Plan Review Details - Permit 02060509
Plan Review Stops For Permit 02060509
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-08-07 Cont ID  
Sent By jwitmer Date 2002-08-07 Time 14:41 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-06-24 Cont ID  
Sent By btrobaug Date 2002-08-06 Time 07:20 Rev Time 0.76
Received By jwitmer Date   Time   Sent To  
Notes
2002-06-24 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02060509
 ADD: 7592 IRONHORSE BLVD
 CONT: ANTHONY & SYLVAN
 TEL: 686-7946
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)1803.1.3 EXCAVATION FOR ANY PURPOSE
 SHALL NOT EXTEND WITHIN 1 FT OF THE
 ANGLE OF REPOSE OR NARURAL SLOPE OF THE
 SOIL UNDER ANY FOOTING OR FOUNDATION,
 UNLESS SUCH FOOTING OR FOUNDATION IS
 FIRST PROPERLY UNDERPINNED OR PROTECTED
 AGAINST SETTLEMENT. INDICATE WHAT TYPE
 OF PROTECTION SHALL BE USED AGAINST
 SETTLMENT?
  
 2) CHAP.13-612.ABC2.3.2 COVERS REQUIRED
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO MINI-
 MIZE HEAT LOSS.
  
 4) FBC-2001 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. (DETAIL)
  
 5) FBC 424.2.17.1.9 WHERE A WALL OR
 DWELLING SERVES AS PART OF THE BARRIER,
 PROVIDE INFORMATION AS TO HOW PROTECTION
 OF OPENINGS SHALL BE MAINTAINED?
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-08-06 Cont ID  
Sent By btrobaug Date 2002-08-06 Time 07:20 Rev Time 0.00
Received By btrobaug Date 2002-08-06 Time 06:58 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-06-20 Cont ID  
Sent By kstevens Date 2002-08-05 Time 18:12 Rev Time 0.00
Received By btrobaug Date 2002-06-20 Time 07:15 Sent To B
Notes
2002-06-20 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE A LOAD CALCULATION FOR
 THE SERVICE FEEDING THE NEW EQUIPMENT
 INCLUDING ALL ADDITIONAL LOADS,AND
 RESUBMIT FOR REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-08-05 Cont ID  
Sent By kstevens Date 2002-08-05 Time 18:12 Rev Time 0.00
Received By kstevens Date 2002-08-05 Time 18:12 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-06-19 Cont ID  
Sent By kstevens Date 2002-06-19 Time 10:01 Rev Time 0.00
Received By kstevens Date 2002-06-19 Time 10:01 Sent To E
Notes
2002-06-19 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL) PLANS SHOW 1"
 VENT PIPE CALCULATIONS FOR 1 HP PUMP. A
 2 HP PUMP IS BEING USED. PLEASE SUBMIT
 CALCULATIONS FOR 2 HP PUMP.
 2) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 3) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-06-14 Cont ID  
Sent By sgraham Date 2002-06-14 Time 07:35 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***