| 2002-09-11 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | |
| | PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION,MAKE ANY NECESSARY |
| | CORRECTIONS TO THE PLANS AND RESUBMIT |
| | FOR REVIEW. |
| | |
| | 1} PLEASE PROVIDE INFORMATION AS TO |
| | HOW THE PERMIT VALUATION WAS |
| | ESTABLISHED PER 104.6.5 CWPB |
| | AMMENDMENTS(ATTACHED). |
| | |
| | 2} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE OR NOTE ON PLANS FOR BRANCH |
| | CIRCUIT PROTECTION. PER 210-12 |
| | |
| | 3} PLEASE INDICATE THE LOCATION OF THE |
| | SERVICE EQUIPMENT ON THE PLAN. |
| | |
| | 4} INDICATE THE SIZE OF THE CONDUIT AND |
| | WIRE BETWEEN THE METER AND THE PANEL. |
| | |
| | 5} PLEASE NOTE THE OCP FOR THE WATER |
| | HEATER MUST COMPLY WITH 422-11(E)(3). |
| | |
| | 6} PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | |
| | 7} PLEASE NOTE FRONT AND REAR |
| | RECEPTS REQ`D PER 210-52E |
| | |
| | 8} SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | IN THE VICINITY OF BEDROOMS AND CLOSE |
| | PROXIMITY OF STAIRWAYS. 2-5.2.1.3 |
| | 3'FT FROM BATHS/KITCHENS.2-5.2.1.6 |
| | |
| | 9} ALL LOW VOLTAGE TO BE INSTALLED MUST |
| | BE SHOWN ON DRAWING. |
| | |
| | 10} ELECTRICAL PERMIT IS REQUIRED. |
| | |
| | 11} PLEASE NOTE THAT ALL PLANS |
| | THAT ARE SIGNED AND SEALED BY ARCH/ OR |
| | ENGINEER ARE REQ`D PER 61G15-23.002 FOR |
| | ENGINEER AND 61G1-16.004 FOR ARCH. |
| | SHALL HAVE A TITLE BLOCK. |
| | |