| Plan Review Stops For Permit 02060891 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2002-06-18 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-06-18 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-06-18 |
Time |
08:52 |
Sent To |
|
|
| Notes |
| 2002-06-18 00:00:00 | 1) PLANS INDICATE THAT DUCT SMOKE | | | DETECTORS WILL BE CAUSE A TROUBLE | | | SIGNAL WHICH IS NOT ACCEPTABLE. | | | ACTIVATION OF THE DUCT SMOKE DETECTORS | | | ARE TO CAUSE THE FIRE ALARM SYSTEM TO | | | ACTIVATE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|