Plan Review Details - Permit 02070448
Plan Review Stops For Permit 02070448
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-08-15 Cont ID  
Sent By btrobaug Date 2002-08-15 Time 19:06 Rev Time 0.00
Received By btrobaug Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-07-29 Cont ID  
Sent By pkrauss Date 2002-07-29 Time 08:15 Rev Time 0.00
Received By btrobaug Date 2002-07-29 Time 14:29 Sent To R
Notes
2002-07-29 00:00:00FAILED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 ON THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} SMOKE DETECTOR IN THE BATHROOM IS IN
 VIOLATION OF 2-5.2.1.6(B),NFPA-72.
  
 2} THE GROUND BETWEEN THE PANEL AND THE
 MAIN DISCONNECT IS IN VIOLATION OF
 250-6(B)(1).
  
  
 THERE ARE NO SMALL APPLIANCE CIRCUITS IN
 THE LOAD CALCS OR ON THE PANEL SCHEDULE
 AS REQUIRED BY 220-16(A).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-08-08 Cont ID  
Sent By mcarsill Date 2002-08-08 Time 15:48 Rev Time 0.00
Received By mcarsill Date 2002-08-08 Time 15:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-12-19 Cont ID  
Sent By pkrauss Date 2002-12-19 Time 11:15 Rev Time 0.20
Received By pkrauss Date 2002-12-19 Time 11:06 Sent To  
Notes
2002-12-19 00:00:00MECH PERMIT 02070470
 REVISED ENERGY CALCS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-10-16 Cont ID  
Sent By pkrauss Date 2002-10-16 Time 14:29 Rev Time 0.30
Received By pkrauss Date   Time   Sent To  
Notes
2002-10-16 00:00:00MECH REV PERMIT 02070470

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-07-29 Cont ID  
Sent By pkrauss Date 2002-07-29 Time 08:15 Rev Time 0.35
Received By pkrauss Date 2002-07-29 Time 08:15 Sent To E
Notes
2002-07-29 00:00:00MECHANICAL PERMIT 02070470

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-12-18 Cont ID  
Sent By kstevens Date 2002-12-18 Time 08:47 Rev Time 0.10
Received By kstevens Date 2002-12-18 Time 08:47 Sent To  
Notes
2002-12-18 00:00:00SUBMITTAL LETTER - DELETE REQUIREMENT TO
 INSULATE HOT WATER LINES.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-08-08 Cont ID  
Sent By rmcdouga Date 2002-08-08 Time 08:23 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-08-08 00:00:00OK PER J.LEECH 7-27-02 WAS ENTERED IN
 COMPUTER UNDER THE FIRST R STOP BY
 MISTAKE.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-08-08 Cont ID  
Sent By rmcdouga Date 2002-08-08 Time 08:26 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-08-08 00:00:00************BUILDING PROVISO************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-07-27 Cont ID  
Sent By btrobaug Date 2002-07-29 Time 16:02 Rev Time 0.33
Received By jleech Date 2002-07-27 Time 07:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-07-19 Cont ID  
Sent By sgraham Date 2002-07-19 Time 15:00 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***