Plan Review Details - Permit 02061792
Plan Review Stops For Permit 02061792
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-07-18 Cont ID  
Sent By btrobaug Date 2002-07-16 Time 14:56 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-07-16 Cont ID  
Sent By btrobaug Date 2002-07-16 Time 14:56 Rev Time 0.00
Received By btrobaug Date 2002-07-16 Time 14:49 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-08-05 Cont ID  
Sent By kstevens Date 2002-08-05 Time 10:14 Rev Time 0.00
Received By kstevens Date 2002-08-05 Time 10:14 Sent To  
Notes
2002-08-05 00:00:00PASSED/PROVISO
  
 FBC02001 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-07-15 Cont ID  
Sent By kstevens Date 2002-07-15 Time 18:11 Rev Time 0.00
Received By kstevens Date 2002-07-15 Time 18:11 Sent To  
Notes
2002-07-15 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 PLUMBING.
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MINIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL) TWO MAIN DRAINS SHOWN ON PIPING
 SCHEMATIC, BUT ONLY ONE SHOWN ON POOL
 LAYOUT SHEET. PLEASE CLAIRFY.
 2) FBC02001 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED. (ADD TO NOTES)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-07-18 Cont ID  
Sent By rmcdouga Date 2002-07-18 Time 14:26 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-07-18 00:00:00OK PER S.GRAHAM 7-1-02