Plan Review Details - Permit 02070266
Plan Review Stops For Permit 02070266
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-02-19 Cont ID  
Sent By jwitmer Date 2003-02-19 Time 16:50 Rev Time 0.50
Received By jwitmer Date 2003-02-19 Time 16:50 Sent To  
Notes
2003-02-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02070266
 ADD: 2808 AUSTRAILIAN AVE
 CONT: BLISS
 TEL: (561)391-0212
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 REVISION : SUBMITTED FEB 14/03
  
 DENIED:
 1) PERMIT IS FOR INTERIOR WORK ONLY
 2) ROOFING PERMIT SEPERATE PERMIT IS
 REQUIRED, ON IONTERIOR REMODEL APPLICA-
 TION (SEPERATE PERMIT FOR ROOF)
 3) PRODUCT TESTING REPORTS REQUIRED
 FOR ROOFING PERMIT. SUBMIT PRODUCT
 REPORTS FOR EACH TYPE OF APPLICATION.
 4) SEPERATE PERMIT FOR THE REPLACING OF
 CANVAS AWNING.
  
 JIM WITMER
 BUILDING PLAN REVIEW
 (561)659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-09-30 Cont ID  
Sent By dpalmer Date 2003-02-18 Time 15:37 Rev Time 1.25
Received By jwitmer Date 2002-09-30 Time 15:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-07-29 Cont ID  
Sent By jwitmer Date 2002-07-29 Time 08:03 Rev Time 2.50
Received By jwitmer Date 2002-07-29 Time 08:03 Sent To  
Notes
2002-07-29 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02070266
 ADD: 2808 AUSTRALIAN AV # A
 CONT: BLISS CONSTRUCTION, INC
 TEL: (561)391-0212
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENETRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY.
  
 2)11.4.8.5. HANDRAILS: IF A RAMP HAS
 A RISE GREATER THAN 6" OR A HORIZONTAL
 PROJECTION GREATER THAN 72", THEN IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 3) 11.5.1 INDICATE COMPLIANCE WITH
 SEATING: RESTAURANTS/ CAFETERIAS.
  
 4) MAIN ENTRY, BUZZER ENTRY KEY PAD:
 11-4.27 CONTROLS & OPERATING MECHANISMS,
 (3) THE HIGHEST OPERABLE PART OF ANY CON
 TROL, DISPENSERS,RECEPTACLES AND OTHER
 OPERABLE EQUIPMENT SHALL BE PLACED WITH
 IN AT LEAST ONE OF THE REACH RANGES
 SPECIFIED IN 11-4.2.5 AND 11-4.2.6.
  
 5) 304.2.1(2) SMALL ASSEMBLY A-2, OCCU-
 PANT LOADS OF 50 OR MORE.
  
 6) BUZZER ENTRY KEY PAD, ADDITIONAL INFO
 REQUIRED, SEE 1019.7.1.(1)
  
 7)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A9.00 WINDOW SPECIFICATIONS: INDIC
 ATES CHANGE OUT OF WINDOWS UNDER PHASEII
 IF PHASE II IS NOT PART OF PERMIT DELETE
 OR IF PART OF THIS PERMIT PROVIDE
 PRODUCT INFORMATION, SBCCI OR DADE
 COUNTY REPORT.
  
 8)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,WATER-
 FOUNTAIN IN CORRIDOR II, INDICATE COMPLI
 ANCE W/ 103.2.3.2 & 44" MINIMUM CORRIDOR
 WIDTH?
  
 9) ROOMS 35,38,39 & 40 DO NOT HAVE
 EXIT LIGHT VISIBLE FROM OFFICE DOORWAY?
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-11-25 Cont ID  
Sent By dpalmer Date 2002-11-25 Time 11:02 Rev Time 0.50
Received By dpalmer Date 2002-11-25 Time 11:02 Sent To  
Notes
2002-11-25 00:00:00SUBMITTALS FOR MC CABLE
 SUBMITTTALS FOR LTS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-10-07 Cont ID  
Sent By btrobaug Date 2002-11-21 Time 16:25 Rev Time 0.50
Received By dpalmer Date 2002-10-07 Time 14:18 Sent To  
Notes
2002-10-07 00:00:00RE-STAMP.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-07-18 Cont ID  
Sent By dpalmer Date 2002-07-18 Time 06:16 Rev Time 0.00
Received By dpalmer Date 2002-07-17 Time 18:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-09-24 Cont ID  
Sent By mcarsill Date 2002-09-24 Time 09:50 Rev Time 0.00
Received By mcarsill Date 2002-09-24 Time 09:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-08-02 Cont ID  
Sent By mcarsill Date 2002-08-02 Time 14:25 Rev Time 0.00
Received By mcarsill Date 2002-08-02 Time 14:25 Sent To  
Notes
2002-08-02 00:00:001) NUMERICAL ADDRESS REQUIRED ON
 BUILDING.
  
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR HOOD, DUCT, AND FIRE SUPPRESSION
 SYSTEM.
  
 3) ALL CORRIDORS SHALL PROVIDE A
 MINIMUM OF AT LEAST FORTY FOUR INCHES
 IN CLEAR WIDTH. SEVERAL LOCATIONS ON
 THE PLANS DO NOT MEET THIS MINIMUM
 CODE REQUIREMENT.
  
 4) IF THE BUILDING IS NOT FIRE
 SPRINKLER PROTECTED, ALL ELECTRICAL,
 MECHANICAL, AND STORAGE ROOMS ARE
 REQUIRED TO BE AT LEAST ONE HOUR
 FIRE RATED WITH AT LEAST FORTY FIVE
 MINUTE FIRE RATED FIRE DOORS. PLEASE
 REVISE PLANS TO REFLECT THIS.
  
 5) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY FIRE ALARM SYSTEM MODIFICATIONS.
  
 6) PLEASE PROVIDE PRODUCT APPROVALS FOR
 3M FIREWRAP IDENTIFIED IN THE PLANS.
 THIS INFORMATION CAN BE SUBMITTED NOW
 OR WITH THE HOOD PLANS AND PERMIT.
  
 7) DRY CHEMICAL FIRE SUPPRESSION SYSTEM
 IS NOT PERMITTED. ONLY A WET FIRE
 SUPPRESSION SYSTEM WILL BE ALLOWED
 SINCE IT MEETS THE UL 300 STANDARD AND
 DRY CHEMICAL DOES NOT. PLEASE REVISE
 PLANS AS NECESSARY.
  
 8) SECURITY DEVICES SHALL NOT INTERFERE
 WITH FREE EGRESS FROM THE BUILDING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-02-18 Cont ID  
Sent By dpalmer Date 2003-02-18 Time 15:37 Rev Time 0.00
Received By dpalmer Date 2003-02-18 Time 15:36 Sent To B
Notes
2003-02-18 00:00:00TO JIM WITMER'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-02-06 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 16:20 Rev Time 0.00
Received By dpalmer Date 2003-02-06 Time 16:20 Sent To P
Notes
2003-02-06 00:00:00TO PLUMB INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-21 Cont ID  
Sent By btrobaug Date 2002-11-21 Time 16:25 Rev Time 0.00
Received By btrobaug Date 2002-11-21 Time 16:24 Sent To E
Notes
2002-11-21 00:00:00TO DVP./WRT

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-01-23 Cont ID  
Sent By hmoser Date 2003-01-23 Time 15:10 Rev Time 0.50
Received By hmoser Date 2003-01-23 Time 15:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-08-01 Cont ID  
Sent By pkrauss Date 2002-08-01 Time 10:43 Rev Time 0.40
Received By pkrauss Date 2002-08-01 Time 10:43 Sent To  
Notes
2002-08-01 00:00:00PROVISO:MECHANICAL PERMIT 02070267
  
 SEPARATE PERMITS REQUIRED FOR HOOD, FIRE
 SUPRESSION & WALK-IN COOLER/FREEZER.
 PLEASE PROVIDE PLANS & MANUFACTURER
 SUBMITTAL DATA WITH PERMIT APPLICATION.
  
 FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE AS
 PER 2001 FBC(M) 606.2.1. & NFPA 90A
 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-12-06 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 16:20 Rev Time 0.75
Received By kstevens Date 2002-12-06 Time 16:59 Sent To  
Notes
2002-12-06 00:00:00PLUMBING SUBMITTAL - OK

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-10-18 Cont ID  
Sent By kstevens Date 2002-10-18 Time 17:43 Rev Time 2.00
Received By kstevens Date 2002-10-18 Time 17:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-10-08 Cont ID  
Sent By kstevens Date 2002-10-08 Time 14:26 Rev Time 0.00
Received By kstevens Date 2002-10-08 Time 14:26 Sent To  
Notes
2002-10-08 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 MECHANICAL
  
 1) FOLLOWING COMMENTS FROM THE PREVIOUS
 PLAN REVIEW WERE NOT ADDRESSED.
 2) SHT P-1 PLEASE CONTACT RODNEY COMPO,
 ENVIRONMENTAL COMPLIANCE MANAGER TO SIZE
 GREASE INTERCEPTOR. SEE ATTACHED SHEET
 FOR APPROVED CITY WEST PALM DETAIL. SHT
 P-1 DETAIL NOT APPROVED.
 3) PLEASE ROUTE PLANS TO THE PALM BEACH
 COUNTY HEALTH UNIT - 901 EVERNIA WPB
 (561) 355-3018 FOR PLAN REVIEW BEFORE
 RESUBMITTING TO THE CITY FOR PLAN RE-
 VIEW.
 4) #5 FROM PREVIOUS REVIEW: SHTS P-1,
 P-2, & P-3 SAFE WASTE IS NOT APPROVED.
 ALL INDIRECT WASTE SHALL DRAIN INTO A
 FLOOR SINK. SEC 802.3 LOCATE ALL FLOOR
 SINKS UNDER UNITS BEING DRAINED.
 5) #7 FROM PREVIOUS REVIEW: SHT P-1,
 DISHWASHER SHALL DRAIN INTO THE SANITARY
 SYSTEM, NOT GREASE SYSTEM PER UTILITY
 ORD.
 6) #11 FROM PREVIOUS REVIEW: SHT P-2,
 WATER HEATER NOT SHOWN ON WATER ISOMET-
 RIC. SHOW DETAIL FOR PIPING OF PAN DRAIN
 AND RELIEF VALVE (T/P) DISCHARGE PIPING.
 COMPLY WITH SECTIONS 504.7 AND 607.3.2.
 SHOW ON WATER HEATER DETAIL.
 7) #13 FROM PREVIOUS REVIEW: SHT P-2,
 GAS ISOMETRIC, SALAMANDER NOT SHOWN ON
 SHT A6.01 KITCHEN KEY PLAN & DETAILS.
 8) ITEM C FROM PREVIOUS REVIEW:
 SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2001
 FUEL GAS CODE SEC. 402.2
 9) ITEM D FROM PREVIOUS REVIEW:
 EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 10) #16 FROM PREVIOUS REVIEW: SHT P-3
 MATERIALS AND EQUIPMENT "L" AND EXECUT-
 ION OF WORK "F" AIR CHAMBERS ARE NOT
 APPROVED. PLEASE DELETE REFERENCES.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-07-20 Cont ID  
Sent By kstevens Date 2002-07-20 Time 17:37 Rev Time 0.00
Received By kstevens Date 2002-07-20 Time 17:37 Sent To  
Notes
2002-07-20 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 MECHANICAL
  
 1) SHT A2.02 TOILET ROOM #26, 11-4.22.4,
 IF TOILET STALLS ARE PROVIDED, THEN AT
 LEAST ONE STALL SHALL BE A STANDARD
 STALL COMPLYING WITH 11-4.17. (FIG 30A)
 2) SHT P-1 PLEASE CONTACT RODNEY COMPO,
 ENVIRONMENTAL COMPLIANCE MANAGER TO SIZE
 GREASE INTERCEPTOR. SEE ATTACHED SHEET
 FOR APPROVED CITY WEST PALM DETAIL.
 3) PLEASE ROUTE PLANS TO THE PALM BEACH
 COUNTY HEALTH UNIT, DIVISION OF ENVIRON-
 MENTAL HEALTH - 901 EVERNIA WPB (561)
 355-3018 FOR PLAN REVIEW BEFORE RESUB-
 MITTING TO THE CITY FOR PLAN REVIEW.
 4) SHT P-1 SINKS IN FOOD PREP AREA SHALL
 DRAIN INDIRECTLY TO AN APPROVED RECEPTI-
 CAL (FLOOR SINK)
 5) SHTS P-1, P-2, & P-3 SAFE WASTE IS
 NOT APPROVED. ALL INDIRECT WASTE SHALL
 DRAIN INTO A FLOORSINK. SEC 802.3 LOCATE
 ALL FLOOR SINKS UNDER UNITS BEING DRAIN-
 ED. FLOOR DRAINS NOT APPROVED
 6) TABLE 401.3 REQUIRES A DRINKING
 FOUNTAIN. PLEASE SUBMIT DETAIL. SHOW
 COMPLIANCE WITH 11-4.15 AND ALL SUBSECT-
 IONS AND WITH 11-4.1.3(10)(A) PROVISIONS
 FOR THOSE WHO HAVE TROUBLE BENDING OR
 STOOPING.
 7) SHT P-1 DISHWASHER SHALL DRAIN INTO
 SANITARY SYSTEM, NOT GREASE PER UTILITY
 ORD.
 8) SHT P-1 CONDENSORS 23.03/23.04 SHALL
 DRAIN TO FLOOR SINK. 802.3
 9) BACKFLOW REQUIRED ON WATER SERVICE.
 10) SHT P-2 WATER ISOMETRIC, WATER HAM-
 MER ARRESTORS ARE REQUIRED PER 604.9.
 IF USED, THEY SHALL BE LOCATED NEAR FIX-
 TURE IN AN "EFFECTIVE RANGE" NOT AT TOP
 OF DROP AS SHOWN. PDI-WH 201 & MANUFACT-
 URE INSTALLATION INSTRUCTIONS.
 11) SHT P-2 WATER HEATER NOT SHOWN ON
 WATER ISOMETRIC. SHOW DETAIL FOR PIPING
 OF PAN DRAIN AND RELIEV VALVE (T/P) DIS-
 CHARGE PIPING. COMPLY WITH SECTIONS
 504.7 AND 607.3.2 - SHOW ON WATER HEATER
 DETAIL.
 12) SHT P-3 FLOOR DRAIN - SAFE WASTE
 DETAIL NOT APPROVED. DELETE DETAIL
 13) SHT P-2 GAS ISOMETRIC, SALAMANDER
 NOT SHOWN ON SHT A6.01 KITCHEN KEY PLAN
 & DETAILS.
 14) GAS PERMIT REQUIREMENTS. INFORMATION
 REQUIRED FOR GAS PERMIT.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODESEC 402.2 IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2001
 FUEL GAS CODE SEC. 402.2
 D. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. NO HOOD
 SHUT DOWN SHOWN ON PLANS.
 15) PLEASE PROVIDE CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECS. 1106 & 1107. ADD 1/2 AREA OF ALL
 VERTICAL WALLS AND AREA OF ROOFS DRAIN-I
 ING FROM ABOVE. SHOW LOCATION OF ALL
 DRAINS ON PLANS.
 16) SHT P-3 MATERIALS AND EQUIPMENT "L"
 AND EXECUTION OF WORK "F" AIR CHAMBERS
 ARE NOT APPROVED. PLEASE DELETE REFEREN-
 CE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377