| 2002-07-17 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3)FL BLDG 1909.3 (EXEPTION# 2) |
| | CONCRETE SLABS ON GRADE CONTAINING 6X6/ |
| | W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| | FABRIC LOCATED IN THE MIDDLE TO THE |
| | UPPER 1/3RD OF THE SLAB SHALL BE SUP- |
| | PORTED BY APPROVED MATERIALS OR SUPPORTS |
| | AT SPACING NOT TO EXCEED 3 FT OR IN |
| | ACCORDANCE WITH MANUFACTURER'S SPEC. |
| | PLEASE INDICATE ON PLANS. |
| | |
| | 4) PROVIDE DETAILS FOR THE STEEL COLUMN |
| | CAPS AND BASES ON PLANS. INDICATE THE |
| | SIZE,THICKNESS,WELD TYPE,LOCATION AND |
| | SIZE OF BOLT HOLES,ETC. |
| | |
| | 5) INDICATE THE COMPONENT & CLADDING |
| | WIND PRESSURES FOR THE ROOF COVERING. |
| | |
| | 6) THE GLASS BLOCK IN BATHS 2,3 & 4 ARE |
| | IN HAZARDOUS LOCATIONS WHICH REQUIRE |
| | TEMPERED GLASS OR GLASS BLOCK WITH A |
| | MINIMUM FACE UNIFORM FACE THICKNESS OF |
| | 0.25". FBC 2405.2.1 & 2404.2.2. |
| | |
| | 7) THE MAIN EGRESS DOOR (FRONT DOOR) IS |
| | REQUIRED TO HAVE A MINIMUM CLEAR OPENING |
| | OF 32".(EACH LEAF OF A DOUBLE DOOR MUST |
| | COMPLY) FBC 1012.1 |
| | |
| | 8) INDICATE THE OPENING SIZE OF THE |
| | ATTIC ACCESS ON THE PLANS. |
| | |
| | 9) THE CANTILEVERED CONCRETE BEAM DETAIL |
| | ON SHEET 6 CALLS FOR THE TOP STEEL TO |
| | RUN 36" BEYOND THE EDGE OF THE OPENING, |
| | HOWEVER, THE COLUMNS ARE ONLY 2'WIDE. |
| | PLEASE PROVIDE STEEL PLACEMENT DETAIL |
| | FOR THE CANT. BEAM. |
| | |
| | 10)THE LINTELS FOR THE OPENINGS ADJACENT |
| | TO THE CANTILEVER BEAM REQUIRE A MINIMUM |
| | END BEARING OF 4". PLEASE INDICATE HOW |
| | THIS WILL BE ACCOMPLISHED AT THE COLUMNS |
| | FOR THE CANT. BEAM. |
| | |
| | 11) THE ROOF FRAMING PLAN ON SHEET 6 |
| | DOES NOT CLEARLY INDICATE THE TRUSS |
| | LAYOUT. THE ANCHORS ARE NOT INDICATED |
| | FOR ALL OF THE TRUSS BEARING POINTS. THE |
| | WOOD GIRDERS TO CONC. FILLED BLOCK |
| | COLUMNS ANCHORS ARE NOT INDICATED ON THE |
| | PLANS. THE BEAM HEIGHT INDICATED AT THE |
| | GARAGE DOES NOT AGREE WITH THE BEAM |
| | HEIGHT LEGEND. |
| | |
| | 12) THE GLASS BLOCK DETAIL ON SHEET 8 |
| | REFERENCES THE S.F.B.C. PLEASE REVISE TO |
| | 2001 FBC. |
| | |
| | 13) THE SOIL REPORT STATES THAT EXTERIOR |
| | FOUNDATIONS SHOULD BEAR AT LEAST 18" |
| | BELOW ADJACENT OUTSIDE FINAL GRADES. THE |
| | CITY AMENDMENTS TO THE FBC 1804.1.7 |
| | REQUIRE MONOLITHIC FOUNDATIONS AT |
| | HABITABLE AREAS TO BE A MINIMUM OF 4" |
| | ABOVE FINISH GRADE. THIS WILL REQUIRE A |
| | 22" DEEP FOUNDATION AND THE PLANS |
| | INDICATE 16" DEEP FOOTINGS. PLEASE |
| | CORRECT. |
| | |
| | 14) PLEASE CORRECT THE ATTACHMENT/ |
| | FASTENER SPECIFICATIONS ON SHEET 8 FOR |
| | WIRE LATH. REFER TO ASTM C 1063 FOR THE |
| | ATTACHMENT OF METAL LATH WHICH VARIES BY |
| | TYPE, 710.2.2 FOR FLAT RIB AND 7.10.2.3 |
| | FOR 3/8" RIB LATH. FBC 2504.2.2. |
| | |
| | 15) THE PRODUCT APPROVALS FOR PREMDOR |
| | HAVE DRAWINGS WHICH DO NOT MATCH THE |
| | REPORT. THE ACCEPTANCE NOS. DIFFER. ALSO |
| | THE DESIGN PRESSURES ARE NOT LISTED. |
| | THE DRAWINGS FOR THE PREMDOOR ENTERGY |
| | BRAND DOOR IS MISSING THE REPORT. |
| | |
| | 16) THE SITE SPECIFIC PRODUCT APPROVALS |
| | FOR THE NORANDEX MULLIONS REQUIRE THE |
| | EMBOSSED SEAL AND SIGNATURE OF THE |
| | ENGINEER THAT IS CERTIFYING THE PRODUCT |
| | IN ADDITION THAT OF THE DESIGNER OF |
| | RECORD. |
| | |
| | 17)PROVIDE ENGINEERING FOR BUTT GLASS |
| | ASSEMBLY. WHERE OTHER THAN FIRM SUPPORT |
| | ON ALL SIDES IS PROVIDED, DETAILED SHOP |
| | DRAWINGS, SPECIFICATIONS AND RATIONAL |
| | ANALYSIS AND/OR TEST DATA ASSURING SAFE |
| | PERFORMANCE FOR THE SPECIFIC APPLICATION |
| | SHALL BE PREPARED BY ENGINEERS |
| | EXPERIENCED IN THIS WORK. FBC 2406.2 |
| | |
| | 18) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - GLASS BLOCK |
| | |
| | 19)PROVIDE (2) PRODUCT APPROVALS, KEY |
| | PLANS AND INSTALLATION SCHEDULES |
| | INDICATING THE SPECIFIC TYPE OF |
| | FASTENER AND MOUNTING OPTIONS THAT WILL |
| | BE USED (CIRCLE OR HIGHLIGHT THESE ON |
| | THE PRODUCT APPROVAL DRAWINGS). THIS |
| | INFORMATION IS REQUIRED AT TIME OF |
| | PERMIT OR A SEPARATE PERMIT WILL BE |
| | REQUIRED WITH ADDITIONAL PERMIT FEES. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |