Plan Review Details - Permit 02061018
Plan Review Stops For Permit 02061018
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-07-23 Cont ID  
Sent By btrobaug Date 2002-07-23 Time 07:48 Rev Time 0.00
Received By btrobaug Date 2002-07-23 Time 07:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-06-24 Cont ID  
Sent By btrobaug Date 2002-06-24 Time 09:01 Rev Time 0.00
Received By btrobaug Date 2002-06-24 Time 06:56 Sent To  
Notes
2002-06-24 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION MAKE ANY NECESSARY CHANGES
 ON THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 2} THERE ARE 3#6'S AND 1#4 SHOWN AS
 FEEDERS FOR A/C DISCONNECTS,PLEASE NOTE
 IF THESE ARE ON THE APPROVED PLANS THEY
 MUST BE INSTALLED.
  
 3} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4} SMALL APPLIANCE CIRCUITS,RANGE,WATER
 HEATERS,CLOTHES DRYER AND AIR HANDLERS
 SHOWN ON IN LOAD CALCULATIONS DO NOT
 CORRELATE WITH THE PANEL SCHEDULE.
  
 5} NO WASHER SHOWN ON THE PANEL SCHEDULE
  
 6} ONLY ONE WATER HEATER SHOWN ON THE
 PANEL SCHEDULE,TWO IN THE CALCS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL;
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW