Plan Review Details - Permit 02070459
Plan Review Stops For Permit 02070459
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-11-14 Cont ID  
Sent By mcarsill Date 2002-11-14 Time 14:35 Rev Time 0.00
Received By mcarsill Date 2002-11-14 Time 14:35 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 2 Status P Date 2002-11-14 Cont ID  
Sent By mcarsill Date 2002-11-14 Time 14:36 Rev Time 0.00
Received By mcarsill Date 2002-11-14 Time 14:36 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 1 Status F Date 2002-07-09 Cont ID  
Sent By mcarsill Date 2002-07-09 Time 13:51 Rev Time 0.00
Received By mcarsill Date 2002-07-09 Time 13:51 Sent To  
Notes
2002-07-09 00:00:001) PLANS INDICATE THE 1996 EDITION OF
 NFPA 13. THE PLANS SHALL READ 1999
 EDITION OF NFPA 13.
  
 2) PLEASE INDICATE ON THE PLANS ANY
 AREAS THAT WILL NOT BE SPRINKLER
 PROTECTED THAT IS ALLOWABLE BY CODE.
  
 3) NO PRODUCT APPROVALS PROVIDED FOR
 FIRE SPRINKLER HEADS OR OTHER
 EQUIPMENT PLANNED FOR USE.
  
 4) PLEASE INDICATE ON THE PLANS THE
 LOCATION OF THE SPARE SPRINKLER HEADS
 AND WRENCH WILL BE STORED.
  
 5) STANDPIPE VALVES ARE TO BE REDUCED
 FROM 2 1/2 TO 1 1/2.
  
 6) PLANS SHALL INDICATE MINIMUM
 CLEARANCES TO FIRE PROTECTION DEVICES
 TO BE AT LEAST SEVEN AND HALF FEET.
  
 7) BACKFLOW DEVICE SHALL HAVE TAMPER
 SWITCHES, CHAINS AND LOCKS.
  
 8) PLEASE CLEARLY INDICATE ALL RISER
 CLAMPS FOR STANDPIPE SYSTEM.
  
 9) PLEASE PROVIDE ELEVATION DRAWINGS
 FOR ALL VERTICAL SHAFTS. NO DETAILS
 FOR EXAMPLE PROVIDED FOR FIRE
 SPRINKLER PROTECTION FOR THE TRASH
 CHUTE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-11-14 Cont ID  
Sent By mcarsill Date 2002-11-14 Time 14:35 Rev Time 0.00
Received By mcarsill Date 2002-11-14 Time 14:35 Sent To  
Notes
***NONE***