| Plan Review Stops For Permit 02061131 |
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-07-23 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2002-07-23 |
Time |
13:27 |
Rev Time |
0.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-07-23 00:00:00 | RE-SUB OK, PES |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-06-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-06-24 |
Time |
14:12 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-06-24 |
Time |
14:12 |
Sent To |
|
|
| Notes |
| 2002-06-24 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER THE FBC-2OO1 | | | FUEL GAS SED 402.2. (FOR UTILITY SHED) | | | 2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE FBC- | | | 2001 FUEL GAS CODE SEC. 402.2. (NO LIST- | | | ING SHOWN ON PAPERWORK). | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
|