Plan Review Details - Permit 02060575
Plan Review Stops For Permit 02060575
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-19 Cont ID  
Sent By pkrauss Date 2002-06-18 Time 14:39 Rev Time 0.00
Received By btrobaug Date 2002-06-19 Time 17:46 Sent To R
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-06-18 Cont ID  
Sent By pkrauss Date 2002-06-18 Time 14:36 Rev Time 0.35
Received By pkrauss Date 2002-06-18 Time 14:29 Sent To E
Notes
2002-06-18 00:00:00PROVISO:MECHANICAL PERMIT 02060589
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 OVERFLOW PROTECTION REQUIRED AS PER
 2001 FBC(M) 307.2.3.
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 SHOULD GAS DRYERS BE INSTALLED -
 SHOW COMPLIANCE FOR COMBUSTION AIR AS
 PER 2001 FBC(M) CHAPTER 7.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-08-05 Cont ID  
Sent By kstevens Date 2002-08-05 Time 19:47 Rev Time 0.00
Received By kstevens Date 2002-08-05 Time 19:47 Sent To  
Notes
2002-08-05 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-07-24 Cont ID  
Sent By kstevens Date 2002-07-24 Time 09:48 Rev Time 0.00
Received By kstevens Date 2002-07-24 Time 09:48 Sent To  
Notes
2002-07-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHOWER IN CABANA BATH AND TUB IN BATH
 #3 NOT VENTED. THE WET VENT SHALL BE
 CONSIDERED THE VENT FOR THE FIXTURES AND
 SHALL EXTEND FROM THE CONNECTION OF THE
 DRY VENT ALONG THE DIRECTION OF THE FLOW
 IN THE DRAIN PIPE TO THE MOST DOWNSTREAM
 FIXTURE DRAIN CONNECTION TO THE HORIZ-
 ONTAL BRANCH DRAIN. 909.1 SINCE THE DRY
 VENT STARTS ABOVE THE LAVS AND THE LAVS
 ARE THE MOST DOWNSTREAM FIXTURE DRAIN
 CONNECTION, THE SHOWER/TUB ARE NOT VENT-
 ED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-06-15 Cont ID  
Sent By jleech Date 2002-06-15 Time 11:46 Rev Time 0.33
Received By jleech Date 2002-06-15 Time 11:46 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-07-02 Cont ID  
Sent By btrobaug Date 2002-06-19 Time 17:46 Rev Time 2.50
Received By lhatten Date 2002-07-01 Time 07:28 Sent To  
Notes
2002-07-02 00:00:00REVIEW & STAMPED PLANS 07/01/2002
 CALC. FEES & PRINT CARDS 07/02/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-06-18 Cont ID  
Sent By sgraham Date 2002-06-18 Time 07:50 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***