| 2002-08-02 00:00:00 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 02070213 |
| | ADD: 6406 CROWN ISLAND COVE |
| | CONT: M/I HOMES |
| | TEL: (561)471-3440 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | |
| | 2) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORT, SBCCI OR DADE COUNTY |
| | REPORT ARE ACCEPTED. MISSING OR ADDITION |
| | AL INFORMATION REQUIRED: |
| | A) WINDOWS: BUTT GLAZING: 2406.2 |
| | SPECIAL CASES, WHERE OTHER THAN FIRM SUP |
| | PORT ON ALL SIDES IS PROVIDED, (THREE |
| | SIDES, TWO SIDES, CANTILEVERED, OR HIGH- |
| | LY FLEXIBLEFOR EXAMPLE) DETAILED SHOP |
| | DRAWINGS SPECIFICATIONS AND RATIONAL |
| | ANALYSIS AND OR TEST DATA ASSURING THE |
| | SAFE PERFORMANCE FOR THE SPECIFIC |
| | INSTALLATION SHALL BE PREPARED BY |
| | ENGINEERS EXPERIENCED IN THIS WORK AND |
| | SHALL BE SUBMITTED FOR AND RECEIVE, IF |
| | WARRENTED FORMAL APPROVAL BY THE BUILD- |
| | ING OFFICIAL.PROVIDE DATA. |
| | B)OVERHEAD GARAGE DOOR, SPECIFY OR HIGH |
| | LIGHT WHICH MODEL SHALL BE USED. |
| | C) STORM SHUTTERS, ELEVATIONS MISSING |
| | PRESSURES POS/ NEG ON ARCHETECTURAL |
| | SHEETS. |
| | SITE SPECIFIC: NOT FILLED OUT BY |
| | THE ARCHETECT, MISSING ADDRESS. |
| | ENGINEERING NOT SIGNED BY ENGINEER |
| | OF RECORD. |
| | AS PER CITY IMPLEMENTATION STANDARD |
| | FOR HURRICANE MISSLE IMPACT PROTECTION. |
| | SECTIONS TO BE USED NOT HIGHLIGHTED. |
| | NO KEY PLAN IDENTIFYING OPENINGS FOR |
| | IDENTIFYING WINDOWS VS SHUTTERS. |
| | SCHEDULE DOESN'T INDICATE FASTENER |
| | TO BE USED, SPACING MAY BE OFF. |
| | SCHEDULE DOESN'T INDICATE SHUTTERS |
| | TO BE INSTALLED HORIZONTALLY OR VERTICAL |
| | D) SHEET 9 OF 9: -66.1 PRESSURE ???? |
| | THE PRODUCT APPROVALS DO NOT COME CLOSE |
| | TO THIS PRESSURE. |
| | |
| | 3) FAMILY ROOM: SLIDING GLASS DOOR OPEN- |
| | ING, WILL THE TRACK FOR (4) DOORS AND |
| | SCREEN FIT UNDER THE BEAM? |
| | |
| | 4) FAMILY ROOM: (4 1/2") WALL MADE OF |
| | WHAT MATERIALS? ANCHORED HOW? |
| | |
| | 5) FAMILY ROOM: THE WALL ABOVE THE |
| | 8"X23"INDICATES THAT IT HAS SHEER WALL |
| | SECTIONS, FASTENED HOW? BUILT OUT OF |
| | WHAT MATERIALS? THICKER THAN THE REST OF |
| | THE WALLS? |
| | |
| | 6) THE LOAD OF THE SECOND STORY WALL IS |
| | TRANSFERED ONTO A 8"X23" BEAM THE ONE |
| | END IS SUPPORTED BY 45 DEGREE COLUMN W/ |
| | 2/#5'S??? |
| | |
| | 7) THE SAME WALL SECTION, BUTT GLAZING, |
| | NO DETAILS AS TO HOW IT IS ATTCHED SIDES |
| | OR TOP? CANTILEVERED BEAM ABOVE. |
| | |
| | 8) MISSING ROOF FRAMING MEMBERS AT THE |
| | BUTT GLASS DETAIL. |
| | |
| | 9) CANTILEVERED TRUSSES, EXTERIOR OF THE |
| | FAMILY ROOM, NO DETAILS? |
| | |
| | 10) FLOOR TRUSS OR GIRDER (LAST TRUSS) |
| | ACHIEVE SUPPORT? BETWEEN FAMILY ROOM AND |
| | THE KITCHEN? |
| | |
| | 11) HOW DOES SHEETS A&B RELATE TO THE |
| | REMAINDER OF THE JOB? THERE ARE DETAILS |
| | WITH NO INFORMATION? |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDEN- |
| | TIFYING THE SHEET OR SPECIFICATION PAGE |
| | WHERE THE CHANGES CAN BE FOUND, WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | JIM WITMER |
| | PLAN REVIEW |
| | TEL: (561)659-8096 EX.8412 |
| | FAX: (561)659-8026 |