Plan Review Details - Permit 02060519
Plan Review Stops For Permit 02060519
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-09-06 Cont ID  
Sent By rbrown Date 2002-09-06 Time 15:42 Rev Time 0.00
Received By rbrown Date 2002-09-06 Time 15:42 Sent To  
Notes
2002-09-06 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) BEFORE A PERMIT COULD BE ISSUED THE
 OUTSTANDING MONIES OWED TO THE CITY OF
 WEST PALM BEACH SHALL BE PAID TO
 ADDRESS THE 'HOLDS' LISTED ON THE
 ATTACHED PRINTOUT.
  
 2) FBC 3401.7.2REPAIRS TO AN EXISTING
 BUILDING. THE PLANS DO NOT MAKE IT CLEAR
 AS TO WHAT IS NEW AND WHAT IS EXISTING
 CONSTRUCTION.ARE THE ROOM SIZES/LAYOUT
 AND ROOM USE DESIGNATIONS ALTERED FROM
 EXISTING?ANNOTATE THE PLANS TO
 CLARIFY WHAT IS EXISTING.THE TYPICAL
 WALL SECTION ON SHEET 4 INDICATES
 EXTENSIVE WORK TO BE CARRIED OUT, YET
 THE APPLIED VALUATION OF THE WORK IS
 JUST $2400 (NOTE: THE PLANS WERE LEFT AT
 THIS OFFICE ON 8/23/02 WITHOUT AN
 APPLICATION FORM FROM WHICH TO VERIFY
 THE VALUE OF THE WORK).AMEND THE
 VALUATION TO CORRELATE WITH THE EXTENT
 OF THE WORK SHOWN ON THE PLANS.
  
 3) FBC 3401.7.2THE REQUIRED DEGREE OF
 COMPLIANCE WITH THE CURRENT BUILDING
 CODE WILL BE DETERMINED BY COMPARING THE
 COST OF THE REPAIRS/ALTERATIONS AGAINST
 THE VALUE OF THE EXISTING BUILDING.
 THEREFOR, A FULL REVIEW CANNOT BE
 CARRIED OUT UNTIL COMMENT 2 (ABOVE) HAS
 BEEN ADDRESSED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-09-11 Cont ID  
Sent By btrobaug Date 2002-09-11 Time 11:10 Rev Time 1.00
Received By btrobaug Date 2002-09-11 Time 09:42 Sent To P
Notes
2002-09-11 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY
 CORRECTIONS TO THE PLANS AND RESUBMIT
 FOR REVIEW.
  
 1} PLEASE PROVIDE INFORMATION AS TO
 HOW THE PERMIT VALUATION WAS
 ESTABLISHED PER 104.6.5 CWPB
 AMMENDMENTS(ATTACHED).
  
 2} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 3} PLEASE INDICATE THE LOCATION OF THE
 SERVICE EQUIPMENT ON THE PLAN.
  
 4} INDICATE THE SIZE OF THE CONDUIT AND
 WIRE BETWEEN THE METER AND THE PANEL.
  
 5} PLEASE NOTE THE OCP FOR THE WATER
 HEATER MUST COMPLY WITH 422-11(E)(3).
  
 6} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 7} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
  
 8} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STAIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 9} ALL LOW VOLTAGE TO BE INSTALLED MUST
 BE SHOWN ON DRAWING.
  
 10} ELECTRICAL PERMIT IS REQUIRED.
  
 11} PLEASE NOTE THAT ALL PLANS
 THAT ARE SIGNED AND SEALED BY ARCH/ OR
 ENGINEER ARE REQ`D PER 61G15-23.002 FOR
 ENGINEER AND 61G1-16.004 FOR ARCH.
 SHALL HAVE A TITLE BLOCK.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-09-16 Cont ID  
Sent By btrobaug Date 2002-10-09 Time 15:01 Rev Time 0.00
Received By kstevens Date 2002-09-16 Time 09:48 Sent To  
Notes
2002-09-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME. ADDRESS AND NUMBER ON EACH
 SHEET. A TITLE BLOCK ON EACH SHEET CON-
 TAINING THE PRINTED NAME, ADDRESS, AND
 NUMBER OF THE ENGINEER OR ENGINEERING
 BUSINESS WILL SATISFY THIS REQUIREMENT.
 61G15-23.002(2)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***