Plan Review Details - Permit 02061124
Plan Review Stops For Permit 02061124
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2002-06-25 Cont ID  
Sent By mamini Date 2002-06-25 Time 08:25 Rev Time 3.00
Received By mamini Date 2002-06-25 Time 08:25 Sent To  
Notes
2002-06-25 00:00:00PASSED WITH PROVISOS :
 1. POLLUTION / EROSION PLAN MUST BE
 INSTALLED IN FIELD PRIOR TO ANY CONS-
 TRUCTION WORKS BEGIN.
 2. CONTRACTOR MUST COMPLY WITH ATTACHED
 CLARIFICATION LETTER BY MR. WILLIAM S.
 TEASDALE,P.E. OF WST GROUP, SITE WORKS
 ENGINEER OF RECORD.
 3. ANY WORK WITHIN PUBLIC R.O.W WILL
 REQUIRE A SEPARATE PERMIT FROM CITY
 ENGINEERS' OFFICE , 659-8040.
 4. UPON ISSUANCE OF THE SFWMD PERMIT, A
 COPY MUST BE SUBMITTED TO THE
 CONSTRUCTION SERVICES, ATTENTION,
 MOHAMMAD R. AMINI.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-06-27 Cont ID  
Sent By mcarsill Date 2002-06-27 Time 12:55 Rev Time 0.00
Received By mcarsill Date 2002-06-27 Time 12:55 Sent To  
Notes
2002-06-27 00:00:001) SINGLE HOSE FIRE HYDRANTS ARE NOT
 PERMITTED. ONLY APPROVED FIRE HYDRANTS
 THAT MEET UTILITY AND FIRE RESCUE
 STANDARDS WILL BE ACCEPTED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-06-21 Cont ID  
Sent By mcarsill Date 2002-06-21 Time 11:22 Rev Time 0.00
Received By mcarsill Date 2002-06-21 Time 11:22 Sent To  
Notes
2002-06-21 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO,DURING AND AFTER CONSTRUCTION.
  
 2) FIRE DEPARTMENT CONNECTIONS ARE TO
 BE LOCATED NO FARTHER THAN 150 FEET
 FROM FIRE HYDRANTS.
  
 3) THERE APPEARS TO BE SOME CONFUSION
 WITH SP1 AND SP4. FIRE HYDRANTS AND
 FIRE DEPARTMENT CONNECTIONS ARE
 SEPARATE DEVICES AND SHOULD BE SHOWN
 AS SEPARATE DEVICES.
  
 4) ALL ENTRY GATES ARE TO BE PERMITTED
 SEPARATELY. ALL ENTRY WAYS SHALL BE
 AT LEAST 20 FEET IN CLEAR WIDTH.
 PROVISIONS ARE TO BE MADE FOR FIRE
 AND PARAMEDICAL ACCESS. IF ELECTRIC,
 PROVISIONS ARE TO BE MADE FOR ACCESS
 WHEN POWER IS LOST.
  
 5) POST INDICATOR VALVES ARE REQUIRED.
  
 6) FIRE LINE BACKFLOW DEVICE(S) ARE TO
 BE SUPERVISED WITH TAMPER SWITCHES AND
 BE CHAINED AND LOCKED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL