| 2002-06-25 00:00:00 | PROVISO:MECHANICAL PERMIT 02060906 |
| | |
| | 2001 FBC(M) 402.2 - NATURAL VENTILATION |
| | FOR OUTSIDE AIR REQUIRMENT. SHOW |
| | COMPLIANCE FOR THE MINIMUM OPENABLE AREA |
| | TO THE OUTDOORS. (4 PERCENT OF THE FLOOR |
| | AREA BEING VENTILATED) OR TABLE 403.3 |
| | FOR MECHANICAL VENTILATION. |
| | |
| | SMOKE DETECTORS SHALL BE INSTALLED |
| | SUPPLY SYSTEMS WITH A DESIGN CAPACITY |
| | GREATER THAN 2,000 CFM, IN THE SUPPLY |
| | AIR DUCT. 2001 FBC(M) 606.2.1OR |
| | UPON ACTIVATION, THE SMOKE DETECTORS |
| | SHALL SHUTDOWN THE AIR DISTRIBUTION |
| | SYSTEM. 2001 FBC(M) 606.4 |
| | |
| | SHOULD A GAS DRYER BE INSTALLED - |
| | SHOW COMPLIANCE FOR COMBUSTION AIR AS |
| | PER 2001 FBC(M) CHAPTER 7. |
| | |
| | CONDENSATE SHALL DISCHARGE A MINIMUM OF |
| | 12" AWAY FROM THE BUILDING STRUCTURE AS |
| | PER 2001 FBC 1503.4.4. |
| | |
| | AHU LOCATED IN GARAGE - |
| | APPLIANCES SHALL NOT BE INSTALLED IN A |
| | LOCATION WHERE SUBJECT TO MECHANICAL |
| | DAMAGE UNLESS PROTECTED BY APPROVED |
| | BARRIERS.2001 FBC(M) 303.4 |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT 659-8096 |
| | EXT. 8388. |