Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-06-14 Cont ID  
Sent By btrobaug Date 2002-06-14 Time 17:20 Rev Time 0.00
Received By btrobaug Date 2002-06-14 Time 16:08 Sent To FIRE
Notes
2002-06-14 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND RESUBMIT FOR REVIEW.
  
 1} WHAT IS THE GENERATORS PRIME MOVER?
 IF FUEL SHOW TANK LOCATION.
  
 2} GIVE GENERATOR OUTPUT-KVA,VOLTS,PHASE
  
 3} INDICATE HOW GENERATOR IS GROUNDED.
  
 4} IS GENERATOR BEING USED AS A
 SEPERATELY DERIVED SYSTEM?
  
 5} WHERE DO CONDUITS 4,5 & 6 GO?
  
 6} SHOW PHYSICAL LOCATION OF THE
 GENERATOR AND ANY FUEL TANKS BEING
 USED,ON A DRAWING.
  
 7} SHOW GROUPING OF DISCONNECTS ON
 DRAWING.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-06-18 Cont ID  
Sent By btrobaug Date 2002-06-17 Time 08:48 Rev Time 0.00
Received By mcarsill Date 2002-06-18 Time 15:03 Sent To  
Notes
2002-06-18 00:00:001) INSUFFICIENT INFORMATION PROVIDED
 TO DO PLAN REVIEW. PLEASE SEE
 ELECTRICAL PLAN REVIEW COMMENTS.
 PLEASE PROVIDE MORE DETAILS AND
 INFORMATION SO AN ADEQUATE PLAN REVIEW
 CAN BE PERFORMED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910