Plan Review Details - Permit 02060553
Plan Review Stops For Permit 02060553
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-19 Cont ID  
Sent By pkrauss Date 2002-06-18 Time 14:15 Rev Time 0.00
Received By btrobaug Date 2002-06-19 Time 13:01 Sent To R
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-12-11 Cont ID  
Sent By rregueir Date 2002-12-11 Time 17:22 Rev Time 0.50
Received By rregueir Date 2002-12-11 Time 17:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-08-05 Cont ID  
Sent By pkrauss Date 2002-08-05 Time 08:15 Rev Time 0.35
Received By pkrauss Date 2002-08-05 Time 07:35 Sent To  
Notes
2002-08-05 00:00:00PROVISO:MECHANICAL PERMIT 02060635
  
 WHERE MULTIPLE AIR HANDLING SYSTEMS
 SHARE A COMMON SUPPLY OR RETURN AIR
 DUCTS OR PLENUMS WITH A COMBINED DESIGN
 CAPACITY GREATER THAN 2,000 CFM, THE
 RETURN & SUPPLY AIR SYSTEM SHALL BE
 PROVIDED WITH SMOKE DETECTORS IN
 ACCORDANCE WITH SECTION 606.2.1.
  
 SMOKE DETECTORS SHALL BE INSTALLED
 SUPPLY SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY
 AIR DUCT. 2001 FBC(M) 606.2.1OR
 UPON ACTIVATION, THE SMOKE DETECTORS
 SHALL SHUTDOWN THE AIR DISTRIBUTION
 SYSTEM. 2001 FBC(M) 606.4
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-06-18 Cont ID  
Sent By pkrauss Date 2002-06-18 Time 14:02 Rev Time 0.40
Received By pkrauss Date 2002-06-18 Time 13:48 Sent To E
Notes
2002-06-18 00:00:00PROVISO:MECHANICAL PERMIT 02060635
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 OVERFLOW PROTECTION REQUIRED AS PER
 2001 FBC(M) 307.2.3.
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-08-02 Cont ID  
Sent By kstevens Date 2002-08-02 Time 17:41 Rev Time 0.00
Received By kstevens Date 2002-08-02 Time 17:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-06-15 Cont ID  
Sent By jleech Date 2002-06-15 Time 11:10 Rev Time 0.33
Received By jleech Date 2002-06-15 Time 11:10 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-08-02 Cont ID  
Sent By rmcdouga Date 2002-08-02 Time 15:34 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-08-02 00:00:00************BUILDING PROVISO************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PROVIDE A SOIL BEARING TEST REPORT
 PER CITY AMENDMENTS TO 2001 FBC SECTION
 1804.2.2, PRIOR TO POURING FOUNDATION.
  
 3) THE STORM PANEL INSTALLATION SCHEDULE
 IS MISSING ONE OF THE SECOND FLOOR
 WINDOWS. SUBMIT A REVISED SCHEDULE PRIOR
 TO INSTALLATION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-07-08 Cont ID  
Sent By btrobaug Date 2002-06-19 Time 13:46 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-07-08 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) STRUCTURE IS LOCATED IN AN "A8" FLOOD
 ZONE, AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 3) PROVIDE A SOIL BEARING REPORT PER
 CITY AMENDMENTS TO THE 2001 FBC 1804.2.2
  
 4) INDICATE THE APPLICABLE INTERNAL
 PRESSURE COEFFICIENT AND THE BASIC WIND
 PRESSURE ON THE PLANS AS REQUIRED BY THE
 FBC SEC. 1606.1.7.
  
 5) PLEASE CORRECT #1 UNDER FOUNDATION
 NOTES TO 0.006 POLYETHELENE (6 MIL.) AS
 REQUIRED BY FBC 1909.2.
  
 6) OPENINGS FROM A GARAGE DIRECTLY INTO
 A ROOM USED FOR SLEEPING PURPOSES IS NOT
 PERMITTED PER FBC 411.2.8. THE BONUS
 ROOM IS REQUIRED TO BE PERMANENTLY
 MARKED ON THE PLANS THAT IT IS NOT TO BE
 USED FOR SLEEPING PURPOSES.
  
 7) THE WINDOW (H) IN THE FIRST FLOOR
 BATH ROOM IS REQUIRED TO HAVE TEMPERED
 GLASS PER 2405.2.1.
  
 8) PLEASE CHANGE NOTE 6 UNDER GENERAL
 NOTES ON SHEET A-2 TO REFERENCE THE
 2001 FLORIDA PLUMBING CODE.
  
 9) PLEASE PROVIDE SURVEY WITH THE SIDE
 SET BACK DIMENSIONS LISTED.
  
 10) THE NAIL SIZE AND SPACING LISTED FOR
 THE SECOND STORY FLOOR DIAPHRAM AT
 SECTION 2 ON SHEET S-2 DOES NOT
 CORRESPOND TO THAT LISTED IN THE
 DIAPHRAM SCHEDULE. PLEASE CORRECT.
  
 11) THE A/C AREA LISTED ON THE PLANS
 DIFFERS FROM THE CONDITIONED AREA GIVEN
 ON THE ENERGY CALCULATIONS. PLEASE
 CORRECT.
  
 12) INDICATE ON THE PLANS THAT THE BONUS
 ROOM WALLS ARE INSULATED.
  
 13) PLEASE REVIEW THE AREA OF WOOD FRAME
 WALL ADJACENT TO UNCONDITIONED SPACE
 GIVEN ON THE ENERGY FORM AND CORRECT.
  
 14) INDICATE HOW FIREBLOCKING AT THE TOP
 OF THE STAIR RUN WILL BE ACHIEVED. SEE
 FBC 2305.1.4.
  
 15) INDICATE DRAFTSTOPPING LOCATIONS AND
 MATERIAL FOR THE ROOF/CEILING ASSEMBLY
 AS REQUIRED BY FBC 2305.2.2.
  
 16) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - FRONT DOOR WITHOUT SIDELITES
 - STRUCTURAL MULLIONS
 - SINGLE HUNG WINDOWS (THE COVER PAGE OF
 THOSE SUBMITTED HAS A DIFFERENT
 ACCEPTANCE NUMBER THAN THE OTHER PAGES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2002-06-18 Cont ID  
Sent By sgraham Date 2002-06-18 Time 07:47 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***