| Plan Review Stops For Permit 02061076 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-12-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-12-26 |
Time |
13:45 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
2002-12-26 |
Time |
13:45 |
Sent To |
|
|
| Notes |
| 2002-12-26 00:00:00 | REVISION S-1.S-2 DATED 11-13-02 | | | MECHANICAL UNIT STANDS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-08-02 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2002-08-02 |
Time |
09:15 |
Rev Time |
2.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-07-01 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2002-07-01 |
Time |
15:19 |
Rev Time |
2.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-07-01 00:00:00 | FIRST REVIEW 7/1/02 | | | 1. SHEET, S-1 ENGINEER OF RECORD TO | | | PROVIDE STRUCTURAL ANALYSIS THAT | | | EXISTING STRUCTURE WILL SUPPORT THE | | | NEW LOADS IMPOSED BY THE BREWREY | | | WITHOUT ALTERATION OF THE EXISTING | | | BUILDING. | | | 2. SHEET, S-2 STRUCTURAL ENGINEER TO | | | CERTIFY THAT THE TOP AND BOTTOM CORDS | | | OF THE TRUSSES WILL TAKE THE NEW LOADS | | | TO BE IMPOSED. | | | 3. SHEET, E-4.03 MEZZANINE, PROVIDE | | | STRUCTURAL DESIGN FOR A MINUMIN OF 125 | | | POUNDS PER SQUARE FOOT OR IF HIGHER | | | LOADS THE THE ACTUCAL LOAD IMPOSED. | | | 4. SHEET, M-3.02 IS INDICATED AS | | | REQUIRED FOR MEZZANINE ON SHEET | | | M-2.03 SHEET NOT SUBMITTED, REQUIRED TO | | | REVIEW | | | MEZZANINE CONSTRUCTION. | | | 5. SHEET A-1.01 INDICATES TWO MECHANICAL | | | PLATFORMS INDICATE ALL STRUCTURAL | | | DESIGN FOR BOTH AND DETAIL ACCESS. | | | DESIGN FOR CODE CONFORMITY. | | | NOTE: ALL DESIGNS CERTIFICATION ARE TO | | | BE IN CONFORMITY WITH THE FLORIDA | | | BUILDING CODE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2003-04-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-04-30 |
Time |
07:50 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-04-30 |
Time |
07:50 |
Sent To |
|
|
| Notes |
| 2003-04-30 00:00:00 | REV TO NOTES ONLY | | | NO CORRECTIONS FROM LAST PLAN. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2003-01-28 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-04-28 |
Time |
09:21 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-01-28 |
Time |
07:49 |
Sent To |
|
|
| Notes |
| 2003-01-28 00:00:00 | ************ UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE EQUIPMENT SHEDULE | | | AND PANEL SCHEDULE. PLEASE SEE GLYCOL | | | CHILLER, PANEL SHOWS 35A OCP AND EQUIP- | | | -MENT SCHEDULE SHOWS A 45A LOAD?? | | | | | | 2)NOTE; PLEASE SHOW CIRCUIT #'S FOR | | | EMLT/EXT LTS. 700-12E. | | | CLARIFY TYPE OF FIXTURES INSTALLED. | | | | | | 3)NOTE: PLEASECLARIFY "LOCATION" TYPE | | | SHOWN ON PLAN PER NECART:500. PLANS | | | SHOW CLASS 1 DIV 1. PLEASE VERIFY FIELD | | | CONDITIONS AND CHECK ART 500 FOR | | | POSSIBLE OTHER CLASS LOCATION. IT HAS | | | BEEN NOTED BY INSPECTOR THAT WIRING IS | | | NOT PER CLASS 1 DIV 1 AS NOTED ON PLAN?? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-07-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-07-30 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-07-30 |
Time |
12:41 |
Sent To |
|
|
| Notes |
| 2002-07-30 00:00:00 | ********** NOTE ********** | | | | | | PLEASE NOTE THAT ALL "OLD" E -SHEETS | | | NEED TO BE TAKEN OUT OF SETS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-07-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-07-03 |
Time |
06:54 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-07-03 |
Time |
06:54 |
Sent To |
|
|
| Notes |
| 2002-07-03 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SHOW/CLARIFY LOCATIONS | | | PER ART 500 NEC. HAZARDOUS LOCATIONS FOR | | | GRAIN/MIXING/GRINDING??? | | | | | | 2)NOTE: PLEASE CLARIFY AND LABEL TRANS- | | | -FORMERS AT THEIR LOCATIONS. PLEASE | | | NOTE TRANS. BEING SHOWN IN TWO LOCATIONS | | | ?? | | | | | | 3)NOTE: PLEASE SEPARATE LINE DIAGRAM FOR | | | SERVICES EQUIPMENT BEING INSTALLED UNDER | | | THIS PERMIT. | | | | | | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED? | | | 110-9 | | | | | | 5) NOTE: PLEASE SHOW ALL CONTINUOUS AT | | | 125%. (LIGHTING ETC) | | | 215-2,215-3,230-42 | | | | | | 6) NOTE: PLEASE SHOW CALCULATIONS FOR | | | TRACK LIGHTING PER 220-12B. | | | | | | 7)NOTE: PLEASE CLARIFY GROUNDING OF | | | TRANSFORMERS PER 250-30 | | | | | | 8 )NOTE: PLEASE NOTE THAT THE LOAD | | | CALCULATIONS NEED TO BE SHOWN. SQ FT/ | | | RECEPT LOADS ETC. PER 220-3,220-10, | | | 220-11, 220-13. (215-5) | | | PLEASE CLARIFY ALL SHOWN AT CONNECTED | | | LOAD? | | | | | | 9)NOTE: PLEASE CLARIFY OCP FOR TEMP FEED | | | TO "M2". PLEASE INDICATE LOCATION OF | | | "EXISTING" GUTTER ON SECOND FLR.? | | | PLEASE NOTE LENGTH OF TAPPED CONDUCTORS | | | PER 240-21. RISER SHOWS 100A #3`S WITH | | | A 600A FEED? PLEASE CLARIFY OCP AT | | | "M3" SHOWN AS 200A /ALSO NOTE TAPPED | | | CONDUCTOR LENGTH? PER 240-21 | | | | | | 10)NOTE: PLEASE NOTE THAT REVIEW FOR | | | RISER DIAGRAM FOR FUTURE REST. WILL NOT | | | BE REVIEWED AT THIS TIME. (NOT COMPLETE) | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2002-06-26 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2002-06-26 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
mamini |
Date |
2002-06-26 |
Time |
11:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-08-02 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-08-02 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-08-02 |
Time |
08:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-07-03 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-07-03 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-07-03 |
Time |
10:14 |
Sent To |
|
|
| Notes |
| 2002-07-03 00:00:00 | 1) PLEASE PROVIDE DETAILS ON BREWERY | | | EQUIPMENT. THIS OFFICE NEEDS HEIGHTS | | | AND WIDTHS OF EQUIPMENT. PLEASE | | | PROVIDE DIMENSIONS OF EQUIPMENT WITH | | | REGARDS TO EXITING WITHIN THE BREWERY. | | | | | | 2) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR WALLS | | | AND CEILINGS OF THE BREWERY. | | | | | | 3) PLEASE INDICATE WHAT "TEMPORARY" | | | PARTITION MEANS IN DURATION. | | | | | | 4) WHAT TYPE OF MATERIALS WILL BE USED | | | FOR THE TEMPORARY PARTITION. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-04-28 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-04-28 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-04-28 |
Time |
09:21 |
Sent To |
E |
|
| Notes |
| 2003-04-28 00:00:00 | TO DP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-01-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-01-30 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2003-01-30 |
Time |
15:33 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2003-01-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-01-30 |
Time |
15:33 |
Rev Time |
1.25 |
| Received By |
pkrauss |
Date |
2003-01-23 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2003-01-23 00:00:00 | PLANS SUBMITTED FOR BREWERY PIPING & | | | ASSEMBLY.PLEASE CLARIFY THE FOLLOWING | | | INFORMATION: | | | | | | 1. LOCATION OF REMOTE GLYCOL CHILLER. | | | 2. LOCATION OF BOILER. | | | 3. PROVIDE INFORMATION ON PIPING (I.E. | | | MATERIAL, SIZE, LAYOUT). | | | 4. PROVIDE SUBMITTALS FOR ALL EQUIPMENT, | | | VALVES, STRAINERS, FLEX CONNECTORS, | | | ETC. | | | | | | THIS INFORMATION WAS NEVER SUBMITTED OR | | | REVIEWED.MECHANICAL PERMITS ISSUED | | | THUS FAR WERE FOR THE HVAC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-08-01 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-08-01 |
Time |
11:14 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-08-01 |
Time |
11:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-07-02 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2002-07-02 |
Time |
06:50 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2002-07-02 |
Time |
06:49 |
Sent To |
|
|
| Notes |
| 2002-07-02 00:00:00 | DENIED: | | | | | | PROVIDE INFORMATION ON EQUIPMENT | | | MOUNTING OR SUPPORT DETAILS. | | | | | | PROVIDE OUTSIDE AIR CALCULATION FOR | | | AHU-4 SHOWING COMPLIANCE WITH TABLE | | | 403.3 OF THE FBC(M) 2001. | | | | | | NOTE: SEPARATE PERMITS WITH PLANS | | | REQUIRED FOR WALK IN COOLERS FREEZERS, | | | HOODS SUPPRESSION SYSTEMS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-08-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-08-01 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-08-01 |
Time |
11:52 |
Sent To |
|
|
| Notes |
| 2002-08-01 00:00:00 | PASSED/PROVISO | | | | | | WATER HAMMER ARRESTORS SHALL BE LOCATED | | | NEAR FIXTURES IN AN "EFFECTIVE RANGE" | | | NOT AT TOP OF DROP. PDI-WH 201/MANUF. | | | INSTRUCTIONS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-07-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-07-10 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-07-10 |
Time |
11:33 |
Sent To |
|
|
| Notes |
| 2002-07-10 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) SHTS LS-1.01 & A-5.01 WOMEN'S TOILET | | | ROOM #011. THE ACCESSIBLE W/C SHALL BE | | | LOCATED IN THE CORNER DIAGONAL TO THE | | | DOOR. SEC. 11-4.17.3 & FIG. 30E. | | | 2) SHT A-5.01 PLEASE SHOW CLEAR FLOOR | | | SPACE FOR HDCP FIXTURES. 11-4.16.2 W/C, | | | 11-4.18.3 URNAL, & 11-4.19.3 LAV. | | | 3) SHT A-5.01 DETAIL #3, TOILET ROOM EL- | | | EVATION (H), URNAL HEIGHT SHALL BE 17" | | | PER 11-4.18.2 | | | 4) SHT A-5.01 DETAIL (I), W/C TO BE 1'6" | | | TO CENTER OFF WALL NOT 1'8" AS SHOWN. | | | SEE FIG. 30E. | | | 5) PLEASE SUBMITSANITARY AND WATER | | | RISER DIAGRAMS FOR TOILET ROOMS AND | | | BREWERY. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|