Plan Review Details - Permit 02070311
Plan Review Stops For Permit 02070311
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-01-17 Cont ID  
Sent By hpiskura Date 2003-01-17 Time 10:53 Rev Time 0.00
Received By hpiskura Date 2003-01-17 Time 10:53 Sent To  
Notes
2003-01-17 00:00:00REVISION #3 10/25/02 AND REVISION #5
 11/20/02

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-08-06 Cont ID  
Sent By pschmitz Date 2003-01-13 Time 08:17 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-12-27 Cont ID  
Sent By dpalmer Date 2002-12-27 Time 06:19 Rev Time 0.50
Received By dpalmer Date 2002-12-27 Time 06:18 Sent To  
Notes
2002-12-27 00:00:00**************** NOTE ***********
  
 1)NOTE: PLEASE SEE NOTE REDLINED FOR
 CORRECTED CODE REFERENCED. SHOULD BE
 99 NEC>
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-07-26 Cont ID  
Sent By dpalmer Date 2002-07-26 Time 05:55 Rev Time 0.00
Received By dpalmer Date 2002-07-26 Time 05:55 Sent To  
Notes
2002-07-26 00:00:00**** NOTE ***
  
 PLANS REDLINED FOR TWO ITEMS.
 WRONG ART. REFERENCED FOR EQUIP GRNDS.
 250-122
 COLOR CODING OF CONDUCTORS PER LOCAL
 AMENDMENTS. 215
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-09-17 Cont ID  
Sent By hpiskura Date 2002-09-17 Time 12:57 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-12-18 Cont ID  
Sent By mcarsill Date 2002-12-18 Time 16:37 Rev Time 0.00
Received By mcarsill Date 2002-12-18 Time 16:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-08-21 Cont ID  
Sent By mcarsill Date 2002-08-21 Time 15:09 Rev Time 0.00
Received By mcarsill Date 2002-08-21 Time 15:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-08-02 Cont ID  
Sent By mcarsill Date 2002-08-02 Time 13:30 Rev Time 0.00
Received By mcarsill Date 2002-08-02 Time 13:30 Sent To  
Notes
2002-08-02 00:00:001) TEMPORARY WALLS SHALL NOT CONSIST
 OF NON-FIRE RATED VISQUEEN OR OTHER
 NON-APPROVED MATERIALS.
  
 2) THE TEMPORARY WALLS ARE NOT TO
 INTERFERE WITH ANY REQUIRED FIRE
 SPRINKLER SYSTEM PROTECTION.
  
 3) PERMITS REQUIRED FOR ANY NEW
 FIRE SPRINKLER OR FIRE ALARM WORK.
  
 4) DEBRIS FROM DEMOLITION SHALL BE
 REMOVED DAILY.
  
 5) THE FIRE SPRINKLER SYSTEM SHALL
 REMAIN ON DURING CONSTRUCTION. IF
 PORTIONS OF THE SYSTEM MUST BE TURNED
 OFF, ALL CODE REQUIREMENTS ARE TO BE
 FOLLOWED WITH REGARDS TO NOTIFICATION
 OF FIRE RESCUE, HOSPITAL, AND FIRE
 ALARM MONITORING COMPANY. FIRE WATCHES
 MUST IF NECESSARY MUST BE COORDINATED
 WITH THE BUREAU OF FIRE PREVENTION,
 835-2910.
  
 6) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-13 Cont ID  
Sent By btrobaug Date 2002-12-13 Time 18:38 Rev Time 0.00
Received By btrobaug Date 2002-12-13 Time 18:37 Sent To  
Notes
2002-12-13 00:00:00TO COMM BOARD #30./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-12-18 Cont ID  
Sent By pkrauss Date 2002-12-18 Time 13:07 Rev Time 0.40
Received By pkrauss Date 2002-12-18 Time 12:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-08-21 Cont ID  
Sent By pkrauss Date 2002-08-14 Time 14:16 Rev Time 0.45
Received By pkrauss Date 2002-08-14 Time 13:43 Sent To  
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status P Date 2003-01-13 Cont ID  
Sent By pschmitz Date 2003-01-13 Time 08:17 Rev Time 1.00
Received By pschmitz Date   Time   Sent To B
Notes
2003-01-13 00:00:00MED GAS, APPR.PES

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-01-11 Cont ID  
Sent By kstevens Date 2003-01-11 Time 10:15 Rev Time 1.10
Received By kstevens Date 2003-01-11 Time 10:14 Sent To  
Notes
2003-01-11 00:00:00REVISION OK - PLUMBING ONLY

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-07-23 Cont ID  
Sent By pschmitz Date 2002-07-23 Time 10:37 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-07-23 00:00:00MEDICAL GAS PLAN REVIEW, PROVISO:
 COMPLY WITH NFPA 99-C,1999 EDITION
 PIPED GAS SYSTEMS, LEVEL 1
 CERTIFIED INSTALLER, BRAZER AND SYSTEM
 VERIFICATION, PERFORMED BY OTHER THAN
 THE INSTALLING CONTRACTOR.
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS561-659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-07-22 Cont ID  
Sent By kstevens Date 2002-07-22 Time 10:57 Rev Time 0.00
Received By kstevens Date 2002-07-22 Time 10:57 Sent To  
Notes
2002-07-22 00:00:00PLUMBING ONLY - SEPARATE REVIEW FOR
 MED-GAS.

Review Stop Z ZONING
Rev No 1 Status N Date 2002-09-17 Cont ID  
Sent By hpiskura Date 2002-09-17 Time 12:57 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***