Plan Review Details - Permit 02060515
Plan Review Stops For Permit 02060515
Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-07-09 Cont ID  
Sent By ndenmark Date 2002-07-09 Time 08:26 Rev Time 0.25
Received By ndenmark Date 2002-07-09 Time 08:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-13 Cont ID  
Sent By pkrauss Date 2002-06-12 Time 16:51 Rev Time 0.35
Received By pkrauss Date 2002-06-12 Time 16:49 Sent To  
Notes
2002-06-12 00:00:00 
 PROVIDE MANUFACTURER SPECS ON THE
 EQUIPMENT (LINE SIZE) AT JOBSITE FOR
 INSPECTION.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-06-12 Cont ID  
Sent By ndenmark Date 2002-06-12 Time 06:16 Rev Time 0.25
Received By ndenmark Date 2002-06-12 Time 06:16 Sent To  
Notes
2002-06-12 00:00:00DENIED:
  
 PROVIDE DUCT SIZES
 PROVIDE INFORMATION ON ROOF STANDS
 IF THIS AREA IS PREVIOUSLY NOT
 CONDITIONED, PROVIDE ENERGY CALCS PER
 FBC 13-101.5 (FLORIDA ENERGY EFFICIENCY
 CODE)