Plan Review Details - Permit 02060885
Plan Review Stops For Permit 02060885
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-09-10 Cont ID  
Sent By hpiskura Date 2002-09-03 Time 11:12 Rev Time 0.00
Received By hpiskura Date 2002-09-03 Time 10:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-06-20 Cont ID  
Sent By hpiskura Date 2002-06-20 Time 16:19 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-09-10 Cont ID  
Sent By dpalmer Date 2002-09-10 Time 11:53 Rev Time 0.25
Received By dpalmer Date 2002-09-10 Time 11:52 Sent To  
Notes
2002-09-10 00:00:00NO ELEC REV.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-09-04 Cont ID  
Sent By dpalmer Date 2002-09-04 Time 06:02 Rev Time 0.25
Received By dpalmer Date 2002-09-04 Time 06:01 Sent To  
Notes
2002-09-04 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT THERE ARE NO
 INDICATIONS OF REVISIONS BY CLOUDS OR
 TRIANGLES? PLEASE ALSO NOTE THAT THERE
 ARE NO REVISIONS DATES SHOWN ON RIGHT
 HAND SIDE OF E-SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-21 Cont ID  
Sent By dpalmer Date 2002-06-21 Time 12:49 Rev Time 0.00
Received By dpalmer Date 2002-06-21 Time 12:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-09-24 Cont ID  
Sent By mcarsill Date 2002-09-24 Time 13:40 Rev Time 0.00
Received By mcarsill Date 2002-09-24 Time 13:39 Sent To  
Notes
2002-09-24 00:00:00SECURITY DEVICES PLANNED FOR EXIT DOORS
 SHALL COMPLY WITH DELAYED EGRESS OR
 ACCESS CONTROLLED EGRESS. PLEASE SEE
 "SPECIAL LOCKING ARRANGEMENTS PER THE
 2000 EDITION OF THE LIFE SAFETY CODE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-06-26 Cont ID  
Sent By mcarsill Date 2002-06-26 Time 11:49 Rev Time 0.00
Received By mcarsill Date 2002-06-26 Time 11:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-09-12 Cont ID  
Sent By pkrauss Date 2002-09-12 Time 10:18 Rev Time 0.35
Received By pkrauss Date 2002-09-12 Time 09:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-06-22 Cont ID  
Sent By pkrauss Date 2002-06-22 Time 09:41 Rev Time 0.40
Received By pkrauss Date 2002-06-22 Time 09:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-09-09 Cont ID  
Sent By kstevens Date 2002-09-09 Time 18:11 Rev Time 0.00
Received By kstevens Date 2002-09-09 Time 18:11 Sent To  
Notes
2002-09-09 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) PLEASE PROVIDE A SANITARY AND A WATER
 RISER DIAGRAM FOR THE SERVICE SINK. SHOW
 TIE IN FOR DRAIN, VENT AND WATER .
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-07-16 Cont ID  
Sent By pschmitz Date 2002-07-16 Time 09:27 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-07-16 00:00:00PLUMBING PLAN REVIEW,PROVISO,SHT A-3 PES

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-06-28 Cont ID  
Sent By kstevens Date 2002-06-28 Time 17:50 Rev Time 0.00
Received By kstevens Date 2002-06-28 Time 17:50 Sent To  
Notes
2002-06-28 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) A DRINKING FOUNTAIN AND SERVICE SINK
 ARE REQUIRED PER TABLE 403.1. PLEASE
 INDICATE IF THESE ARE PROVIDED
 2) SHT A-3 MANUFACTURE INFORMATION REQ-
 UIRED FOR HOLDING TANK/PUMP AND FOR
 POINT OF USE WATER HEATERS. PLEASE SHOW
 PRODUCT APPROVAL WITH LISTING BY AN
 APPROVED TESTING AGENCY.(UL FOR EXAMPLE)
 3) SHT A-3 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED. WATER HAMMER
 ARRESTORS ARE REQUIRED FOR QUICK CLOSING
 VALVES PER 604.9
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377