| 2002-08-01 00:00:00 | BUILDING DENIED |
| | |
| | 1) STRUCTURE IS LOCATED IN AN "AO" FLOOD |
| | ZONE AN ELEVATION CERTIFICATE WILL BE |
| | REQUIRED. |
| | |
| | 2)FL BLDG 1909.3 (EXCEPTION# 2) |
| | CONCRETE SLABS ON GRADE CONTAINING 6X6/ |
| | W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| | FABRIC LOCATED IN THE MIDDLE TO THE |
| | UPPER 1/3RD OF THE SLAB SHALL BE SUP- |
| | PORTED BY APPROVED MATERIALS OR SUPPORTS |
| | AT SPACING NOT TO EXCEED 3 FT OR IN |
| | ACCORDANCE WITH MANUFACTURER'S SPEC. |
| | PLEASE INDICATE ON PLANS. |
| | |
| | 3)1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| | ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| | TO THE ROUGH OPENING SUBTRATE. PLEASE |
| | PROVIDE PRODUCT APPROVAL FOR CLIPPED |
| | MULLIONS. |
| | |
| | 4)2305.2.2 FLOOR/CEILING ASSEMBLIES |
| | SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL/ |
| | ING ASSEMBLIES SEPARATING USEABLE SPACE |
| | INTO 2 OR MORE APPROXIMATE AREAS WITH NO |
| | AREA GREATER THAN 500 SQ FT. DRAFTSTOP- |
| | PING SHALL BE PROVIDED PARALLEL TO THE |
| | MAIN FRAMING MEMBERS. PLEASE INDICATE |
| | ON PLANS THE LOCATION AND MATERIALS THAT |
| | WILL BE USED. |
| | |
| | 5) PROVIDE CLARIFICATION OF CANTILEVER |
| | BEAMS. THE PLANS DO NOT INDICATE WHERE |
| | THE WALL ON THE RIGHT SIDE OF THE |
| | COVERED PORCH ENDS AND THE CANT. BEAM |
| | BEGINS. THE FOUNDATION, WALL AND |
| | VERTICAL REINFORCEMENT ON SHEETS 1,2 & |
| | 3B FOR THE RIGHT WALL AT THE COVERED |
| | PORCH DOES NOT MATCH THE ELEVATIONS. |
| | |
| | 6) THE POSITIVE WINDLOAD PRESSURE LISTED |
| | ON THE PLANS FOR THE GARAGE DOOR (+39.8) |
| | EXCEEDS THE POS. DESIGN PRESSURE GIVEN |
| | IN THE PRODUCT APPROVAL FOR THE OVERHEAD |
| | GARAGE DOOR. PLEASE SUBMIT AN ACCEPTABLE |
| | PRODUCT APPROVAL. |
| | |
| | 7) PLEASE UPDATE THE PRODUCT APPROVAL |
| | COVER SHEET (WIND PRESSURE SCHEDULE) |
| | THAT LISTS THE WINDOWS AND DOORS AND |
| | THEIR PRODUCT ACCEPTANCE NUMBERS. |
| | |
| | 8)1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| | ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| | TO THE ROUGH OPENING SUBTRATE. |
| | PLEASE SUBMIT PRODUCT APPROVALS FOR |
| | CLIPPED MULLIONS. |
| | |
| | 9) THE KEY PLANS AND INSTALLATION |
| | SCHEDULES SUBMITTED FOR THE STORM PANELS |
| | ARE FOR THE WRONG MODEL. |
| | |