Plan Review Details - Permit 02061893
Plan Review Stops For Permit 02061893
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-09-06 Cont ID  
Sent By pkrauss Date 2002-09-04 Time 16:56 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-08-02 Cont ID  
Sent By dpalmer Date 2002-07-24 Time 15:49 Rev Time 2.00
Received By lmartine Date   Time   Sent To  
Notes
2002-08-02 00:00:00 
 PROVISO
 -------
  
 SUBMIT CURRENT TEST REPORTS FOR,
 CASEMENT WINDOWS, FIXED WINDOWS, GARAGE
 DOOR, STORM SHUTTERS, NOTE; NON IMPACT
 FRENCH DOORS REQUIRE SHUTTERS.
  
 SEE ZONING NOTE ON SHEET A-1 FOR SITE
 WALL PERMIT.
  
  
  
 LUIS MARTINEZ
 659-8096
 3

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-08-22 Cont ID  
Sent By dpalmer Date 2002-08-22 Time 16:46 Rev Time 0.75
Received By dpalmer Date 2002-08-22 Time 16:25 Sent To P
Notes
2002-08-22 00:00:00*********** NOTES REDLINED ON PLANS ***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-07-24 Cont ID  
Sent By pkrauss Date 2002-07-22 Time 09:42 Rev Time 0.00
Received By dpalmer Date 2002-07-24 Time 15:49 Sent To B
Notes
2002-07-24 00:00:00******************** UNSAT ************
  
 1)NOTE: PLEASE NOTE RISER DIAGRAM SHOWS
 MCB AND PANEL IS SHOWN AS MLO? PLEASE
 CORRLEATE.
  
 2) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 3) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 MISSING IN SOME LOCATIONS, PLEASE ALSO
 NOTE ALMOST THE ENTIRE HOUSE SHOWN AS
 BEING REWIRED, PLEASE CLARIFY LIVING RM
 AND DINING RM? WHAT WORK IS BEING DONE,
 NEW WIRING? EXISTING THAT MEETS 99 NEC
 ALREADY?
  
 4)) NOTE: PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
 MISSING FRONT.
  
 5))NOTE: PLEASE NOTE, EITHERMISSING
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 PLEASE NOTE HALLWAY MASTER BED RM AND
 FOYER/EXIT TO OUTSIDE. FIXTURE REQ`D
  
 6)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS
 ON ELECTRICAL PLANS.
  
 7 )NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
 ENTIRE BRANCH CIRCUIT IS REQ`D TO HAVE
 ARC FAULT PROTECTION.
  
 8)NOTE: PLEASE NOTE KITCHEN COUNTERTOP
 SPACING OF OUTLETS TO MEET 210-52 (C),
 1,2,3,4,5.
  
 9)NOTE: PLEASE NOTE ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE ARE TO BE SHOWN AS
 GFI/GFI PROTECTED. PER 210-8-A-6
  
 10)NOTE: PLEASE NOTE OCP FOR "GAS" WATER
 HEATER SHOWN AS EXCEEDING THE MAX OF
 150% OF LOAD. LOAD FOR GS WATER HEATER
 SHOWN AT 2KW? PLEASE VERFIY. 422-11E
  
 11)NOTE: PLEASE NOTE OCP/WIRE/LOAD FOR
 AHU #1 PLEASE NOTE MIN SIZING PER 424-3
 (B). 125%.MIN.
  
 12)NOTE: PLEASE ALSO NOTE OCP SHOWN AS
 2P30 FOR 2KW OF POOL HEATER 422-1
  
 13)NOTE: PLEASE NOTE THAT ONLY ONE SMALL
 APPLIANCE CIRCUIT IS SHOWN ON LOAD
 CALCULATIONSAND PANEL SCHEDULE.
 PLEASE SEE 210-52B,210-11-C-1 TWO MIN.
  
 14)NOTE: PLEASE JUST NOTE;PLAN NOTES
 MENTION ALL WIRE SMALLER THAN #10 AWG
 SHALL BE SOLID. PLEASE NOTE IF THIS IS
 NOTED, NO STRANDED WILL BE PERMITTED TO
 BE INSTALLED. PLEASE VERIFY
 MAY ONLY BE CHANGED BY ARCH OF RECORD.
  
 15)NOTE: PLEASE NOTE, PLAN NOTES MENTION
 "STANDARD BLDG CODE" PLEASE NOTE WE
 ARE UNDER THE "FL BLDG CODE"
  
 16)NOTE: PLEASE NOTE MISSING HALLWAY
 OUTLET(S) PER 210-52H
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-09-04 Cont ID  
Sent By kstevens Date 2002-08-28 Time 13:45 Rev Time 0.40
Received By pkrauss Date 2002-09-04 Time 16:28 Sent To B
Notes
2002-09-04 00:00:00MECHANICAL PERMIT 02061895

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-07-22 Cont ID  
Sent By pkrauss Date 2002-07-22 Time 09:13 Rev Time 0.45
Received By pkrauss Date 2002-07-22 Time 08:58 Sent To E
Notes
2002-07-22 00:00:00*******************DENIED***************
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 PLEASE INDICATE SIZE OF DUCT & GRILLES
 FOR THE R/A.
  
 PROVIDE ENERGY & MANUAL J CALCS IN
 ACCORDANCE WITH 2001 FBC CHAPTER 13.
  
 PLEASE NOTE ATTIC ACCESS FOR THE AHU
 SHALL BE A MINIMUM OF 30" X 22" (2001
 FBC(M) 306.2).THE SERVICE PANEL SHALL
 BE WITHIN 6 FT OF AN ATTIC ACCESS (2001
 FBC CHAPTER 13, 610.ABC.3.5.2)
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-08-28 Cont ID  
Sent By dpalmer Date 2002-08-22 Time 16:48 Rev Time 0.00
Received By kstevens Date 2002-08-28 Time 13:45 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-08-22 Cont ID  
Sent By pschmitz Date 2002-08-22 Time 06:19 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-08-22 00:00:00REVISION,APPR,PES

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-07-13 Cont ID  
Sent By jleech Date 2002-07-13 Time 10:44 Rev Time 0.33
Received By jleech Date 2002-07-13 Time 10:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-07-03 Cont ID  
Sent By sgraham Date 2002-07-03 Time 07:55 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***