Plan Review Details - Permit 02060664
Plan Review Stops For Permit 02060664
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-10-03 Cont ID  
Sent By jwitmer Date 2002-10-03 Time 10:07 Rev Time 1.50
Received By tjonseck Date 2002-10-03 Time 10:07 Sent To  
Notes
2002-10-03 00:00:00 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 02060664
 ADDRESS: 228 9TH ST
 CONT: TERRY SPARKS
 TELL # (561)832-6407
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-09-27 Cont ID  
Sent By jwitmer Date 2002-09-19 Time 06:31 Rev Time 1.25
Received By jwitmer Date 2002-09-19 Time 06:30 Sent To  
Notes
2002-09-19 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02060664
 ADD: 228 9TH ST.
 CONT: TERRY SPARKS
 TEL: (561)538-5218
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) SHEET A-3 ENCLOSED ADDITION, WALL
 SECTION 1-A3 MISSING INFORMATION FOR THE
 ANCHORING OF THE BOTTOM PLATE, SIZE &
 SPACING. MISSING THE TYPE STRAP TO BE
 USED AT THE BOTTOM PLATE TO STUD.
  
 2)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 THE WIND IMPORTANCE FACTOR IS INCOR-
 RECT, MISSING THE INTERNAL PRESSURE
 COEFFICIENT (0.18).
  
 3) PLEASE INDICATE THE TYPE OF HOLD DOWN
 FASTENERS THAT WILL BE USED ON THE FRAM-
 ING NEXT TO WINDOWS & DOORS TO TAKE THE
 ADDITIONAL UPLIFT? 6'-0" + OPENING?
  
 4) FL BLD CODE 2405.2 HAZARDOUS LOCATION
 PROVIDE SAFETY GLASS FOR THESE LOCATIONS
 A) TUB
 B) SWING DOORS
  
 5) 424.17.1.9 WHERE A WALL OF A DWELLING
 SERVES AS A PART OF THE POOL BARRIER,
 SHOW SAFETY COMPLIANCE?
  
 *** 1 STORY COVERED PATIO ***
  
 1) COMPLIANCE WITH TABLE 600 ISSUES HAVE
 NOT BEEN MET!!! NO SURVEY, THE PLOT PLAN
 INDICATES THAT THE WALL NEXT TO THE PROP
 ERTY LINE IS APPROX. 7'-0". TABLE 600
 ALLOWABLE OPENINGS FOR 3'-10' AWAY FROM
 THE PROPERTY LINE IS 20% FOR THE WALL
 FACING THE PROPERTY LINE.
  
 A SOLUTION TO THE 20 % ALLOWABLE
 OPENINGS, BLOCK IN THE WALL TO THE 20%
 ALLOWABLE OPENINGS OR CREATE THE BARRIER
 (FIRE) AT THE PROPERTY LINE WITH A 6'-0"
 HIGH CBS WALL (WHERE THE FENCE IS). THIS
 DOES SATISFY THE 20% ALLOWABLE OPENINGS
 ALSO.
  
 2) 10" C-1 COLUMN DOESN'T INDICATE HOW
 THE TIE IN TO THE FOOTER OCCURS, REBAR
 LAP.
  
 3) INDICATE HOW THE LATERAL STABILITY
 FOR THE ENCLOSURE IS TO OCCUR?
  
 4) MISSING THE PRODUCT TESTING REPORT
 FOR THE ROOF TILE ASSEMBLIES!
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-08-13 Cont ID  
Sent By btrobaug Date 2002-08-12 Time 12:36 Rev Time 2.75
Received By jwitmer Date 2002-08-13 Time 15:30 Sent To  
Notes
2002-08-13 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02060664
 ADD: 228 9TH STREET
 CONT: TERRY SPARKS CONSTRUCTION
 TEL: (561)538-5218
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 *****BEDROOM/ BATH & EXERCISE ADD*****
  
 1) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
  
 2)PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION.
  
 3)FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 4)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 5) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.MISSING REPORTS:
 A) WINDOWS
 B) EXTERIOR DOORS W/ GLAZED OPENINGS
 C) STORM SHUTTERS
 D) ROOFING ASSEMBLIES
  
 6)SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD.
  
 7) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 8)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 10) 1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 11) FBC 1606.TRUSS & GIRDER LOADS,
 VERTICAL,HORIZONTAL AND GRAVITY LOADS,
 INDICATE ON TRUSS PLAN. INDICATE WITH
 ANCHOR SCHEDULE MANUFACTURE, MODEL &
 ALLOWABLE LOADS.
 1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
  
 12) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, A-3
 TYPICAL WALL SECTION INDICATES THE USE
 OF R-30 INSULATION, WILL NOT FIT INTO A
 2X6 STUD WALL.
  
 13) PLEASE INDICATE WHAT TYPE OF HOLD
 DOWN FASTENERS ARE TO BE USED ON SIDES
 WINDOWS & DOORS?
  
 14) WALL SECTION INDICATES THE USE OF
 WOOD SUB-SHEATHING,WIRE LATH & STUCCO.
 2304.2.5 TO PROVIDE A 6" AIR GAP BETWEEN
 GRADE AND SUBSHEATHING,AND STUCCO.
 STUCCO NO LONGER CAN DIE INTO THE SOILS
 WITH WOOD BACKING.
  
 15)FL BLD CODE 2309.6 ATTIC ACCESS, PRO-
 VIDE ATTIC ACCESS 20"X36".
  
 16)FL BLD CODE 2405.2 HAZARDOUS LOCATION
 PROVIDE SAFETY GLASS FOR THIS LOCATION:
 A) TUB
 B) SWING DOORS
  
 17) 424.17.1.9 WHERE A WALL OF A DWELL-
 ING SERVES AS PART OF THE POOL BARRIER,
 SHOW SAFETY COMPLIANCE.
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 ***1 STORY COVERED PATIO***
  
 1) SHOW COMPLIANCE WITH TABLE 600 ISSUE
 20 % OPENINGS.
  
 2) 1606.2.4.MAIN WIND FORCE RESISTING
 SYSTEM. PLANS ARE AT BEST A RENDERING
 OF AN OPEN COVERED PATIO. NO INFORMATION
 IS OFFERED AS TO HOW WIND LOADING IS
 TRANSFERRED FROM THE FOUNDATION THROUGH
 TO THE ROOF? NO DETAILS FOR BEAMS,
 ROOF FRAMING, SHEATHING, ROOF ASSEMBLIES
 ETC!!!!!!
  
 3) IS THERE AND EXISTING DOORWAY FROM
 THE BUILDING?
  
 NOTES IN GENERAL:
  
 1) THE FOUNTAIN IN FRONT YARD SHALL RE-
 QUIRE A SEPERATE PERMIT.
  
 2) FENCES AND EXTERIOR GARDEN OR PRIVACY
 WALLS REQUIRE A SEPERATE PERMIT, SUBMIT
 PLAN TO WATER DEPARTMENT FIRST FLOOR
 BEFORE SUBMITTING FOR PERMIT.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-09-19 Cont ID  
Sent By btrobaug Date 2002-09-19 Time 14:59 Rev Time 0.50
Received By btrobaug Date 2002-09-19 Time 08:53 Sent To  
Notes
2002-09-19 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE LOAD CALCULATIONS
 SHOWING EXISTING AND ALL ADDITIONAL
 LOADS,AND INDICATE THE SIZE OF THE
 EXISTING SERVICE,BEFORE ROUGH INSPECTION
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-08-12 Cont ID  
Sent By btrobaug Date 2002-08-12 Time 12:35 Rev Time 0.00
Received By btrobaug Date 2002-08-12 Time 12:35 Sent To B
Notes
2002-08-12 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE SEE NOTES FROM LAST REVIEW
 ATTACHED.NONE OF THE ITEMS WERE
 ADDRESSED ON THIS RESUB.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8093 EXT.8392

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-06-20 Cont ID  
Sent By btrobaug Date 2002-06-20 Time 07:59 Rev Time 0.00
Received By btrobaug Date 2002-06-20 Time 07:45 Sent To Z
Notes
2002-06-20 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND RESUBMIT FOR REVIEW.
  
 1} PLEASE PROVIDE A LOAD CALCULATION
 SHOWING EXISTING AND ALL ADDED LOADS.
  
 2} PLEASE LIST THE REQ,D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 3} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL;
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-08-12 Cont ID  
Sent By kstevens Date 2002-08-12 Time 11:51 Rev Time 0.00
Received By kstevens Date 2002-08-12 Time 11:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-06-18 Cont ID  
Sent By jleech Date 2002-06-18 Time 20:16 Rev Time 0.33
Received By jleech Date 2002-06-18 Time 20:16 Sent To  
Notes
2002-06-18 00:00:00PROVISO;
 PLUMBING PERMIT COVERS WORK SHOWN ON
 PLANS. IF WORK IS TO BE DONE IN EXISTING
 HOME ADDITIONAL INFORMATION IS REQUIRED.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-07-29 Cont ID  
Sent By btrobaug Date 2002-08-12 Time 12:16 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-07-29 00:00:00APPROVED BY A.GIANNIOTES