Plan Review Details - Permit 02060883
Plan Review Stops For Permit 02060883
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-09-25 Cont ID  
Sent By pkrauss Date 2002-09-25 Time 16:34 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
2002-09-25 00:00:00APPROVED 9-25-02 BY ASST. FIRE MARSHALL
 MIKE CARSILLO.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-07-02 Cont ID  
Sent By mcarsill Date 2002-07-02 Time 14:45 Rev Time 0.00
Received By mcarsill Date 2002-07-02 Time 14:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-06-18 Cont ID  
Sent By mcarsill Date 2002-06-18 Time 12:53 Rev Time 0.00
Received By mcarsill Date 2002-06-18 Time 12:53 Sent To  
Notes
2002-06-18 00:00:001) PLEASE PROVIDE PRODUCT APPROVALS FOR
 3M FIREWRAP OR EQUAL.
  
 2) INSUFFICIENT AIR VELOCITY FROM
 EXHAUST DUCT. EXHAUST DUCT TO PROVIDE
 AT LEAST 1500 CFM THROUGH THE DUCT.
  
 3) THE EXHAUST DUCT IS TO BE A MINIMUM
 OF AT LEAST TEN FEET FROM ADJACENT
 BUILDINGS, PROPERTY LINES, ETC.
  
 4) PLEASE CLARIFY EF-1 LOCATION TO
 PROXIMITY OF SF-1.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-09-24 Cont ID  
Sent By pkrauss Date 2002-09-24 Time 15:53 Rev Time 0.35
Received By pkrauss Date   Time   Sent To  
Notes
2002-09-24 00:00:00PROVISO:
  
 ROUND DUCT INDICATED ON PLAN SHALL BE
 METAL NOT FLEX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-07-02 Cont ID  
Sent By ndenmark Date 2002-07-02 Time 15:40 Rev Time 0.33
Received By ndenmark Date 2002-07-01 Time 15:52 Sent To  
Notes
2002-07-01 00:00:00TEST AND BALANCE REPORT REQUIRED AT
 FINAL

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-06-18 Cont ID  
Sent By pkrauss Date 2002-06-18 Time 10:50 Rev Time 0.45
Received By pkrauss Date 2002-06-18 Time 10:47 Sent To  
Notes
2002-06-18 00:00:00*******************DENIED***************
  
 1. PROVIDE MANUFACTURER INSTALLATION
 INSTRUCTIONS FOR THE "3M FIREWRAP OR
 EQUAL".
  
 2. PLAN SHEET 3 OF 4, PLEASE CLARIFY
 EF-1 LOCATION TO THE PROXIMITY TO
 SF-1.(10 FT MINIMUM REQUIRED)
  
 3. EXHAUST SHALL HAVE A MINIMUM OF 10 FT
 CLEARANCEFROM ADJACENT BUILDINGS,
 PROPERTY LINES, OR AIR INTAKES AS
 PER 2001 FBC(M) 506.3.14.3 & NFPA 96
 4-8.2.1 (A).
  
 4. THE AIR VELOCITY THROUGH THE DUCT
 SHALL NOT BE LESS THAN 1,500 FPM &
 NOT GREATER THAN 2,500 FPM AS PER
 2001 FBC(M) 506.3.6
  
 5. MAKEUP AIR TEMPERATURE SHALL COMPLY
 WITH 2001 FBC(M) 508.1.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.