| | BUILDING PLAN REVIEW |
| | PERMIT: 02070231 |
| | ADD: 8175 DRIGGS HILL |
| | CONT: TAZ CONST |
| | TEL: (954)340-1744 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1) PROVIDE FLOOD ZONE ELEVATION |
| | CERTIFICATE FOR NEW CONSTRUTION WITH |
| | BASE FLOOD ELEVATION, CITY CODE REQUIRES |
| | AN ADDITIONAL 6".REQUIRED BEFORE C.O. |
| | |
| | 2) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | |
| | 3)1503.4.4 PROTECTION AGAINST DECAY & |
| | TERMITES. CONDENSATE LINES & ROOF DOWN |
| | SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| | AWAY FROM THE STRUCTURE SIDEWALL, |
| | WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| | TENSIONS, OR SPLASH BLOCKS. |
| | |
| | 4)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | PLANS ARE MISSING (4) THE INTERNAL |
| | PRESSURE COEFFICIENT(0.18) |
| | |
| | 5) MISSING MEAN ROOF HEIGTH IN LOAD |
| | SCHEDULE.TABLES 1606. |
| | |
| | 6) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORT, SBCCI OR DADE COUNTY |
| | REPORT ARE ACCEPTED. MISSING REPORTS: |
| | A) FIXED GLASS RECTANGULAR |
| | B) FIXED GLASS OVAL |
| | C) SINGLE HUNG WINDOWS |
| | D) SLIDING GLASS DOORS |
| | E) MULLIONS |
| | F)FRONT ENTRY DOORS (PAIR) |
| | G) ROOFING REPORT OR BY SEPERATE PERMIT |
| | |
| | 7)1707.4.5.1 MULLIONS OCCURRING |
| | BETWEEN INDIVIDUAL WINDOW AND GLASS |
| | DOOR ASSEMBLIES. TESTING REPORTS ARE |
| | REQUIRED BY AN APPROVED TESTING |
| | LABORATORY OR BE ENGINEERED. |
| | |
| | 8)1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| | ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| | TO THE ROUGH OPENING SUBTRATE. |
| | |
| | 9)SITE SPECIFIC ENGINEERING (PRODUCT |
| | APPROVAL) REQUIRES THE WET SIGNATURE, |
| | DATE AND EMBOSSED SEAL OF THE ENGINEER |
| | CERTIFYING THE PRODUCT AND SIGNATURE |
| | AND SEAL OF THE DESIGN PROFESSIONAL |
| | OF RECORD. FOR USE WITH NORANDEX. |
| | |
| | 10) THE L-2 LINTEL OVER THE SLIDING |
| | GLASS DOOR AT THE LIVING ROOM REQUIRES |
| | A 4" BEARING AS A MINIMUM, 2101.3.1. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |