Plan Review Details - Permit 02060883
| Plan Review Stops For Permit 02060883 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2002-09-25 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-09-25 |
Time |
16:34 |
Rev Time |
0.05 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-09-25 00:00:00 | APPROVED 9-25-02 BY ASST. FIRE MARSHALL | | | MIKE CARSILLO. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-07-02 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-07-02 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-07-02 |
Time |
14:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-06-18 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-06-18 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-06-18 |
Time |
12:53 |
Sent To |
|
|
| Notes |
| 2002-06-18 00:00:00 | 1) PLEASE PROVIDE PRODUCT APPROVALS FOR | | | 3M FIREWRAP OR EQUAL. | | | | | | 2) INSUFFICIENT AIR VELOCITY FROM | | | EXHAUST DUCT. EXHAUST DUCT TO PROVIDE | | | AT LEAST 1500 CFM THROUGH THE DUCT. | | | | | | 3) THE EXHAUST DUCT IS TO BE A MINIMUM | | | OF AT LEAST TEN FEET FROM ADJACENT | | | BUILDINGS, PROPERTY LINES, ETC. | | | | | | 4) PLEASE CLARIFY EF-1 LOCATION TO | | | PROXIMITY OF SF-1. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2002-09-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-09-24 |
Time |
15:53 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-09-24 00:00:00 | PROVISO: | | | | | | ROUND DUCT INDICATED ON PLAN SHALL BE | | | METAL NOT FLEX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-07-02 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2002-07-02 |
Time |
15:40 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2002-07-01 |
Time |
15:52 |
Sent To |
|
|
| Notes |
| 2002-07-01 00:00:00 | TEST AND BALANCE REPORT REQUIRED AT | | | FINAL |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-06-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-18 |
Time |
10:50 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-06-18 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2002-06-18 00:00:00 | *******************DENIED*************** | | | | | | 1. PROVIDE MANUFACTURER INSTALLATION | | | INSTRUCTIONS FOR THE "3M FIREWRAP OR | | | EQUAL". | | | | | | 2. PLAN SHEET 3 OF 4, PLEASE CLARIFY | | | EF-1 LOCATION TO THE PROXIMITY TO | | | SF-1.(10 FT MINIMUM REQUIRED) | | | | | | 3. EXHAUST SHALL HAVE A MINIMUM OF 10 FT | | | CLEARANCEFROM ADJACENT BUILDINGS, | | | PROPERTY LINES, OR AIR INTAKES AS | | | PER 2001 FBC(M) 506.3.14.3 & NFPA 96 | | | 4-8.2.1 (A). | | | | | | 4. THE AIR VELOCITY THROUGH THE DUCT | | | SHALL NOT BE LESS THAN 1,500 FPM & | | | NOT GREATER THAN 2,500 FPM AS PER | | | 2001 FBC(M) 506.3.6 | | | | | | 5. MAKEUP AIR TEMPERATURE SHALL COMPLY | | | WITH 2001 FBC(M) 508.1.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
|