| 2002-06-18 00:00:00 | *************** UNSAT ****************** |
| | |
| | 1)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| | PROTECTED BRANCH CIRCUIT ON PANEL |
| | SCHEDULE. PLEASE NOTE THAT ALL PREVIOUS |
| | PLANS ARE COMING IN AND SHOWING AS |
| | "ACI" PROTECTED OUTLETS. PLEASE NOTE |
| | THAT THE PROTECTION REQ`D IS FOR THE |
| | ENTIRE BRANCH CIRCUIT. PLEASE ALSO NOTE |
| | THAT IT IS "AFCI" NOT "ACI" 210-12. |
| | THEY DO NOT MAKE AN "AFCI" RECEPT. |
| | |
| | 2)NOTE: PLEASE NOTE THAT THE RISER |
| | DIAGRAM DOES NOT CORRELATE WITH ITSELF |
| | AND PANEL SCHEDULES? PLEASE NOTE,RISER |
| | NOTE SAYS, TO BE A 225A MCB AND RISER |
| | SHOWS 200A? PANEL ALSO SHOWN AS 200A. |
| | PLEASE CORRELATE. |
| | |
| | 3)NOTE: PLEASE NOTE LOAD SHOWN FOR PANEL |
| | "B" EXCEEDS 60A FEED FOR THAT PANEL. |
| | |
| | 4)NOTE: PLEASE NOTE PANEL "B" IS SHOWN |
| | AS 75A MLO? PLEASE NOTE THAT A 75A PANEL |
| | IS NOT A COMMON PANEL SIZE.? |
| | |
| | 5)NOTE: PLEASE NOTE THAT ALL CODES REF |
| | THE "2001" NEC. PLEASE NOTE WE ARE UNDER |
| | THE "99" NEC. |
| | |
| | 6)NOTE: PLEASE NOTE GFI RECEPT SPACING |
| | FOR MASTER BATH PER 210-52D. PLEASE NOTE |
| | GFI WITHIN 3' OF SINK., |
| | |
| | 7)NOTE: PLEASE CLARIFY OUTLET SPACING |
| | NEXT TO FRIG? COUNTER? 210-52(C)-1. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRCIAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |