| 2002-07-10 00:00:00 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 02061416 |
| | ADD: 3826 PASCO NAVARRO |
| | CONT: O/B RICKETTS, ALLESTA |
| | TEL: 659-3047 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2)ALL INFORMATION, DRAWINGS, SPECIF- |
| | ICATIONS AND ACCOMPANYING DATA SHALL |
| | BEAR THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. |
| | CITY AMENDMENTS 104.2.1 |
| | |
| | 3) 1606.1.1 WHEN PLANS (R-3) ARE NOT DE- |
| | SIGNED BY A PROFESSIONAL THEY MUST MEET |
| | A PRESCRIPTIVE CODE, SUCH AS A PROVIS- |
| | IONS IN AF&PA WOOD FRAME CONSTRUCTION |
| | FOR ONE- AND TWO FAMILY DWELLINGS- 1995 |
| | SBC HIGH WIND EDITION 1996 SHALL BE PER- |
| | MITTED FOR THE APPLICABLE WOOD FRAME |
| | BUILDINGS OF GROUP R3 OCCUPANCY FOR A |
| | BASIC WIND SPEED OF 146 MPH OR LESS. |
| | |
| | 4)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 5)PROVIDE ENERGY CALCULATIONS AND |
| | EQUIPMENT SIZING CALCULATIONS (MANUAL J) |
| | AS REQUIRED BY THE 2001 FLORIDA ENERGY |
| | EFFICIENTCY CODE FOR BUILDING CONSTRUC- |
| | TION. |
| | |
| | 6)1503.4.4 PROTECTION AGAINST DECAY & |
| | TURMITES. CONDENSATE LINES & ROOF DOWN |
| | SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| | AWAY FROM THE STRUCTURE SIDEWALL, |
| | WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| | TENSIONS, OR SPLASH BLOCKS. |
| | |
| | 7)FIGURE 1606 WIND-BORNE DEBRIS |
| | REGION; INDICATES THAT W.P.B. CITY OF IS |
| | LOCATED IN THE 140 MPH ZONE. PLANS ARE |
| | TO INDICATE THIS. |
| | |
| | 8)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 9) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORT, SBCCI OR DADE COUNTY |
| | REPORT ARE ACCEPTED.MISSING REPORTS: |
| | A)WINDOWS |
| | B)DOORS EXTERIOR |
| | C)ROOFING MATERIALS |
| | D)STORM SHUTTERS |
| | SITE SPECIFIC ENGINEERING (PRODUCT |
| | APPROVAL) REQUIRES THE WET SIGNATURE, |
| | DATE AND EMBOSSED SEAL OF THE ENGINEER |
| | CERTIFYING THE PRODUCT AND SIGNATURE |
| | AND SEAL OF THE DESIGN PROFESSIONAL |
| | OF RECORD. |
| | FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | |
| | 10) 1606.4.4 ANCHOR METHODS. PROVIDE |
| | INFORMATION FOR INSTALLATION OF DOOR |
| | AND WINDOW BUCKS. |
| | |
| | 11)1707.3.1 JOIST HANGERS, FRAMING |
| | ANCHORS & SIMILAR DEVICES SHALL BE TEST- |
| | ED IN ACCORDANCE W/ ASTM D 1761 & BE |
| | LABELED AND LISTED FOR THEIR LOAD CARRY- |
| | ING CAPACITY. |
| | |
| | 12) 1804.1.3 THE BOTTOM OF THE FOUNDA- |
| | TION SHALL EXTEND NO LESS THAN 12" |
| | BELOW FINISH GRADE. |
| | |
| | 13) 2304.5 CLEARENCE BETWEEN WOOD SIDING |
| | & EARTH ON THE EXTERIOR OF A BUILDING |
| | SHALL NOT BE LESS THAN 6" EXCEPT WHERE |
| | SIDING, SHEATHING AND FRAME WALL ARE OF |
| | APPROVED DURABLE WOOD OR APPROVED PRE- |
| | SERVATIVE TREAATED WOOD. |
| | |
| | 14) FL BLDG 1909.3 (EXEPTION# 2) |
| | CONCRETE SLABS ON GRADE CONTAINING 6X6/ |
| | W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| | FABRIC LOCATED IN THE MIDDLE TO THE |
| | UPPER 1/3RD OF THE SLAB SHALL BE SUP- |
| | PORTED BY APPROVED MATERIALS OR SUPPORTS |
| | AT SPACING NOT TO EXCEED 3 FT OR IN |
| | ACCORDANCE WITH MANUFACTURER'S SPEC. |
| | |
| | 15) 1203.5 MECHANICAL VENTILATION |
| | REQUIRED FOR BATHROOM, NO WINDOW, WINDOW |
| | WOULD REQUIRE NO LESS THAN 3 SQ FT |
| | OPEN AREA. |
| | |
| | 16)2504.2.2 INSTALLATION OF EXTERIOR |
| | LATHING AND FRAMING SHALL COMPLY WITH |
| | ASTM C-1063. |
| | |
| | 17)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDEN- |
| | TIFYING THE SHEET OR SPECIFICATION PAGE |
| | WHERE THE CHANGES CAN BE FOUND, WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | JIM WITMER |
| | PLAN REVIEW |
| | TEL: (561)659-8096 EX.8412 |
| | FAX: (561)659-8026 |