Plan Review Details - Permit 02061404
Plan Review Stops For Permit 02061404
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-07-14 Cont ID  
Sent By pkrauss Date 2002-06-27 Time 08:32 Rev Time 1.50
Received By jwitmer Date 2002-07-14 Time 14:49 Sent To  
Notes
2002-07-14 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02061404
 ADD: 633 33RD ST
 CONT: FALLON CONSTRUCTION CORP
 TEL: (305) 971-8110
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) ENGINEER TO DETERMINE AS TO THE FIRE
 DAMAGE TO THE FLOOR JOIST,CEILING JOIST,
 RAFTERS OR TRUSS ASSEMBLIES. ENGINEER TO
 DESCRIBE THE AMOUNT OF FLOOR JOIST, CEIL
 ING JOIST OR RAFTERS TO BE REPLACED, OR
 IF NEW MATERIALS ARE TO BE SISTERED TO
 FIRE DAMAGED FRAMING MEMBERS, THE SPLICE
 THE AMOUNT OF FASTENERS, SIZE, ETC.
  
 2) THE WRONG FORM IS USED FOR THE ENERGY
 CALCULATIONS, CHAP. 13.101.2.3 RENOVA-
 TIONS, RENOVATED BUILDINGS SHALL, MEET
 THE PRESCRIPTIVE CONTAINED IN METHOD C
 OF SUB-CHAPTER 6 FOR RESIDENTIAL BUILD-
 ING.
 NO INSULATION UNDER WOOD FLOOR?
  
 3) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THE PLAN DOES NOT INDICATE AS TO WHAT
 THE WALLS ARE CONSTRUCTED OF? WOOD WALLS
 DO THEY MEET THE WIND REQUIREMENTS,
 CONTINIOUS WIND RESTRAINT?
  
 4)FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 5)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 6) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) WINDOW MULLION
 B) ROOFING
  
 7)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 8)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 9)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE. ATTACHED SAMPLE SCHEDULE.
  
 10) 1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-06-26 Cont ID  
Sent By btrobaug Date 2002-06-26 Time 14:06 Rev Time 0.00
Received By btrobaug Date 2002-06-26 Time 13:34 Sent To M
Notes
2002-06-26 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 THE PLANS DO NOT INDICATE THE SCOPE OF
 THE ELECTRICAL WORK.
 THE FOLLOWING INFORMATION IS NEEDED FOR
 THE SERVICE;
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} INDICATE THE EQUIPMENT GROUNDING
 CONDUCTOR PER 250-122.(DISCONNECT TO
 PNL).
  
 3} SHOW THE LOCATION OF THE METER AND
 MAIN DISCONNECT ON THE PLAN.
  
 4} NOTE:PANEL "C" IS SHOWN WITH A
 200AMP CIRCUIT BREAKER,IF THIS IS SHOWN
 ON THE APPROVED SET OF PLANS IT MUST BE
 INSTALLED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-06-27 Cont ID  
Sent By btrobaug Date 2002-06-26 Time 14:07 Rev Time 0.35
Received By pkrauss Date 2002-06-27 Time 07:43 Sent To B
Notes
2002-06-27 00:00:00DENIED:
  
 COMMENT #6 (PLAN SHEET A-2) EXHASUT FANS
 FOR BATHROOMS SHALL BE RECIRCULATING. AS
 PER 2001 FBC(M) 502.1, EXHUAST SHALL
 DISCHARGE TO THE OUSIDE OF THE BUILDING.
  
 AS PER 2001 FBC(M) 401.6, AIR EXHAUST &
 INTAKE OPENINGS THAT TERMINATE OUTDOORS
 SHALL BE PROTECTED WITH CORROSION
 RESISTANT SCREENS, LOUVERS OR GRILLES.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 RETURN AIR SHALL BE EQUAL TO SUPPLY
 AIR BY MEANS OF AIR TRANSFER OR A RETURN
 AIR (JUMPER).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-06-27 Cont ID  
Sent By pkrauss Date 2002-06-27 Time 08:29 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
2002-06-27 00:00:00NO PLUMBING PLANS SUBMITTED FOR REVIEW.
 PHK

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***