Plan Review Details - Permit 02060592
Plan Review Stops For Permit 02060592
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-07-12 Cont ID  
Sent By bstaples Date 2002-07-12 Time 14:08 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-06-20 Cont ID  
Sent By hpiskura Date 2002-06-20 Time 15:55 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-06-20 00:00:00THE TWO REMAINING EXIT ACCESS DOORS DO
 NOT MEET THE SEPARATION REQUIREMENTS OF
 FBC 1004.1.4.
  
 THE DECLARED $53500 PERMIT VALUATION
 APPEARS TOO LOW FOR THIS SCOPE OF WORK.
 PLEASE PROVIDE A COPY OF THE SIGNED
 CONTRACT AND A DETAILED TAKEOFF
 INCLUDING EXTENSIONS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-07-17 Cont ID  
Sent By dpalmer Date 2002-07-17 Time 07:11 Rev Time 0.00
Received By dpalmer Date 2002-07-17 Time 07:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-27 Cont ID  
Sent By dpalmer Date 2002-06-27 Time 11:42 Rev Time 0.00
Received By dpalmer Date 2002-06-27 Time 08:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-07-16 Cont ID  
Sent By mcarsill Date 2002-07-16 Time 11:21 Rev Time 0.00
Received By mcarsill Date 2002-07-16 Time 11:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-07-02 Cont ID  
Sent By mcarsill Date 2002-07-02 Time 08:53 Rev Time 0.00
Received By mcarsill Date 2002-07-02 Time 08:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-07-17 Cont ID  
Sent By ndenmark Date 2002-07-17 Time 12:47 Rev Time 0.33
Received By ndenmark Date 2002-07-17 Time 12:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-06-22 Cont ID  
Sent By pkrauss Date 2002-06-22 Time 09:54 Rev Time 0.35
Received By pkrauss Date 2002-06-22 Time 09:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-07-18 Cont ID  
Sent By kstevens Date 2002-07-18 Time 11:15 Rev Time 0.00
Received By kstevens Date 2002-07-18 Time 11:15 Sent To  
Notes
2002-07-18 00:00:00PASSED/PROVIS0
  
 WATER HAMMER ARRESTOR SHALL BE LOCATED
 NEAR FIXTURES NOT AT TOP OF DROP AS
 SHOWN

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-06-28 Cont ID  
Sent By kstevens Date 2002-06-28 Time 15:12 Rev Time 0.00
Received By kstevens Date 2002-06-28 Time 15:12 Sent To  
Notes
2002-06-28 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) PER TABLE 403.1 A DRINKING FOUNTAIN
 AND A SERVICE SINK ARE REQUIRED. IF SAID
 FIXTURES ARE LOCATED IN THE COMMON AREA
 PLEASE CALL THEM OUT ON THE PLANS.
 2) SHT A-3.0 ICE MAKER. SUBMIT DETAIL
 SHOWING HOW THE ICE MAKER SHALL BE
 DRAINED. IF CONNECTED WITH A PUMP AN AIR
 GAP FITTING SHALL BE REQUIRED LIKE THE
 DISHWASHER.
 3) SHT P-1 WATER ISOMETRIC, WATER HAMMER
 ARRESTOR SHALL BE LOCATED NEAR THE FIX-
 TURES IN AN "EFFECTIVE RANGE" PER PDI-WH
 201 AND MANUF INSTALLATION INSTRUCTIONS
 NOT AT TOP OF DROP AS SHOWN.
 4) SHT P-1 WATER ISOMETRIC, PLEASE PRO-
 VIDE MANUFACTURE INFORMATION FOR INSTA-
 HOT. PRODUCT APPROVAL REQUIRES LISTING
 FROM AN APPROVED TESTING AGENCY. (UL)
 5) SHT P-1 PLUMBING NOTES #13 AIR CHAMB-
 ERS NOT APPROVED. DELETE NOTE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377