Plan Review Details - Permit 02061083
Plan Review Stops For Permit 02061083
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2002-12-26 Cont ID  
Sent By jwitmer Date 2002-12-26 Time 13:58 Rev Time 0.50
Received By jwitmer Date 2002-12-26 Time 13:33 Sent To  
Notes
2002-12-26 00:00:00RESTRAUNT REVISION 11-13-02 MECH UNIT
 SUPPORT

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-11-12 Cont ID  
Sent By jwitmer Date 2002-11-12 Time 14:47 Rev Time 1.25
Received By jwitmer Date 2002-11-12 Time 14:47 Sent To  
Notes
2002-11-12 00:00:00PRODUCT APPROVAL STOREFRONT/JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-09-09 Cont ID  
Sent By btrobaug Date 2002-11-07 Time 18:37 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2002-09-09 00:00:00PROVISO:
 1) IMPACT FEES TO BE PAID TO COUNTY OR
 PLANS STAMPED NO FEES DUE.JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-08-29 Cont ID  
Sent By jwitmer Date 2002-08-29 Time 14:02 Rev Time 4.00
Received By jwitmer Date 2002-08-29 Time 14:02 Sent To  
Notes
2002-08-29 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02061083
 ADD: 700 S ROSEMARY B-19
 CONT: SHAKMAN
 TEL: (561)750-8288
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) EXTERIOR DOOR A-001 REQUIRES A 1 1/2
 HR RATING, TABLE 705.1.2, SEE NOTE 2.
  
 2) SHEET A-5.01 WALL DETAIL INDOCATES
 THE USE OF ELEVATED BOOTHS:
 11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENETRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY. PROVIDE INFORMATION HOW YOU
 WILL COMPLY WITH THIS SECTION! PROVIDE
 PRODUCT INFO. FOR LIFT, ETC ...
  
 3) INDICATE ON PLANS COMPLIANCE WITH
 403.2.4.1 PERMANENT PLATFORMS MAY BE
 CONSTRUCTED OF "FIRE RETARDANT TREATED
 WOOD" FOR TYPE I, II III OR IV CONSTRUC-
 TION.
  
 4) REMOVE ALL OLD PAGES FROM PLAN, RESUB
 WITH ONLY 1OLD SET OF PLANS WITH CORREC-
 TIONS!!!!!
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-07-30 Cont ID  
Sent By jwitmer Date 2002-07-30 Time 07:00 Rev Time 7.00
Received By jwitmer Date 2002-07-30 Time 07:00 Sent To  
Notes
2002-07-30 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT:02061083
 ADD: 700 S ROSEMARY AV #212
 CONT: SHAKMAN CONSTRUCTION
 TEL: (561)750-8288
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) TOTAL OCCUPANT LOAD GIVEN 413, VS
 TABLE 103.1 CALCULATION @ 510.
  
 2) PLANS STATE THAT 3 EXIT DOORS ARE
 AVAILABLE, SEC 1001.1.3 STATES THAT
 MEANS OF EGRESS SHALL NOT BE PERMITTED
 THROUGH KITHENS OR RESTROOMS, ONLY (2)
 EXITS EXIST.
  
 3) MAXIMUM OCCUPANT LOAD FOR THE (2)
 EXITS, 34"X3=102"/.2= 510 PERSONS,
 MAXIMUM.
  
 4) TABLE 704.1, OCCUPANCY SEPERATION
 REQUIES 2HRS., NO INFO GIVEN FOR DOOR
 OPENING A-001 REQUIRES 1 1/2 HR. PROTEC-
 TION, SEE TABLE 705.1.2.
  
 5) 1019.7 (1-2) PANIC HARDWARE REQUIRED
 FOR A-2 > 300 PERSONS.
  
 6) COOLER DOOR VS CORRIDOR 012:
 DURING ITS SWING, ANY DOOR IN A MEANS OF
 EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST
 ONE HALF OF THE REQUIRED WIDTH OF THE
 AISLE, CORRIDOR, PASSAGEWAY OR LANDING,
 NOR PROJECT MORE THAN 7" INTO THE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR OR
 LANDING WHEN FULLY OPEN.
  
 7) SEC 1019.8.1.IN BUILDING OF A GROUP A
 OCCUPANCY, FLIGHTS OF LESS THAN 3 RISERS
 SHALL NOT BE USED IN INTERIOR OR EXTER-
 IOR STAIRWAYS, EXIT PASSAGEWAYS, AILES,
 AT ENTRANCE OR ELSEWHWHERE IN CONNECTION
 WITH REQUIRED EXITS.
  
 8)11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENETRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY.
  
 9)11-4.1.3(3) GROUND & FLOOR SURFACES
 ALONG ACCESSIBLE ROUTES & IN ACCESSIBLE
 ROOMS & SPACES SHALL COMPLY WITH
 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE)
 A STATIC COEFFICIENT OF FRICTION OF 0.6
 IS RECOMENDED FOR ACCESSIBLE ROUTES
 AND 0.8 FOR RAMPS.
  
 10) 11-5.2 COUNTERS & BARS, 11-5.4
 DINING AREAS, INDICATE CODE COMPLIANCE.
  
 11) 1016.1.1MEANS OF EGRESS ILLUMINATION
 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH THIS SECTION
 FOR EVERY BUILDING AND STRUCTURE.FOR THE
 PURPOSE OF THIS REQUIREMENT, EXIT ACCESS
 SHALL INCLUDE STAIRS, AILES, CORRIDORS
 RAMPS, AND EXIT PASSAGEWAYS LEADING TO A
 PUBLIC WAY.
  
 12) 1016.1.3 THE FLOORS AND OTHER WALK-
 ING SURFACES WITHIN AN EXIT AND WITHIN
 THE PORTIONS OF THE EXIT ACCESS AND EXIT
 DISCHARGE DESIGNATED IN 1016.1.1 SHALL
 BE ILLUMINATED TO VALUES OF AT LEAST
 1-FT CANDLE MEASURED AT THE FLOOR.
  
 13) EMERGENCY LIGHTING AND STANDBY POWER
 1016.2.1 FOR THE PURPOSE OF THIS REQUIRE
 MENT EXIT ACCESS SHALL INCLUDE DESIGNAT-
 ED STAIRS, AISLES,RAMPS & CORRIDORS.
 PROVIDE INFO.
  
 14) STAGES & PLATFORMS, LOADS: 403.2.3.1
 THE DESIGN OF PLATFORMS SHALL COMPLY
 WITH THE REQUIREMENTS OF CHAP 16.
 PROVISIONS SHALL BE MADE FOR THE LOADS
 IN 403.2.3.2 AND TABLE 1604.1, LIVE LOAD
  
 15) 403.2.4.1 PERMANENT PLATFORMS MAY
 BE CONSTRUCTED OF "FIRE RETARDANT TREAT-
 ED WOOD"FOR TYPES I, II, III, AND IV
 CONSTRUCTION.
  
 16) WILL THE SPACE BENEATH THE PERMANENT
 PLATFORM BE USED FOR STORAGE OR ANY
 OTHER PURPOSE OTHER THAN EQUIPMENT,
 WIRING OR PLUMBING?
  
 17) SHEET A-5.01 BREWERY WALL DETAIL
 INDICATES AN ELEVATED BOOTH ARRANGEMENT,
 11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENETRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY.
  
 18) 1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 19)1511.7ROOF MOUNTED MECHANICAL UNITS
 SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGTH IN ACCORDANCE WITH TABLE 1511.7.
  
 20) A-3.01 DETAIL MECHANICAL PLATFORM @
 KITHEN, THIS DETAIL, THIS CONSTRUCTION
 OF A MEZZANINE SHALL MEET THE REQUIRE-
 MENTS OF 503.2.3.1-4.
  
 21) INDICATE CODE CONFORMANCE FOR 1 HR
 RATING ON WALLS & FLOOR OF MEZZANINE?
  
 22) INDICATE THE ALLOWABLE SAFE FLOOR
 LOADS OF MEZZANINE, IS EQUIPMENT TO
 SET ON THE FLOOR? OR IS THERE ROOM FOR
 ADDITIONAL STORAGE?
  
 23)106.4.2 STORAGE & FACTORY- INDUS-
 TRIAL OCCUPANCIES. IT SHALL BE THE
 RESPONSIBILITY OF THE OWNER, AGENT,
 PROPIETOR OR OCCUPANT OF GROUP S AND
 GROUP F OCCUPANCIES, OR ANY OCCUPANCY
 WHERE EXCESSIVE FLOOR LOADING IS LIKELY
 TO OCCUR, TO EMPLOY A COMPETENT ARCHI-
 TECT OR ENGINEER IN COMPUTING THE SAFE
 FLOOR LOAD CAPACITY. ALL SUCH COMPUTA-
 TIONS SHALL BE ACCOMPANIED BY AN AFFA-
 DAVIT FROM THE ARCHITECT OR ENGINEER
 STATING THE SAFE ALLOWABLE FLOOR LOADS
 ON EACH FLOOR IN POUNDS PER SQ FT.THE
 COMPUTATIONS & AFFADAVIT SHALL BE FILED
 AS A PERMANENT RECORD OF THE BLDG DEPT.
  
 ADDITIONAL SQ FT (MEZZANINE) REQUIRES
 REVIEW BY COUNTY FOR POSSIBLE ASSESSMENT
 OF IMPACT FEES.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2003-04-30 Cont ID  
Sent By dpalmer Date 2003-04-30 Time 07:52 Rev Time 0.33
Received By dpalmer Date 2003-04-30 Time 07:52 Sent To  
Notes
2003-04-30 00:00:00REV TO NOTES ONLY.
 PANEL/BRKR TYPE.

Review Stop E ELECTRICAL
Rev No 7 Status N Date 2003-04-16 Cont ID  
Sent By sthyng Date 2003-04-28 Time 09:19 Rev Time 0.50
Received By dpalmer Date 2003-04-16 Time 08:53 Sent To  
Notes
2003-04-16 00:00:00PLAN SUBMITTED W/ NOTES FOR PANEL BOARD
 AND TYPE OF BRKRS.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2003-01-07 Cont ID  
Sent By dpalmer Date 2003-01-07 Time 06:17 Rev Time 1.00
Received By dpalmer Date 2003-01-07 Time 06:16 Sent To  
Notes
2003-01-07 00:00:00REVISION IN SET FOR BREWERY TO BE
 SUBMITTED UNDER BREWERY PERMIT.
 TWO COPIES OF 4.03 BACK TO CONTRACTOR.
  
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2002-12-19 Cont ID  
Sent By dpalmer Date 2002-12-19 Time 16:13 Rev Time 1.50
Received By dpalmer Date 2002-12-19 Time 16:13 Sent To  
Notes
2002-12-19 00:00:00**************UNSAT ****************
  
 1)NOTE: PLEASE NOTE THERE ARE STILL
 ITEMS ON PLANS /RISER/PANELS/ AND
 EQUIPMENT SUMMARY.
 PLEASE ALSO NOTE ITMES FOR BREWERY
 PANEL/EQUIPMENT NEED TO BE VERIFIED ALSO
 .(CHILLER MENTIONS SEE PANEL SCHEDULE)
 ?? NOT SHOWN ON PANEL?
  
 2)NOTE: PLEASE SUBMIT ONLY REVISIONS
 ON REST WITH THIS PERMIT # AND ANY
 REVISIONS FOR BREWERY ON BREWERY PERMIT
 #.
  
 PLEASE SEE ATTACHED LETTER PERTAINING
 TO 553.80(2B) FAC.COMMENTS FOR RISER
 DIAGRAM HAS NOW BEEN THE LAST THREE
 REVIEWS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2002-12-05 Cont ID  
Sent By dpalmer Date 2002-12-05 Time 09:32 Rev Time 2.00
Received By dpalmer Date 2002-12-05 Time 09:32 Sent To  
Notes
2002-12-05 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE NOTES AND ITEMS FROM
 PREVIOUS REVIEW WERE NOT ADDRESSED AND
 PLANS STILL DO NOT CORRELATE.
 THERE ARE MANY ITEMS ON RISER DIAGRAM
 THATSTILL DO NOT CORRELATE WITH
 PANEL SCHEDULES/PANELS.
  
 2)NOTE: PLEASE NOTE SITUATION WITH(K-38)
 OVEN HAS ALSO NOT BEEN ADRESSED???
 SHOWN ON GAS RISER AND AS ELEC ALSO.
 IT WAS BROUGHT TO OUR ATTENTION BY
 CONTRACTOR THAT DOUBLE OVEN WAS NO
 LONGER GAS AND WAS GOING TO BE ONLY
 ELECTRIC. THE LAST FOUR TIMES PLANS
 HAVE COME IN FOR REVIEW, ALL STILL SHOW
 AS GAS AND ELECTRIC????
 PLEASE VERIFY AND MAKE ANY NESS. CHANGES
  
 3)NOTE: PLEASE THERE ARE ITEMS ON
 KITCHEN EQUIPMENT SCHEDULE THAT DO NOT
 CORRELATE CIRCUTI #`S WITH SAME ITEMS
 ON PANEL SCHEDULES??
  
 4)NOTE:PLEASE SEE LETTER ATTACHED;
 PLEASE NOTE A FOUR TIMES FEE HAS BEEN
 ADDED FOR PLAN REVIEW PORTION OF PERMIT
 FEE. THIS IS REQ`D UNDER FAC.553.80(2)B
 PLEASE SEE ATTACHED BZ RECEIPT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL, OR IF A MEETING IS NEEDED
 TO GO OVER PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-10-29 Cont ID  
Sent By dpalmer Date 2002-10-29 Time 10:46 Rev Time 0.75
Received By dpalmer Date 2002-10-29 Time 10:46 Sent To P
Notes
2002-10-29 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE, LAST REVISION HAD
 A PROVISO THAT THE DOUBLE OVEN (K-38)
 WAS CHANGING FROM GAS TO ELECTRIC?
 PLEASE NOTE PLANS STILL SHOW AS GAS ON
 ELECTRICAL PLANS AND GASRISER.
 PLEASE CLARIFY.
  
 2)NOTE: LAST SET OF PLANS WERE REDLINED
 FOR SIGN CIRCUIT REQ`D TO BE DEDICATED.
 PLEASE NOTE PANEL SCHEDULE STILL SHOWS
 W/ SHOW WINDOW RECEPTS. PLEASE CORRECT
 600-5
  
 3)NOTE; PLEASE NOTE, RISER DIAGRAM
 AND PANEL SCHEDULES DO NOT CORRELATE.
 PLEASE NOTE OCP SHOWN ON M1 TO FEED
 T-TX-1, DOES NOT CORRELATE W/ RISER.
 PLEASE ALSO NOTE PANEL "BRW3" DOES NOT
 SHOW A FEED/OCP TO TRASNFORMER TX-2?
 PLEASE CLARIFY TX-2 SHOWN ON PANEL
 M2??
  
 PLEASE CORRELATE PLANS AND SUBMIT FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-08-28 Cont ID  
Sent By dpalmer Date 2002-08-28 Time 06:22 Rev Time 0.50
Received By dpalmer Date 2002-08-28 Time 06:21 Sent To  
Notes
2002-09-12 00:00:00PLEASE ALSO NOTE DOUBLE OVEN IS NOW
 ELECTRIC AND HAS BEEN REMOVED FROM GAS
 PLANS.
 PLEASE PROVIDE REVISED PLANS, TO INCLUDE
 PANEL SCHEDULES/LOAD CALCUALTIONS ETC.
 BEFORE ANY ELECTRICAL INSPECTION IS
 CALLED IN.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
2002-08-28 00:00:00******* NOTES REDLINED ************
  
 PLEASE NOTE, PLANS REDLINED FOR SIGN
 CIRCUIT TO BE DEDICATED PER 600-5.
 SHOWN ON CIRCUIT W/ WINDOW RECEPTS.
  
  
 DEWEY PALMER
 ELECTRCIAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-07-15 Cont ID  
Sent By dpalmer Date 2002-07-15 Time 12:24 Rev Time 0.00
Received By dpalmer Date 2002-07-15 Time 12:24 Sent To  
Notes
2002-07-15 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE CLARIFY GROUNDING FOR
 TRANSFORMERS PER 250-30
  
 2)NOTE: PLEASE CLARIFY TEMPORARY OCP FOR
 #3 CONDUCTORS FEEDING "M2".
 SHOWS 600A
  
 3)NOTE: PLEASE NOTE THAT A DISC IS SHOWN
 ON RISER DIAGRAM AFTER "TX-1" TO MEET
 240-21. PLEASE CLARIFY LOCATION OF THIS
 DISC ON PLANS?? NOT SHOWN ON E-4.02
 PLEASE NOTE CLEARENCES FOR EQUIPMENT
 ON MEZZ/STORAGE FOR DEDICATED ELECTRICAL
 SPACE PER 110-26.
  
 4)NOTE: PLEASE CLARIFY MISSING GFI FOR
 ROOF TOP A/C EQUIPMENT PER 210-63. IS
 THIS EXISTING?
  
 5)NOTE: PLEASE NOTE THAT NOTE ON E-4.01
 MENTIONS ALL RECEPTS WITHIN 2' OF WET
 AREAS ARE TO BE GFI. PLEASE NOTE THAT
 PER LOCAL AMENDMENTS ALL RECEPTS W/IN
 6' OF SINKS/WET AREAS ARE TO BE GFI/GFI
 PROETCTED. 210-8
  
 6)NOTE: PLEASE CLARIFY LOCATION OF SIGN
 CIRCUIT PER 600-5
  
 7)NOTE: PLEASE CLARIFY LOCATION OF SHOW
 WINDOW OUTLETS PER 210-62.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2003-01-02 Cont ID  
Sent By mcarsill Date 2003-01-02 Time 14:20 Rev Time 0.00
Received By mcarsill Date 2003-01-02 Time 14:20 Sent To  
Notes
2003-01-02 00:00:00FIRE ALARM PLANS SUBMITTED UNDER MASTER
 PERMIT NUMBER. PLEASE PROVIDE A
 SEPARATE PERMIT NUMBER AND PROVIDE CUT
 SHEETS FOR EQUIPMENT PLANNED FOR USE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2002-12-19 Cont ID  
Sent By mcarsill Date 2002-12-19 Time 10:39 Rev Time 0.00
Received By mcarsill Date 2002-12-19 Time 10:38 Sent To  
Notes
2002-12-19 00:00:00SEE ELECTRICAL COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-09-12 Cont ID  
Sent By mcarsill Date 2002-09-12 Time 09:08 Rev Time 0.00
Received By mcarsill Date 2002-09-12 Time 09:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-08-15 Cont ID  
Sent By mcarsill Date 2002-08-15 Time 09:16 Rev Time 0.00
Received By mcarsill Date 2002-08-15 Time 09:16 Sent To  
Notes
2002-08-15 00:00:001) NO STAIR DETAILS OR INFORMATION
 PROVIDED FOR THE REQUIRED HANDRAILS
 OR RAMPS.
  
 2) IT STILL APPEARS THAT SOME SEATS
 ARE STILL TOO CLOSE TOGETHER.
  
 3) WITH REGARDS TO THE GAS LIGHT
 LITERATURE, NO INFOMATION PROVIDED
 THAT THESE DEVICES ARE LISTED BY
 EITHER UL OR FM. PLEASE PROVIDE
 NECESSARY INFORMATION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-07-03 Cont ID  
Sent By mcarsill Date 2002-07-03 Time 12:16 Rev Time 0.00
Received By mcarsill Date 2002-07-03 Time 12:16 Sent To  
Notes
2002-07-03 00:00:001) PANIC HARDWARE REQUIRED ON ALL EXIT
 DOORS SUBJECT TO OCCUPANCY OF 100 OR
 MORE PERSONS.
  
 2) OCCUPANT LOAD TO BE DETERMINED BY
 FIRE RESCUE.
  
 3) TABLES AND CHAIRS APPEAR TO BE TOO
 CLOSE TOGETHER IS SOME LOCATIONS.
  
 4) PLEASE EXPLAIN OCCUPANT LOAD OF 380
 PERSONS. A REVIEW OF THE SEATING PLAN
 DOES NOT INDICATE 380 SEATS. PLEASE
 ADVISE. DO THE LARGE SQUARES ON THE
 PLANS REPRESENT BOOTHS AND IF SO HOW
 MANY TO EACH SQUARE.
  
 5) PLEASE PROVIDE DIMENSIONS BETWEEN
 CHAIRS.
  
 6) PLEASE INDICATE ON THE PLANS THE
 LOCATIONS FOR SEATING FOR AT LEAST
 TWO HANDICAPPED PERSONS.
  
 7) PLEASE PROVIDE FLAME SPREAD FOR
 WALLS AND CEILINGS, ESPECIALLY THE
 WOOD CEILING.
  
 8) SEPARATE PLANS AND PERMITS REQUIRED
 FOR HOOD, DUCT, AND FIRE SUPPRESSION
 SYSTEMS.
  
 9) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER REMODEL.
  
 10) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM REMODEL.
  
 11) RAISED PLATFORMS IF PERMANANT MUST
 BE THE SAME TYPE OF CONSTRUCTION AS THE
 BUILDING.
  
 12) OPEN FLAME DEVICES ARE NOT ALLOWED.
 GAS LIGHTS AND CANDLES MAY ONLY BE
 USED IF THE EXCEPTIONS OF THE CODE CAN
 BE MET.
  
 13) NO FIRE SPRINKLER PLANS PROVIDED
 WITH DRAWINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-04-28 Cont ID  
Sent By sthyng Date 2003-04-28 Time 09:19 Rev Time 0.00
Received By sthyng Date 2003-04-28 Time 09:19 Sent To E
Notes
2003-04-28 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2002-11-21 Cont ID  
Sent By btrobaug Date 2002-11-21 Time 17:34 Rev Time 0.00
Received By btrobaug Date 2002-11-21 Time 17:34 Sent To  
Notes
2002-11-21 00:00:00TO COMM BOARD #45./WRT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-11-07 Cont ID  
Sent By btrobaug Date 2002-11-07 Time 18:36 Rev Time 0.00
Received By btrobaug Date 2002-11-07 Time 18:33 Sent To B
Notes
2002-11-07 00:00:00TO JIM W./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By btrobaug Date 2002-10-25 Time 14:43 Sent To  
Notes
2002-10-28 00:00:00TO DVP./WRT

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-12-17 Cont ID  
Sent By hmoser Date 2002-12-17 Time 17:49 Rev Time 1.00
Received By hmoser Date 2002-12-17 Time 17:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-09-03 Cont ID  
Sent By pkrauss Date 2002-09-03 Time 15:25 Rev Time 0.50
Received By pkrauss Date 2002-09-03 Time 14:19 Sent To  
Notes
2002-09-03 00:00:00PROVISO:
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION, & WALK-IN COOLERS.
 PLEASE PROVIDE PLANS & MANUFACTURER
 SUBMITTAL DATA WITH PERMIT APPLICATION.
  
 PLEASE NOTE:
  
 EXHAUST FANS FOR HOOD/GREASE DUCT SHALL
 TERMINATE:
  
 (A) A MINIMUM OF 10 FT FROM ADJACENT
 BUILDINGS, PROPERTY LINES & AIR INTAKES.
  
 (B) TERMINATE A MINIMUM OF 40" ABOVE THE
 THE ROOF SURFACE.
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR AS
 PER 2001 FBC(M) 606.2.2 IN ACCORDANCE
 WITH 606.4 OR 606.4.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-06-24 Cont ID  
Sent By pkrauss Date 2002-06-24 Time 15:17 Rev Time 0.00
Received By pkrauss Date 2002-06-24 Time 15:16 Sent To  
Notes
2002-06-24 00:00:00 
 1.PROVIDED ADDITIONAL INFORMATION FOR
 THE MECHANICAL EQUIPMENT AT THE
 MEZZANINE LEVEL. IS THIS AREA RATED?
 INDICATE ACCESS. INDICATE IF ROOM IS
 VENTILATED.
  
 2.PLEASE NOTE, BALANCED RETURN AIR -
 2001 FBC(M) 601.4 RETURN AIR SHALL
 BE EQUAL TO SUPPLY AIR BY MEANS OF
 AIR TRANSFER OR A DUCTED RETURN.
  
 3.PLAN SHEET M-201 INDICATES A GLYCOL
 CHILLER AND CU-1.WILL THIS BE A
 PART OF PERMIT 02061076?IS THIS
 LOCATION A PART OF THIS TENANT
 SPACE?
  
 PLEASE NOTE, ADDITIONAL PERMITS REQUIRED
 FOR WALK-IN COOLERS & FREEZERS, HOOD &
 FIRE SUPRESSION.PLEASE PROVIDE PLANS
 & MANUFACTURER INSTALLATION INTRUCTIONS.
 THIS ALSO INCLUDES ANY DUCT WRAP THAT
 MAY BE USED ON THE GREASE DUCT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 5 Status F Date 2002-12-20 Cont ID  
Sent By kstevens Date 2002-12-20 Time 08:44 Rev Time 0.50
Received By kstevens Date 2002-12-20 Time 08:44 Sent To  
Notes
2002-12-20 00:00:00THIS REVISION HAS BEEN SUPERCEEDED BY
 REVISION DATED 12-19-

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-11-02 Cont ID  
Sent By kstevens Date 2002-11-02 Time 12:34 Rev Time 1.00
Received By kstevens Date 2002-11-02 Time 12:33 Sent To  
Notes
2002-11-02 00:00:00REVISION OK - SHTS P-300 - P-400

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-09-12 Cont ID  
Sent By dpalmer Date 2002-10-29 Time 10:46 Rev Time 0.00
Received By kstevens Date 2002-09-12 Time 11:17 Sent To  
Notes
2002-09-12 00:00:00PLUMBING PASSED - GAS RISER NOT APPROVED
 RISER DIAGRAM TO BE SUBMITTED WITH GAS
 PERMIT APPLICATION.

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-08-30 Cont ID  
Sent By kstevens Date 2002-08-30 Time 10:27 Rev Time 0.00
Received By kstevens Date 2002-08-30 Time 10:27 Sent To  
Notes
2002-08-30 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) FROM PREVIOUS REVIEW, COMMENT #7 MAN-
 UFACTURE CUT SHEET NOT FOUND. PLEASE
 SUBMIT INFORMATION FOR REVIEW.
 2) FROM PREVIOUS REVIEW#12(B) SUBMIT
 MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT
 TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND THE FBC-2001 FUEL GAS
 CODE SECTION 402.2-AND-#12(C)
 MANUAL SHUT OFF VALVE TO BE UPSTREAM OF
 AUTOMATIC SHUT OFF VALVE WITH A UNION
 IN BETWEEN FOR SERVICE OF SOLINOID VALVE
 (NOT SHOWN ON RISER).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-07-18 Cont ID  
Sent By kstevens Date 2002-07-18 Time 14:21 Rev Time 0.00
Received By kstevens Date 2002-07-18 Time 14:16 Sent To  
Notes
2002-07-18 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) PLEASE SUBMIT A GREASE WASTE RISER
 DIAGRAM.
 2) PLEASE SUBMIT A WATER RISER DIAGRAM
 FOR KITCHEN AND BAR AREAS. WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIX-
 TURES IN AN "EFFECTIVE RANGE" NOT AT TOP
 OF DROPS AS SHOWN ON SHT P-400 BATHROOM
 WATER ISOMETRIC.PLEASE CHANGE WATER
 HAMMER ARRESTOR LOCTIONS ON BATHROOM
 WATER RISER DIAGRAM. PDI-WH 201 SECTION
 604.9
 3) PLEASE SEE PLUMBING REVIEW COMMENTS
 FOR PERMIT #02061076 CONCERNING TOILET
 ROOM ELEVATIONS.
 4) SHT P4 FOOD SERVICE EQUIP. SHTS. P5
 REFERS TO SAFE WASTE. SAFE WASTE NOT
 APPROVED. INDIRECT WASTE REQUIRED.
 5) SHT P4 FOOD SERVICE EQUIP. SHEETS,
 ALL INDIRECT WASTE SHALL DRAIN TO FLOOR
 SINKS. P6 REFERS TO 2" STUB UP 4" ABOVE
 FLOOR. SECTION 802.3 APPROVED INDIRECT
 WASTE RECEPTOR.
 6) SHT P-000 PLUMBING SPECIFICATIONS,
 #'S 1.2, 1.7, & 6.1 REFER TO STANDARD
 BUILDING CODE. CODE IN EFFECT IS FBC-
 2001 PLUMBING & FBC-2001 FUEL GAS PLEASE
 CHANGE CODE REFERENCE.
 7) SHT P-000 PLMBG. SPECS. # 2.6 FILTER
 SHALL BE NSF APPROVED. PLEASE SUBMIT
 MANUF. INFOR. FOR FILTER.
 8) SHT P-000 PLMG. SPECS., # 1.8, DI-
 ELECTRIC UNIONS NOT APPROVED FOR WATER
 PIPING. PLEASE DELETE REFERENCE.
 9) SHT P-000 GAS WATER HEATER AND STOR-
 AGE TANK DETAIL. FLOOR SINK REQUIRED FOR
 ALL INDIRECT WASTE FROM PRESSURE/TEMP
 RELIEF VALVE DISCHARGE AND PAN DRAIN.
 PAN DRAIN REQUIRED FOR ALL WATER HEATERS
 AND STORAGE TANKS ABOVE THE GROUND FLOOR
 SPACE. SEC 504.8.1" PAN DRAIN REQUIRED
 SEC 623.7 FUEL GAS
 10) SHT P-000 PLUMBING NOTES #5 - SEE
 PLAN REVIEW COMMENT # 4 SAFE WASTE.
 11) PER UTILITY ORDINANCE, DRAINAGE FROM
 DISHWASHER SHALL DRAIN INTO SANITARY
 SYSTEM NOT INTO GREASE WASTE SYSTEM.
 12) THE FOLLOWING INFORMATION IS REQUIR-
 ED FOR GAS PERMIT.
 A. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU 402
 (34). NO BTU'S SHOWN FOR WATER HEATER &
 STORAGE TANK.
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2.
 C. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved