Plan Review Details - Permit 02070302
Plan Review Stops For Permit 02070302
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-12-05 Cont ID  
Sent By hpiskura Date 2002-12-05 Time 12:26 Rev Time 0.00
Received By hpiskura Date 2002-12-05 Time 10:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-09-18 Cont ID  
Sent By pkrauss Date 2002-11-22 Time 10:53 Rev Time 0.00
Received By hpiskura Date 2002-09-18 Time 15:03 Sent To  
Notes
2002-09-18 00:00:00THE REVISED SHEETS FOR THE BUILDING MEET
 THE CURRENT CODE.THERE IS STILL NO
 INFORMATION ON THE TOWER OR ANTENNA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-08-06 Cont ID  
Sent By hpiskura Date 2002-08-06 Time 13:37 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-08-06 00:00:00THE CODE DATA SHEET AND SOME PLACES ON
 THE PLAN DECLARED DESIGN TO THE 1997
 SBCCI.THE 2001 FBC IS THE CODE IN
 EFFECT.PLEASE REVISE AND ENSURE
 COMPLIANCE AS NECESSARY.
  
 THE CENTRAL TOWER INC. SHEETS ARE
 REQUIRED TO HAVE THE ENGINEER'S
 EMBOSSED SEAL.
 THE DESIGN MUST COMPLY WITH THE FBC
 (ASCE 7-98) FOR WIND LOADS.
  
 THERE ARE NO CONSTRUCTION DETAILS FOR
 THE TOWERS OR THE ANTENNAS TO BE
 ATTACHED TO THEM.THE INFORMATION IS
 NECESSARY IF THEY ARE TO BE CONSTRUCTED
 UNDER THIS PERMIT.
  
 SHOW THE RISE RUN DETAILS FOR THE
 STAIRS. SEE FBC 1007.
  
 SHOW THE WIND PRESSURES FOR THE
 COMPONENTS AND CLADDING.
  
 IF THE NOTICE OF ACCEPTANCE OR TEST
 REPORTS FOR THE WINDOWS, DOORS AND ROOF
 COVERING ARE NOT INCLUDED WITH THIS
 PERMIT APPLICATION, SEPARATE PERMITS
 AND ADDITIONAL FEES WILL BE REQUIRED.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-11-20 Cont ID  
Sent By dpalmer Date 2002-11-20 Time 06:31 Rev Time 0.25
Received By dpalmer Date 2002-11-20 Time 06:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-09-17 Cont ID  
Sent By dpalmer Date 2002-09-17 Time 18:10 Rev Time 0.25
Received By dpalmer Date 2002-09-17 Time 18:10 Sent To  
Notes
2002-09-17 00:00:00********** NOTE ******
  
 PLANS ARE OK.
 STILL NEED SECOND SET OF PLANS FOR
 EITHER PERMIT #. PLEASE NOTE THESE HAVE
 TWO DIFFERENT ADDRESSES AND ARE PERMITT-
 -ED SEPARATELY.
  
  
 DEWEY PALMER.
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-08-02 Cont ID  
Sent By dpalmer Date 2002-08-02 Time 08:07 Rev Time 0.00
Received By dpalmer Date 2002-08-02 Time 08:06 Sent To  
Notes
2002-08-02 00:00:00*************** UNSAT ****************
  
 PLEASE ALSO SEE COMMENTS ON PERMIT #
 02070303
  
 1)NOTE: PLEASE CLARIFY SECOND PANEL AND
 METER? SHOWN ON BLDG PLAN. INTERIOR.
  
 2)NOTE: PLEASE SHOW ALL CONTINOUS LOADS
 AT 125%. PLEASE NOTE THAT AT THIS
 LOCATION, MANY LOADS ARE 3 OR MORE HOURS
  
 3)NOTE: PLEASE SUBMIT TWO MORE SETS AS
 THEY PERMITTED SEPARATELY AND HAVE
 SEPARATE ADDRESSES.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-11-22 Cont ID  
Sent By mcarsill Date 2002-11-22 Time 10:04 Rev Time 0.00
Received By mcarsill Date 2002-11-22 Time 10:04 Sent To  
Notes
2002-11-22 00:00:00PER DIRECTION OF THE CITY FIRE MARSHAL
 BOB PRUSIECKI, ANY ADDITONAL DEVELOPMENT
 IN THIS AREA WILL REQUIRE THE
 INSTALLATION OF FIRE HYDRANTS IN THE
 AREA.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-08-22 Cont ID  
Sent By pkrauss Date 2002-08-14 Time 16:56 Rev Time 0.00
Received By mcarsill Date 2002-08-22 Time 12:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-15 Cont ID  
Sent By dpalmer Date 2002-11-15 Time 14:43 Rev Time 0.00
Received By dpalmer Date 2002-11-15 Time 14:43 Sent To  
Notes
2002-11-15 00:00:00TO COMM BOARD #27

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-11-22 Cont ID  
Sent By pkrauss Date 2002-11-22 Time 10:52 Rev Time 0.15
Received By pkrauss Date 2002-11-22 Time 10:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-08-14 Cont ID  
Sent By pkrauss Date 2002-08-14 Time 16:14 Rev Time 0.35
Received By pkrauss Date 2002-08-14 Time 16:13 Sent To FIRE
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-07-23 Cont ID  
Sent By sgraham Date 2002-07-23 Time 09:49 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***