Plan Review Details - Permit 02061124
| Plan Review Stops For Permit 02061124 |
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2002-06-25 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2002-06-25 |
Time |
08:25 |
Rev Time |
3.00 |
| Received By |
mamini |
Date |
2002-06-25 |
Time |
08:25 |
Sent To |
|
|
| Notes |
| 2002-06-25 00:00:00 | PASSED WITH PROVISOS : | | | 1. POLLUTION / EROSION PLAN MUST BE | | | INSTALLED IN FIELD PRIOR TO ANY CONS- | | | TRUCTION WORKS BEGIN. | | | 2. CONTRACTOR MUST COMPLY WITH ATTACHED | | | CLARIFICATION LETTER BY MR. WILLIAM S. | | | TEASDALE,P.E. OF WST GROUP, SITE WORKS | | | ENGINEER OF RECORD. | | | 3. ANY WORK WITHIN PUBLIC R.O.W WILL | | | REQUIRE A SEPARATE PERMIT FROM CITY | | | ENGINEERS' OFFICE , 659-8040. | | | 4. UPON ISSUANCE OF THE SFWMD PERMIT, A | | | COPY MUST BE SUBMITTED TO THE | | | CONSTRUCTION SERVICES, ATTENTION, | | | MOHAMMAD R. AMINI. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-06-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-06-27 |
Time |
12:55 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-06-27 |
Time |
12:55 |
Sent To |
|
|
| Notes |
| 2002-06-27 00:00:00 | 1) SINGLE HOSE FIRE HYDRANTS ARE NOT | | | PERMITTED. ONLY APPROVED FIRE HYDRANTS | | | THAT MEET UTILITY AND FIRE RESCUE | | | STANDARDS WILL BE ACCEPTED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-06-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-06-21 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-06-21 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2002-06-21 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | | TO,DURING AND AFTER CONSTRUCTION. | | | | | | 2) FIRE DEPARTMENT CONNECTIONS ARE TO | | | BE LOCATED NO FARTHER THAN 150 FEET | | | FROM FIRE HYDRANTS. | | | | | | 3) THERE APPEARS TO BE SOME CONFUSION | | | WITH SP1 AND SP4. FIRE HYDRANTS AND | | | FIRE DEPARTMENT CONNECTIONS ARE | | | SEPARATE DEVICES AND SHOULD BE SHOWN | | | AS SEPARATE DEVICES. | | | | | | 4) ALL ENTRY GATES ARE TO BE PERMITTED | | | SEPARATELY. ALL ENTRY WAYS SHALL BE | | | AT LEAST 20 FEET IN CLEAR WIDTH. | | | PROVISIONS ARE TO BE MADE FOR FIRE | | | AND PARAMEDICAL ACCESS. IF ELECTRIC, | | | PROVISIONS ARE TO BE MADE FOR ACCESS | | | WHEN POWER IS LOST. | | | | | | 5) POST INDICATOR VALVES ARE REQUIRED. | | | | | | 6) FIRE LINE BACKFLOW DEVICE(S) ARE TO | | | BE SUPERVISED WITH TAMPER SWITCHES AND | | | BE CHAINED AND LOCKED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
|
|
|