Plan Review Details - Permit 02061272
Plan Review Stops For Permit 02061272
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-08-15 Cont ID  
Sent By btrobaug Date 2002-08-15 Time 18:08 Rev Time 0.00
Received By btrobaug Date 2002-08-15 Time 17:41 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-07-05 Cont ID  
Sent By btrobaug Date 2002-07-05 Time 09:03 Rev Time 0.00
Received By btrobaug Date 2002-07-05 Time 08:19 Sent To R
Notes
2002-07-05 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THE FOLLOWING
 CHANGES/ADDITIONS TO THE PLANS MUST BE
 MADE FOR CODE COMPLIANCE:
  
 1} THE #6 EQUIPMENT GROUND RUNNING FROM
 THE METER TO THE FIRST MEANS OF
 DISCONNECT MUST NOT BE RAN AS IT WOULD
 CREATE A PARALLEL PATH TO GROUND WITH
 THE NEUTRAL(GROUNDED
 CONDUCTOR).250-24(A)(5).
  
 2} PANEL "A" IS MARKED AS MAIN &
 MLO,PLEASE CLARIFY.
  
 3} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 4} PLEASE NOTE THAT THE SWITCH AT THE
 TOP OF THE STAIR CONTROLLING THE STAIR
 LIGHTS SHOULD BE A 3-WAY.
  
 5} THE WALL BETWEEN BEDROOM AND MECH.
 ROOM DOORS IN BEDROOM #3 NEEDS A RECEPTA
 CLE PER 210-52(A)(1)(A).
  
 6} A RECEPTACLE NEEDS TO BE ADDED IN
 BEDROOM #3 ON THE NORTH WALL
 PER 210-52(A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL:
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-12-18 Cont ID  
Sent By pkrauss Date 2002-12-18 Time 16:14 Rev Time 0.20
Received By pkrauss Date 2002-12-18 Time 16:04 Sent To  
Notes
2002-12-18 00:00:00MECH PERMIT 02061322
 REVISED ENERGY CALCS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-08-15 Cont ID  
Sent By hmoser Date 2002-08-15 Time 19:36 Rev Time 0.50
Received By hmoser Date 2002-08-15 Time 19:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-07-02 Cont ID  
Sent By btrobaug Date 2002-08-15 Time 18:08 Rev Time 0.33
Received By hmoser Date 2002-07-02 Time 19:56 Sent To  
Notes
2002-07-02 00:00:00PLAN DENIED
 1) CAN NOT READ PLANS
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-12-18 Cont ID  
Sent By kstevens Date 2002-12-18 Time 08:44 Rev Time 0.10
Received By kstevens Date 2002-12-18 Time 08:44 Sent To  
Notes
2002-12-18 00:00:00SUBMITTAL LETTER - DELETE REQUIREMENT TO
 INSULATE HOT WATER LINES.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-06-25 Cont ID  
Sent By jleech Date 2002-06-25 Time 17:57 Rev Time 0.33
Received By jleech Date 2002-06-25 Time 17:56 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2002-09-12 Cont ID  
Sent By rmcdouga Date 2002-09-12 Time 11:36 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-09-12 00:00:00REVISION TO CHANGE SLIDING GLASS DOOR
 FROM 3 PANEL TO 2 PANEL IS OK 9-12-02.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-08-16 Cont ID  
Sent By rmcdouga Date 2002-08-16 Time 16:01 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-08-16 00:00:00************BUILDING PROVISO************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR THREE PANEL SLIDING GLASS
 DOORS PRIOR TO INSTALLATION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-08-05 Cont ID  
Sent By btrobaug Date 2002-08-15 Time 17:47 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-08-05 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) 2001 FBC SECTION 1909.3 REQUIRES
 THE WELDED WIRE MESH IN THE SLAB TO BE
 SUPPORTED WITH THE SPACING BETWEEN
 SUPPORTS NOT TO EXCEED THREE (3) FEET.
 PLEASE REVISE NOTES ON S1 AND S5.
  
 3) DRAFTSTOPPING OF THE FLOOR/CEILING
 SPACE IS REQUIRED BY 2001 FBC 2305.2.2.
 PLEASE REVISE NOTE ON S1 TO REFERENCE
 2001 FBC AND INDICATE WHAT TYPE OF 5/8"
 MATERIAL WILL BE USED.
  
 4) PLEASE REVISE DETAIL 8 ON S4 TO
 REFERENCE THE 2001 FBC.
  
 5) REVISE NOTE 4 UNDER GENERAL NOTES ON
 S4 TO CITY OF WEST PALM BEACH AMENDMENTS
  
 6) INDICATE THE POSITIVE AND NEGATIVE
 WINDLOAD PRESSURES FOR THE SKYLIGHT AND
 GLASS BLOCK OPENINGS.
  
 7) PLEASE INDICATE THE CALL SIZE FOR THE
 2840 SH WINDOWS AT BEDROOM #2. THIS SIZE
 WINDOW DOES NOT MEET EMERGENCY EGRESS
 REQUIREMENTS FOR SECOND FLOOR.
 PROVIDE EMERGENCY EGRESS WINDOW IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGHT OF 24INCHES,NET CLEAR
 OPENING WIDTH OF 20 INCHES AND NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ.FT. SILL HEIGHT
 SHALL NOT BE MORE THAN 44 INCHES ABOVE
 THE FLOOR. 2001 FBC 1005.4
  
 8) PROVIDE THE COMPLETE PRODUCT APPROVAL
 FOR THE KDI STRUCTURAL WINDOW MULLIONS.
 (THREE SHEETS OF DRAWINGS WERE ALL THAT
 WAS SUBMITTED)
  
 9) THE SBCCI PRODUCT EVALUATION REPORT
 IS LIMITED TO TWO PANEL SLIDING GLASS
 DOORS. THE PLANS INDICATE A THREE PANEL
 SGD AT THE MASTER BEDROOM. PLEASE
 SUBMIT THE APPROPRIATE PRODUCT APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2002-06-24 Cont ID  
Sent By sgraham Date 2002-06-24 Time 10:15 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***