Plan Review Details - Permit 02061904
Plan Review Stops For Permit 02061904
Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2003-01-24 Cont ID  
Sent By mamini Date 2003-01-24 Time 10:24 Rev Time 3.00
Received By mamini Date 2003-01-24 Time 10:24 Sent To  
Notes
2003-01-24 00:00:00PASSED:
 1. REVISIONS FOR UDERGROUND UTILITIES
 AND SITE WORKS AS SUBMITTED , APPROVED,
 HOWEVER THIS PERMIT WOULD NOT INCLUDE
 THE IRRIGATION SYESTEMS FOR THE SITE,
 NOTE THAT, A SEPARATE PERMIT FOR
 IRRIGATION PER BUILDING DEPTARTMENT IS
 REQUIRED.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2002-10-30 Cont ID  
Sent By mamini Date 2002-10-30 Time 09:17 Rev Time 5.00
Received By mamini Date 2002-10-30 Time 09:17 Sent To  
Notes
2002-10-30 00:00:00PASSED :
 1. PALN WAS REVIEWED UNDER THE SAME
 PERMIT # FOR PLAN REVIEW
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2002-08-26 Cont ID  
Sent By mamini Date 2002-08-26 Time 08:36 Rev Time 5.00
Received By mamini Date 2002-08-26 Time 08:35 Sent To  
Notes
2002-08-26 00:00:00PASSED WITH PROVISOS :
 1. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATION AND FEES FOR UNDERGROUND
 UTILITIES / SITE WORKS WILL BE REQUIRED.
 2. PLEASE SUBMIT A COPY OF SFWMD PRMIT
 AT THE TIME OF ACTUAL PERMIT APPLICATION
 3. POLLUTION/EROSION PLANS MUST BE
 INATALLED IN FIELD FOR EACH PHASE OF THE
 CONSTRUCTIONS PRIOR TO ANY CONSTRUCTION.
 4. HANDICAPPED PARKING SPACES DESIGNATED
 AS VAN ACCESSIABLE, SHOULD HAVE A 8'-0"
 ACCESS AISLE TO ACCOMMODATE A WHEELCHAIR
 LIFT.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2002-07-15 Cont ID  
Sent By mamini Date 2002-07-15 Time 08:10 Rev Time 5.00
Received By mamini Date 2002-07-15 Time 08:10 Sent To  
Notes
2002-07-15 00:00:00FAILED:
 1. PLEASE VERIFY ALL THE DEVICE-
 ASSEMBLIES AND LABELING ON THE EXISTING
 AND PROPOSED DOMESTING WATER AND FIRE
 LINES AS SHOWN ON SHEET C23, C24, AND
 C26, CORRECT THROUGH OUT AS REQUIRE.
 2. PLEASE STATE OR SHOW, HOW WATER IS
 BEING SUPPLIED FOR THE PROPOSED
 ADDITIONS, BOTH FOR FIRE AND DOMESTIC.
 3. PLEASE STATE THE STATUS OF THE SFWMD
 PERMIT, PLEASE NOTE THAT SAID PERMIT
 WILL BE REQUIRED AT THE TIME OF ACTUAL
 PERMITTING.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-10-30 Cont ID  
Sent By mcarsill Date 2002-10-30 Time 11:56 Rev Time 0.00
Received By mcarsill Date 2002-10-30 Time 11:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-08-30 Cont ID  
Sent By mcarsill Date 2002-08-30 Time 15:42 Rev Time 0.00
Received By mcarsill Date 2002-08-30 Time 15:42 Sent To  
Notes
2002-08-30 00:00:001) ELECTRONIC SWITCHES WILL BE
 REQUIRED ON ANY FIRE LINE BACKFLOW
 DEVICES.
  
 2) FIRE LANE STRIPING DETAIL INDICATES
 SFBC. PLEASE SEE NFPA 1, CHAPTER 3.
  
 3) MAIN ENTRANCE LANES INDICATES TWO
 12' LANES. MINIMUM LANE TO BE AT
 LEAST 20' IN CLEAR WIDTH.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-07-16 Cont ID  
Sent By mcarsill Date 2002-07-16 Time 09:53 Rev Time 0.00
Received By mcarsill Date 2002-07-16 Time 09:35 Sent To  
Notes
2002-07-16 00:00:001) WET FIRE HYDRANTS REQUIRED PRIOR TO,
 DURING AND AFTER CONSTRUCTION.
  
 2) SECURITY GATES NOTED ON GEOMETRIC
 SITE PLAN ARE NOT WIDE ENOUGH. MINIMUM
 WIDTH SHALL BE AT LEAST TWENTY FEET (20)
 FEET IN CLEAR WIDTH.
  
 3) WHAT PROVISIONS HAVE BEEN MADE FOR
 FIRE AND PARAMEDICAL ACCESS THRU THE
 SECURITY FEATURES.
  
 4) TRAVEL LANES SHOWN BETWEEN EXISTING
 MEDICAL OFFICE BUILDING AND FUTURE
 OFFICE BUILDING DISPLAYS ONLY TWELVE
 (12) FEET. SEE PAGES C7AND C8.
  
 5) PLEASE INDICATE ANY AND ALL
 DESIGNATED FIRE LANES TO ALL NEW
 PROPOSED BUILDINGS.
  
 6) NO DETAILS ON HOW FIRE LANES WILL
 BE IDENTIFIED.
  
 7) PROPOSED WORK IS NOT TO INTEFERE
 WITH FIRE RESCUE ACCESS TO THE EXISTING
 EMERGENCY ROOM.
  
 8) NO CONSTRUCTION FENCING IS TO
 INTERFERE WITH ANY EXISTING EXIT
 DISCHARGE OR EXISTING FIRE HYDRANTS.
  
 9) TAMPER SWITCHES, CHAINS AND LOCKS
 ARE REQUIRED ON FIRE LINE BACKFLOW
 DEVICES.
  
 10) ADDITIONAL FIRE HYDRANTS APPEAR TO
 BE NEEDED NEAR THE NEW BUILDINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910