| Plan Review Stops For Permit 02061846 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-07-01 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2002-07-01 |
Time |
14:27 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2002-07-01 |
Time |
14:27 |
Sent To |
|
|
| Notes |
| 2002-07-01 00:00:00 | PROVISO FROM MASTER PLAN REVIEW 02010564 | | | | | | PROVIDE MANUFACTRES INSTALLATION | | | INSTRUCTIONS FOR THE FIRE DAMPERS SHOWN | | | ON M-2 | | | | | | PROVIDE ACCESS TO FOR BOOSTER FANS | | | PROVIDE FEEDBACK TO DRYER SHOULD BOOSTER | | | FAN FAIL. | | | | | | PER FBC(M) 504.4, EXHAUST SHALL | | | TERMINATE ON THE OUTSIDE OF THE | | | BUILDING AND SHALL BE EQUIPPED WITH A | | | BACKDRAFT DAMPER AND SHALL NOT HAVE A | | | SCREEN INSTALLED AT THE DUCT | | | TERMINATION. |
|
|
|