| Plan Review Stops For Permit 02060579 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-06-14 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-06-14 |
Time |
17:20 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-06-14 |
Time |
16:08 |
Sent To |
FIRE |
|
| Notes |
| 2002-06-14 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION AND RESUBMIT FOR REVIEW. | | | | | | 1} WHAT IS THE GENERATORS PRIME MOVER? | | | IF FUEL SHOW TANK LOCATION. | | | | | | 2} GIVE GENERATOR OUTPUT-KVA,VOLTS,PHASE | | | | | | 3} INDICATE HOW GENERATOR IS GROUNDED. | | | | | | 4} IS GENERATOR BEING USED AS A | | | SEPERATELY DERIVED SYSTEM? | | | | | | 5} WHERE DO CONDUITS 4,5 & 6 GO? | | | | | | 6} SHOW PHYSICAL LOCATION OF THE | | | GENERATOR AND ANY FUEL TANKS BEING | | | USED,ON A DRAWING. | | | | | | 7} SHOW GROUPING OF DISCONNECTS ON | | | DRAWING. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-06-18 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-06-17 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-06-18 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2002-06-18 00:00:00 | 1) INSUFFICIENT INFORMATION PROVIDED | | | TO DO PLAN REVIEW. PLEASE SEE | | | ELECTRICAL PLAN REVIEW COMMENTS. | | | PLEASE PROVIDE MORE DETAILS AND | | | INFORMATION SO AN ADEQUATE PLAN REVIEW | | | CAN BE PERFORMED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|