Plan Review Details - Permit 02061901
Plan Review Stops For Permit 02061901
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status   Date   Cont ID  
Sent By pkrauss Date 2002-07-30 Time 13:59 Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-07-02 Cont ID  
Sent By mcarsill Date 2002-07-02 Time 14:21 Rev Time 0.00
Received By mcarsill Date 2002-07-02 Time 14:21 Sent To  
Notes
2002-07-02 00:00:001. PLEASE PROVIDE DOCUMENTATION ON 3M
 FIREWRAP THAT WAS REFERENCED ON THE
 PLANS. TWO COPIES ARE NEEDED, ONE FOR
 THE FIELD SET AND ONE FOR THE CITY
 RETAINED COPY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-07-30 Cont ID  
Sent By pkrauss Date 2002-07-30 Time 13:59 Rev Time 0.35
Received By pkrauss Date 2002-07-30 Time 13:41 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-07-01 Cont ID  
Sent By ndenmark Date 2002-07-01 Time 15:30 Rev Time 0.50
Received By ndenmark Date 2002-07-01 Time 15:30 Sent To  
Notes
2002-07-01 00:00:00PROVIDE INSPECTIONS ON WELDS PRIOR TO
 COVERING OR CONCEALING