLEAR SPACE, ETC.
  
 WILL THE MEZZANINE BE FRAMED ON A
 LEDGERAS SHOWN IN SECTION 16/A4 OR
 JOIST HANGERS AS SHOWN IN SECTION A/A3?
  
 THE PLANS DATED 9/26/02 DO NOT HAVE THE
 MEZZANINE INFORMATION SHOWN ON THE
 PLANS DATED 6/24/02.PLEASE COLLATE THE
 PLANS INTO TWO CONCISE SETS.
  
 THE EXTERIOR STAIRS REQUIRE HANDRAILS AT
 EACH SIDE.SEE FBC 1007.5.2.
  
 THE EXTERIOR STAIRS ARE NOT SERVED BY A
 ROOFED 4 1/2 FEET WIDE BALCONY AS
 REQUIRED BY FBC 1006.2.2.
  
 THE WINDOW OPENINGS IN THE AREA
 PRESCRIBED IN FBC 1006.2.4 ARE REQUIRED
 TO BE FIXED 3/4 HOUR RATED ASSEMBLIES.
 (EXTERIOR STAIR)
  
 PLEASE PROVIDE THE CALCULATION REQUIRED
 BY METRO DADE NOA 99-1012.04 FOR USE OF
 THE MORTAR SET SYSTEM NOA 00-0218.03.
  
 PLEASE PROVIDE A RECENT, LEGIBLE,
 SIGNED SEALED AND DATED SURVEY.

Review Stop Z ZONING
Rev No 6 Status F Date 2003-12-16 Cont ID  
Sent By mmclean Date 2003-12-16 Time 15:46 Rev Time 0.00
Received By mmclean Date 2003-12-16 Time 15:46 Sent To  
Notes
2003-12-16 00:00:00DENIED NEED DEED RESTRICTION PER ANA
 MARIA OF URBAN DESIGN CALLED KARL
 PENEUDL MM

Review Stop Z ZONING
Rev No 5 Status P Date 2003-04-16 Cont ID  
Sent By sgraham Date 2003-04-16 Time 15:51 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2003-04-02 Cont ID  
Sent By sgraham Date 2003-04-02 Time 10:48 Rev Time 0.00
Received By sgraham Date   Time   Sent To B
Notes
2003-04-02 00:00:00DENIED, OUTBUILDING MAY HAVE A MAXINUM
 NET INTERIOR AREA OF 900 SQ FT AND
 MAXINUM HABITABLE AREA OF 450 SQ FT.
 THE 2ND FLOOR IS OVER THE LIMIT AT
 540 SQ FT. FIRST FLOOR MUST REMAIN AS
 A GARAGE.

Review Stop Z ZONING
Rev No 3 Status P Date 2002-10-24 Cont ID  
Sent By hpiskura Date 2003-03-31 Time 16:39 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-10-24 00:00:00PROVISO:NO GREATER THAN 14' FROM FIN.
 FLOOR TO CEILING

Review Stop Z ZONING
Rev No 2 Status F Date 2002-10-10 Cont ID  
Sent By sgraham Date 2002-10-10 Time 16:45 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-10-10 00:00:00DENIED,BLDG TOO TALL, OUT BLDGS (ART 4
 33-42) SHALL BE ONLY 2-STORIES
 2ND CHECKLIST

Review Stop Z ZONING
Rev No 1 Status F Date 2003-12-16 Cont ID  
Sent By sgraham Date 2002-07-11 Time 11:49 Rev Time 1.00
Received By gjoyce Date 2003-12-16 Time 10:10 Sent To  
Notes
2003-12-16 00:00:00MUST OBTAIN A DEED RESTRICTION PRIOR TO
 PERMIT ISSUANCE. AG REGARDING THE CONVER
 SION OR EXPANSION OF THE GARAGE APARTMEN
 T
2002-07-11 00:00:001. ALL STORIES SHALL BE NO GREATER THAN
 14' FROM FINISHED FLOOR TO FINISHED
 CEILING. THIS COUNTS FOR THE CEILING
 THROUGHOUT, NOT JUST WHERE THE CEILING
 MEET THE WALL.
 2. THE ALLOWABLE AREA FOR THE FOOT
 PRINT OF THE STRUCTUE IS 450 SQ FT IN
 REVIEW STAFF MEASURED 462 SQ FT. PLEASE
 REDUCE THE SQUARE FOOTAGE TO MEET THE
 ALLOWABLE.
 3. THE DAC BOARD HAS GIVEN THE STAFF
 THE ADMINISTRATIVE ABILITY TO ALLOW
 FOR A ROOF PITCH OF 3 OR 3.5 OVER
 12 FOR ROOFS IN THE PROVIDENCIA
 NEIGHBORHOOD. STAFF SUGGESTS THAT THE
 PITCH FOR THE ROOF COME DOWN TO
 THE ALLOWABLE 3 TO 3.5 PITCH