Plan Review Details - Permit 02061757
Plan Review Stops For Permit 02061757
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-09-10 Cont ID  
Sent By btrobaug Date 2002-09-10 Time 10:26 Rev Time 0.25
Received By btrobaug Date 2002-09-10 Time 10:12 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-08-02 Cont ID  
Sent By btrobaug Date 2002-08-02 Time 07:53 Rev Time 0.00
Received By btrobaug Date 2002-08-02 Time 06:25 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-07-24 Cont ID  
Sent By btrobaug Date 2002-07-24 Time 15:29 Rev Time 0.00
Received By btrobaug Date 2002-07-24 Time 11:33 Sent To FIRE
Notes
2002-07-24 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 IN THE PLANS AND RESUBMIT FOR REVIEW:
  
 1} INDICATE THE TYPE OF GROUNDING
 ELECTRODE SYSTEM BEING USED AT THE
 GENERATOR.
  
 2} INDICATE THE GROUNDING ELECTRODE
 CONDUCTOR SIZE AND METHOD OF GROUNDING
 AT THE ATS.
  
 3} DOES THE ATS HAVE A MECHANICAL MEANS
 OF DISCONNECT?
  
 4} WHERE IS THE GENERATOR DISCONNECTING
 MEANS LOCATED?
  
 5} PLEASE LIST THE CONDUIT AND WIRE
 SIZE FROM THE EXISTING TANSFORMER TO
 THE ATS.
  
 6} PLEASE INDICATE THE CONDUIT AND WIRE
 SIZE FROM THE ATS TO MDP-1.
  
 7} INDICATE WHERE THE DISCONNECTING
 MEANS IS FOR THE BUILDING SERVICE.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-07-03 Cont ID  
Sent By btrobaug Date 2002-07-03 Time 15:11 Rev Time 0.00
Received By btrobaug Date 2002-07-03 Time 13:51 Sent To FIRE
Notes
2002-07-03 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PROVIDE THE FOLLOWING INFORMATION,MAKE
 NECESSARY CHANGES IN PLAN AND RESUBMIT
 FOR REVIEW.
  
 1} THE SCOPE OF THIS PROJECT REQUIRES AN
 ENGINEERED SET OF DRAWINGS PER 471.025
 FS AND 553-79 FAC.
  
 2} PLEASE PROVIDE A COPY OF THE
 CONTRACTFOR THE PROPOSED PROJECT
 INCLUDING THE COST OF LABOR AND
 MATERIAL PER 104.6.5 CWPB AMMENDMENTS.
  
 3} THE FPL SERVICE TO THE METER IS
 LISTED AS BEING 120/208 VOLT-3
 PHASE.THE GENERATOR INDICATES A 480
 VOLT OUTPUT ,PLEASE CLARIFY.
  
 4} FPL SERVICE IS LISTED AS 3 PHASE,4
 WIRE,BUT WITH 2 SETS OF 3EA 600
 MCM,WHICH WOULD INDICATE SINGLE
 PHASE,OR THREE PHASE WITH NO NEUTRAL.
 PLEASE CLARIFY.
  
 5} PLEASE PROVIDE A LOAD CALCULATION AND
 PANEL SCHEDULE FOR THE NEW PANEL.
  
 6} INDICATE IF THE SERVICE SHOWN IS
 EXISTING OR NEW. IF NEW PLEASE PROVIDE
 AIC RATINGS PER 110-9 AND CALCULATIONS
 PER 215-5.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-08-09 Cont ID  
Sent By btrobaug Date 2002-09-10 Time 10:26 Rev Time 0.00
Received By mcarsill Date 2002-08-09 Time 13:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-07-30 Cont ID  
Sent By btrobaug Date 2002-08-02 Time 07:53 Rev Time 0.00
Received By mcarsill Date 2002-07-30 Time 16:29 Sent To  
Notes
2002-07-30 00:00:001) PLEASE PROVIDE MORE DETAILS ON FUEL
 TANK PLANNED FOR USE. THIS WOULD
 INCLUDE ANY AND ALL PRODUCT APPROVALS
 AND APPLICABLE LISTINGS FOR IT.
  
 2) PLEASE PROVIDE MORE DETAILS ON
 GENERATOR. AGAIN PRODUCT APPROVALS
 OR SPECIFICATION BOOKS WOULD BE
 HELPFUL.
  
 3) IT WAS NOTED THAT THE FUEL TANK
 WILL BE LOCATED NEAR THE LOADING DOCK.
 IS THE FUEL TANK SUBJECT TO ANY
 MECHANICAL DAMAGE. PLEASE ADVISE.
  
 4) PLANS SHOULD INDICATE DIESEL OR
 OTHER TYPE OF FUEL PLANNED FOR THE TANK.
  
 5) PLEASE INDICATE ADJACENT PROPERTY
 LINES WITH REGARDS TO GENERATOR AND
 FUEL TANK INSTALLATION.
  
 6) THE VENT LINE FOR THE FUEL TANK
 SHALL BE A MINIMUM OF 12 FEET ABOVE THE
 TANK.
  
 7) VARIOUS DRAWINGS SHOULD BE CORRELATED
 INTO ONE DOCUMENT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-07-12 Cont ID  
Sent By btrobaug Date 2002-07-24 Time 16:16 Rev Time 0.00
Received By mcarsill Date 2002-07-12 Time 17:10 Sent To  
Notes
2002-07-12 00:00:001) PLEASE PROVIDE DETAILS ON GENERATOR
 PLANNED FOR USE.
  
 2) PLEASE PROVIDE DETAILS ON FOUR
 HUNDRED GALLON FUEL TANK.
  
 3) PLEASE INDICATE PROPERTY LINES
 BY PROVIDING A LEGAL SURVEY.
  
 4) PLEASE BE ADVISED THAT MERCER AVENUE
 IS LOCATED IN THE CITY FIRE LIMITS.
 CERTAIN RESTRICTIONS APPLY TO THE
 INSTALLATION OF ABOVEGROUND FUEL AND
 ABOVEGROUND PROPANE INSTALLATIONS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910